2007-06-22 18:32:46 | *** UNSAT2ND REVIEW *** |
| |
| ** PLEASE SEE THERE ARE STILL SOME NOTES FROM PREVIOUS |
| REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| |
| |
| 1) NOTE: PLEASE SEE MOST OF THE CODES WERE ADDRESSED |
| AND ADJUSTED ON PLANS HOWEVER PLEASE SEE SHEET FA WHICH |
| STILL INDICATES THE SFBC. |
| ** PLEASE SEE COMMENT WITH RESPECT TO FA SYSTEMS. ** |
| SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER |
| PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT THIS NOTE. |
| ** PLEASE SEE COMMENTS IN REVIEW WITH RESPECT TO SOME |
| AREAS OF PLANS WHICH REFLECT THE SOUTH FLORIDA BUILDING |
| CODE SFBC. THIS HAS NOT BEEN IN EFFECT SINCE 3/1/02. |
| |
| 2) NOTE:PLEASE SEE MISSING INFORMATION ON TITLE |
| BLOCKS FOR L AND IRR SHEETS. PLEASE SEE MISSING THE |
| PRINTED NAME AND PRINTED LICENSE NUMBER OF THE DESIGNER |
| OF RECORD. PLEASE ALSO SEE THE SEAL IS NOT VALID UNDER |
| THE FAC 61G1-16.002 |
| 61G1-16.004 |
| |
| 3) NOTE:PLEASE SEE THE STAIRS AS PREVIOUSLY NOTED |
| WILL BE REQUIRED TO HAVE BATTERY BACK UP FIXTURES OF |
| SOME TYPE FOR MINIMUM LIGHTING LEVELS. PLEASE KNOW THE |
| SINGLE TRIPPING OF THE OCP WILL PLACE THE EGRESS OF |
| STAIRS IN DARKNESS. PLEASE PROVIDE FURTHER INFORMATION |
| ON START OF GENERATOR. IF THE GEN UNIT ONLY STARTS |
| UNDER POWER FAILURE OF MAIN, THEN THE BATTERY BACK UP |
| LIGHTS ARE REQUIRED. IF THE UNIT START UP IS TRIGGERED |
| BY THE FAILURES OF THE EMERGENCY DISCONNECT THEN THE |
| MULTI-CIRCUITS WILL BE OK. PLEASE SEE THE NOTE FROM |
| PREVIOUS REVIEW BELOW WILL REMAIN. PLEASE CALL TO GO |
| OVER. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE PROVIDE PHOTO-METRICS FOR STAIR TOWERS WHICH |
| INDICATE THE MINIMUM OF 10FT CANDLES UNDER NORMAL AND |
| 1FT CANDLE UNDER EMERGENCY CONDITIONS. |
| PLEASE ALSO SEE THE FIXTURES AS SHOWN DO NOT PROVIDE |
| ENOUGH INFORMATION FOR TYPE OF FIXTURE. PLEASE SEE A |
| BATTERY BACK UP FIXTURE WILL BE REQUIRED FOR THE |
| MINIMUM LEVELS FOR EGRESS UNDER EMERGENCY CONDITIONS. |
| PLEASE SEE LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. PLEASE |
| SEE THAT THE FAILING OF A SINGLE DEVICE, OCP, SWITCH |
| ETC SHALL NOT LEAVE ANY ONE EGRESS AREA IN TOTAL |
| DARKNESS. |
| PLEASE INDICATE ON PLANS IF THE EXISTING GENERATOR |
| ROOM, FIRE PUMP ROOM AND MAIN ELECTRICAL ROOM CONTAIN |
| EMERGENCY BATTERY BACK UP FIXTURES OF SOME TYPE. IF |
| EXISTING PLEASE SHOW, IF NOT, PLEASE KNOW THESE WILL BE |
| REQUIRED. |
| NEC 700.12E, 700.16, NFPA-101101 7.8, 7.9, NFPA-110 |
| 7.3.1 |
| |
| 4) NOTE: THIS IS THE SAME NOTE. PLEASE SEE THE MINIMUM |
| LEVELS ARE REQUIRED ON PLANS FOR THE SYSTEM AS SHOWN. |
| THIS IS REQUIRED UNDER THE FBC FOR ADA COMPLIANCE WHICH |
| IS MORE RESTRICTIVE THAN NFPA-72. |
| PLEASE SEE PLANS DO INDICATE A FA SYSTEM. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SEE THE FA SHEETS AS THESE INDICATE THE HORN |
| AND STROBE DEVICES FROM THE SFBC AND OTHER CODES WHICH |
| ARE NO LONGER IN EFFECT. |
| PLEASE SEE THE MINIMUM LEVELS FOR THESE DEVICES SHALL |
| BE STATED PER FBC 2004 11-4.28.1,.2 AND .3(4). |
| |
| 5) NOTE: THIS IS THE SAME NOTE: THE LPD WHICH ARE SHOWN |
| ON PLANS WERE VIEWED, HOWEVER THE NEED OF A FIXTURE |
| LEGEND WHICH COORDINATES WITH THE IDENTIFICATION OF |
| PLANS IS NEEDED. PLEASE SEE SOME FIXTURES ARE |
