2007-03-26 13:16:55DENIED BY BUILDING
  
 1)THE NOA FOR THE JOHNS MANVILLE BUILT-UP ROOF SYSTEM
 SPECIFIES A MAXIMUM DESIGN PRESSURE OF -52.5 PSF FOR
 THE SELECTED SYSTEM, WHICH IS TO LOW FOR ROOF ZONES 2
 AND 3. ENHANCED FASTENING IS ALLOWED IN ORDER TO
 INCREASE THE DESIGN PRESSURES IN THESE AREAS PER
 GENERAL LIMITATION NUMBER 7 ON PAGE 19 OF THE NOA.
 HOWEVER, GENERAL LIMITATION NUMBER 7 REQUIRES THAT RAS
 117 CALCULATIONS PREPARED, SIGNED AND SEALED BY A
 FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED
 ROOF CONSULTANT. SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS.
  