2007-06-20 13:28:24-----------DENIED--------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PG LS2.1.4: PLEASE PROVIDE SPECIFIC LOCATION, SIZE AND
 INSTALLATION DETAIL FOR THE FIRE DAMPER IN OFFICE
 STORAGE AREA PER FBC,M 607.8. ALSO, SEE FBC,M 607.2
 REGARDING FIRE DAMPER INSTALLATION INSTRUCTIONS.
 CONSULT FIRE DAMPER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR FRAMED WALL OPENING REQUIREMENTS AND
 INCLUDE WALL OPENING FRAMING DETAIL ON PLANS. FBC
 106.1.2
  