Plan Review Notes
Plan Review Notes For Permit 07030640
Permit Number 07030640
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-19 16:47:12 
  
 DENIED
  
  
 1)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE NOTE
 ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA BUILDING
 CODE WITH 2006 REVISIONS
  
 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO
 BUILDING PER 1603.1.4 FBC
  
 3)PROVIDE TYPE OF CONSTRUCTION AND OCCUPANCY GROUP ON
 PLANS
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.VALUE ADJUSTED TO $359,745 WHICH
 INCREASES THE PERMIT FEE. BALANCE DUE IS $123.14.
  
 5)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004
  
 6)PLAN, ELEVATION AND DOOR, WINDOW SCHEDULE DO NOT
 MATCH.LIVINGROOM ELEVATION HAS 1 WINDOW SCHEDULE HAS
 2 AND NO MULLION STATED FOR LIVINGROOM OR MASTER
 SUITE.
  
 7)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT AND
 ROOF PITCH. THE PITCH ON 1/D1 MAY BE CORRECT BUT DETAIL
 IS TYPICAL DETAIL SO IN MAY NOT BE FOR THIS PARTICULAR
 BUILDING.
  
 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 9)NOA FOR PRE-CAST LINTELS IS INCORRECT SUBMITTED NOA
 IS FOR 4, 6 AND 12" WIDE BLOCK APPLICATIONS PROVIDE
 MIAMI-DADE NOA # 03-0605.05 FOR 8" LINTELS
  
 10)GLASS BLOCK MEETS THE DESIGN PRESSURES REQUIRED
 BUT IS ONLY SMALL MISSILE IMPACT RATED. PER 1609.1.4
 FBC GLAZING WITHIN THE FIRST 30 FEET FROM GRADE ARE
 REQUIRED TO MEET LARGE MISSILE IMPACT TEST REQUIREMENTS
 THEREFORE THESE OPENINGS WILL REQUIRE AN IMPACT
 PROTECTION SYSTEM.
  
 11)PROVIDE LINTEL SCHEDULE THAT SHOW LINTELS MEET THE
 REQUIREMENTS OF 2104.5 FBC FOR MIN END BEARING
  
 12)WINDOW #4 FROM SCHEDULE 48"X101" EXCEEDS THE MAX
 SQUARE FOOTAGE STATED IN THE PGT PRODUCT APPROVAL NOA
 FOR FIXED WINDOWS MAX. SQ.FT. = 32, WINDOW IS 33.66667
 SQ. FT.
  
 13)PRODUCT APPROVAL FOR HANSON ROOF TILE REQUIRES
 ANSWERS TO NOTE #7 IN ORDER TO CALCULATE MOMENT OF
 UPLIFT FOR TILE.
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
  
 BLDG PLAN REVIEW