2007-04-19 16:47:12 | |
| |
| DENIED |
| |
| |
| 1)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE NOTE |
| ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA BUILDING |
| CODE WITH 2006 REVISIONS |
| |
| 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO |
| BUILDING PER 1603.1.4 FBC |
| |
| 3)PROVIDE TYPE OF CONSTRUCTION AND OCCUPANCY GROUP ON |
| PLANS |
| |
| 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC*.VALUE ADJUSTED TO $359,745 WHICH |
| INCREASES THE PERMIT FEE. BALANCE DUE IS $123.14. |
| |
| 5)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| PRACTICE UNDER CHAPTER 481 OR 471 OF |
| THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, |
| SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS |
| PER 106.1 FBC 2004 |
| |
| 6)PLAN, ELEVATION AND DOOR, WINDOW SCHEDULE DO NOT |
| MATCH.LIVINGROOM ELEVATION HAS 1 WINDOW SCHEDULE HAS |
| 2 AND NO MULLION STATED FOR LIVINGROOM OR MASTER |
| SUITE. |
| |
| 7)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT AND |
| ROOF PITCH. THE PITCH ON 1/D1 MAY BE CORRECT BUT DETAIL |
| IS TYPICAL DETAIL SO IN MAY NOT BE FOR THIS PARTICULAR |
| BUILDING. |
| |
| 8)SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD |
| |
| 9)NOA FOR PRE-CAST LINTELS IS INCORRECT SUBMITTED NOA |
| IS FOR 4, 6 AND 12" WIDE BLOCK APPLICATIONS PROVIDE |
| MIAMI-DADE NOA # 03-0605.05 FOR 8" LINTELS |
| |
| 10)GLASS BLOCK MEETS THE DESIGN PRESSURES REQUIRED |
| BUT IS ONLY SMALL MISSILE IMPACT RATED. PER 1609.1.4 |
| FBC GLAZING WITHIN THE FIRST 30 FEET FROM GRADE ARE |
| REQUIRED TO MEET LARGE MISSILE IMPACT TEST REQUIREMENTS |
| THEREFORE THESE OPENINGS WILL REQUIRE AN IMPACT |
| PROTECTION SYSTEM. |
| |
| 11)PROVIDE LINTEL SCHEDULE THAT SHOW LINTELS MEET THE |
| REQUIREMENTS OF 2104.5 FBC FOR MIN END BEARING |
| |
| 12)WINDOW #4 FROM SCHEDULE 48"X101" EXCEEDS THE MAX |
| SQUARE FOOTAGE STATED IN THE PGT PRODUCT APPROVAL NOA |
| FOR FIXED WINDOWS MAX. SQ.FT. = 32, WINDOW IS 33.66667 |
| SQ. FT. |
| |
| 13)PRODUCT APPROVAL FOR HANSON ROOF TILE REQUIRES |
| ANSWERS TO NOTE #7 IN ORDER TO CALCULATE MOMENT OF |
| UPLIFT FOR TILE. |
| |
| |
| NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| FBC* = WEST PALM BEACH ADMINISTRATIVE |
| AMENDMENTS TO FBC |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| |