| IDENTIFIED ON PLANS ARE NOT FOUND ON THE *LEGEND* AS |
| SUBMITTED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF ALL |
| FIXTURES AND CORRELATE WITH PLANS. |
| PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS TO |
| CHAPTER 13 FOR THE POWER ALLOWANCES PERMITTED AND |
| PERFORMANCE CALCULATIONS PER 13-415.2. |
| PLEASE PROVIDE WORST CASE VOLTAGE DROP PER |
| 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW. |
| PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND |
| CONTROLS. |
| PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED FOR |
| LIGHTING CONTROLS, PANELS, SCHEDULING ETC. |
| FBC 106.1.2 |
| |
| 6) NOTE: THIS COULD NOT BE LOCATED IN PACKAGE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT WIND LOADS FOR ROOF TOP LIGHTING POLES |
| SHOWING THE MINIMUM LOADS FOR POLES AND FIXTURES WITH |
| THEIR EFFECTIVE PROJECTED AREAS (EFA) TO MEET THE |
| MINIMUM OF THE FBC 140 MPH WIND LOADS. |
| THIS INFORMATION WILL BE REVIEWED BY THE STRUCTURAL |
| PLANS EXAMINER. |
| FBC 106.1.2 |
| |
| 7) NOTE: PLEASE SEE THE GENERATOR IS NOW BEING SHOWN AS |
| EXISTING AND IS NOW SHOWN AS NATURAL GAS, HOWEVER AS |
| THE LOADS HAVE BEEN INCREASED THE AMOUNT OF ON-SITE |
| FUEL NEEDS TO BE VERIFIED. PLEASE SEE THE MINIMUM FUEL |
| REQUIRED AS STATED IN PREVIOUS REVIEW STILL NEEDS TO BE |
| SHOWN AND IDENTIFIED ON PLANS. PLEASE SEE AS THERE ARE |
| SEVERAL ITEMS WHICH IS NEEDED FOR ALL TRADES, THERE MAY |
| BE NEW COMMENTS FROM OTHER TRADES IF NEW LARGER ON-SITE |
| TANK IS NEEDED. ** AS STATED IN THE CODE, THE LEGALLY |
| REQUIRED OR EMERGENCY SYSTEMS SHALL NOT RELY ON |
| UTILITY. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THAT IT IS UNCLEAR WHAT IS BEING DONE WITH |
| THE GENERATOR. IS THIS UNIT GOING TO BE NEW OR EXISTING |
| TO REMAIN? |
| PLEASE SEE THE RISER SEEMS TO SHOW UNIT AS GAS AND |
| DIESEL? PLEASE CLARIFY IS THIS NATURAL GAS? OR |
| GASOLINE? PLEASE VERIFY. |
| PLEASE SUBMIT THE FUEL CONSUMPTION RATE FOR THE |
| GENERATOR AT FULL LOAD INCLUDING THE LOAD OF THE FIRE |
| PUMP AT 100%. |
| PLEASE SEE NFPA-20 9.6.2.2. |
| PLEASE SEE 701.11B3 |
| |
| 8) NOTE: THIS NOTE REMAINS AS NO LOCKED ROTOR CURRENT |
| INFORMATION COULD BE LOCATED FOR THE MAIN FIRE PUMP |
| CONTROLLER. PLEASE SEE THE RISER WAS REVISED TO SHOW A |
| 1200AMP BREAKER WHICH DOES NOT SEEM TO BE CORRECT. |
| PLEASE SEE THE REQUIRED OCP ON THE MAG-TRIP IS |
| TYPICALLY THE SIZE OF THE BREAKER HOWEVER ONLY A |
| MAG-TRIP WITH SETTINGS. THIS IS NOT ACTUALLY GOING TO |
| BE A 1200AMP BREAKER? |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE BE SURE INFORMATION IS PROVIDED ON PLANS FOR |
| THE LOCKED ROTOR OVER CURRENT PROTECTION ON THE PRIMARY |
| SIDE OF THE FIRE PUMP. |
| PLEASE SEE 695.4B1, NFPA-20 9.3.2.2.3.2 |
| PLEASE ALSO SEE OTHER SECTIONS UNDER 9.3 FOR THE FPC. |
| |
| 9) NOTE: PLEASE SEE THE ADDRESS FOR THE PROJECT IS |
| REQUIRED TO BE ON PLANS. PLEASE SEE THE ADDRESS OF 505 |
| BANYAN BLVD SHOULD BE ON PLANS. PLEASE KNOW THAT ANY |
| SHEETS WHICH MAY ALREADY BE PASSED AND CONTAINS CITY |
| STAMPS MAY *PRINT, STAMP OR BY OTHER PERMANENT MEANS* |
| THE ADDRESS ON TITLE BLOCKS. |
| FAC 61G1-16.004 |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
2007-06-21 06:59:45 | 2007-02-21 06:59:45 |
| REVIEW IN PROGRESS |
2007-06-20 21:07:42 | 2007-06-20 21:07:42 |
| IN ELEC FOR REVIEW. |