Plan Review Notes
Plan Review Notes For Permit 07030640
Permit Number 07030640
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-20 20:04:51ROUTED BACK TO ZONING.
2007-03-20 20:04:28*** UNSAT ***
  
 6623 SPARROW HAWK DR.
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS
 SUBMITTED).
 2005 NFPA-70 (NEC).
 2002 NFPA-72
 2003 NFPA-101
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE 2004 FBC W/2006 FOR NOTE REQUIRED
 FOR TYPE OF RECESSED LIGHTING FIXTURES PER
 13-606.1.ABC.1.2.4
  
 3) NOTE: PLEASE SEE 250.53G AS THE MINIMUM SIZE OF THE
 GROUND ROD SHALL BE 8FT MINIMUM.
  
 4) NOTE: PLEASE SEE THE COMPRESSOR FOR THE A/C CU IS
 BEING SHOWN WITH A LOAD OF 9.8KW; PLEASE VERIFY THIS AS
 THIS LOAD EXCEED THAT OF THE RATING OF THE CIRCUIT
 BREAKER.
 THIS WAS REDLINED ON PREVIOUS PLANS ON MANY OCCASIONS
 BUT TO DATE NO CHANGES HAVE BEEN MADE.
  
 5) NOTE: PLEASE SEE THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THE GENERAL USE OF THE SD FOR SMOKE DETECTORS WAS
 ALWAYS ACCEPTEDHOWEVER BASED ON THE DEFINITIONS AS
 STATED IN NFPA-72 A SD/ SMOKE DETECTOR IS ONLY A DEVICE
 WHICH WILL DETECT AND WILL NOT SOUND AN AUDIBLE ALARM.
 THIS WOULD BE DONE BY HORN/SIREN TYPE DEVICES. PLEASE
 SEE THE DEFINITIONS OF SA/SMOKE ALARMS; THESE ARE
 DEVICES WHICH ARE 120V (AS SHOWN) AND WOULD DETECT AND
 SOUND AN ALARM. THIS IS SOMETHING THAT IS NOW BEING
 COMMENTED ON OTHER REVIEWS FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 6) NOTE: PLEASE SEE THAT UNDER THE NEW 2005 NEC
 210.8A7, ALL 15/20 AMP 125V RECEPTACLES WITHIN 6FT OF
 SINKS SHALL CONTAIN GFI PROTECTION EVEN LAUNDRY ROOMS
 AND WASHING MACHINES LOCATED WITHIN 6FT EVEN IF THEY
 ARE ON A DEDICATED/SINGLE RECEPTACLE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  