Plan Review Notes
Plan Review Notes For Permit 07030592
Permit Number 07030592
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-22 18:32:46*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE STILL SOME NOTES FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE MOST OF THE CODES WERE ADDRESSED
 AND ADJUSTED ON PLANS HOWEVER PLEASE SEE SHEET FA WHICH
 STILL INDICATES THE SFBC.
 ** PLEASE SEE COMMENT WITH RESPECT TO FA SYSTEMS. **
 SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
 ** PLEASE SEE COMMENTS IN REVIEW WITH RESPECT TO SOME
 AREAS OF PLANS WHICH REFLECT THE SOUTH FLORIDA BUILDING
 CODE SFBC. THIS HAS NOT BEEN IN EFFECT SINCE 3/1/02.
  
 2) NOTE:PLEASE SEE MISSING INFORMATION ON TITLE
 BLOCKS FOR L AND IRR SHEETS. PLEASE SEE MISSING THE
 PRINTED NAME AND PRINTED LICENSE NUMBER OF THE DESIGNER
 OF RECORD. PLEASE ALSO SEE THE SEAL IS NOT VALID UNDER
 THE FAC 61G1-16.002
 61G1-16.004
  
 3) NOTE:PLEASE SEE THE STAIRS AS PREVIOUSLY NOTED
 WILL BE REQUIRED TO HAVE BATTERY BACK UP FIXTURES OF
 SOME TYPE FOR MINIMUM LIGHTING LEVELS. PLEASE KNOW THE
 SINGLE TRIPPING OF THE OCP WILL PLACE THE EGRESS OF
 STAIRS IN DARKNESS. PLEASE PROVIDE FURTHER INFORMATION
 ON START OF GENERATOR. IF THE GEN UNIT ONLY STARTS
 UNDER POWER FAILURE OF MAIN, THEN THE BATTERY BACK UP
 LIGHTS ARE REQUIRED. IF THE UNIT START UP IS TRIGGERED
 BY THE FAILURES OF THE EMERGENCY DISCONNECT THEN THE
 MULTI-CIRCUITS WILL BE OK. PLEASE SEE THE NOTE FROM
 PREVIOUS REVIEW BELOW WILL REMAIN. PLEASE CALL TO GO
 OVER.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE PHOTO-METRICS FOR STAIR TOWERS WHICH
 INDICATE THE MINIMUM OF 10FT CANDLES UNDER NORMAL AND
 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE THE FIXTURES AS SHOWN DO NOT PROVIDE
 ENOUGH INFORMATION FOR TYPE OF FIXTURE. PLEASE SEE A
 BATTERY BACK UP FIXTURE WILL BE REQUIRED FOR THE
 MINIMUM LEVELS FOR EGRESS UNDER EMERGENCY CONDITIONS.
 PLEASE SEE LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. PLEASE
 SEE THAT THE FAILING OF A SINGLE DEVICE, OCP, SWITCH
 ETC SHALL NOT LEAVE ANY ONE EGRESS AREA IN TOTAL
 DARKNESS.
 PLEASE INDICATE ON PLANS IF THE EXISTING GENERATOR
 ROOM, FIRE PUMP ROOM AND MAIN ELECTRICAL ROOM CONTAIN
 EMERGENCY BATTERY BACK UP FIXTURES OF SOME TYPE. IF
 EXISTING PLEASE SHOW, IF NOT, PLEASE KNOW THESE WILL BE
 REQUIRED.
 NEC 700.12E, 700.16, NFPA-101101 7.8, 7.9, NFPA-110
 7.3.1
  
 4) NOTE: THIS IS THE SAME NOTE. PLEASE SEE THE MINIMUM
 LEVELS ARE REQUIRED ON PLANS FOR THE SYSTEM AS SHOWN.
 THIS IS REQUIRED UNDER THE FBC FOR ADA COMPLIANCE WHICH
 IS MORE RESTRICTIVE THAN NFPA-72.
 PLEASE SEE PLANS DO INDICATE A FA SYSTEM.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THE FA SHEETS AS THESE INDICATE THE HORN
 AND STROBE DEVICES FROM THE SFBC AND OTHER CODES WHICH
 ARE NO LONGER IN EFFECT.
 PLEASE SEE THE MINIMUM LEVELS FOR THESE DEVICES SHALL
 BE STATED PER FBC 2004 11-4.28.1,.2 AND .3(4).
  
 5) NOTE: THIS IS THE SAME NOTE: THE LPD WHICH ARE SHOWN
 ON PLANS WERE VIEWED, HOWEVER THE NEED OF A FIXTURE
 LEGEND WHICH COORDINATES WITH THE IDENTIFICATION OF
 PLANS IS NEEDED. PLEASE SEE SOME FIXTURES ARE
 IDENTIFIED ON PLANS ARE NOT FOUND ON THE *LEGEND* AS
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF ALL
 FIXTURES AND CORRELATE WITH PLANS.
 PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS TO
 CHAPTER 13 FOR THE POWER ALLOWANCES PERMITTED AND
 PERFORMANCE CALCULATIONS PER 13-415.2.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW.
 PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND
 CONTROLS.
 PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED FOR
 LIGHTING CONTROLS, PANELS, SCHEDULING ETC.
 FBC 106.1.2
  
 6) NOTE: THIS COULD NOT BE LOCATED IN PACKAGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT WIND LOADS FOR ROOF TOP LIGHTING POLES
 SHOWING THE MINIMUM LOADS FOR POLES AND FIXTURES WITH
 THEIR EFFECTIVE PROJECTED AREAS (EFA) TO MEET THE
 MINIMUM OF THE FBC 140 MPH WIND LOADS.
 THIS INFORMATION WILL BE REVIEWED BY THE STRUCTURAL
 PLANS EXAMINER.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE GENERATOR IS NOW BEING SHOWN AS
 EXISTING AND IS NOW SHOWN AS NATURAL GAS, HOWEVER AS
 THE LOADS HAVE BEEN INCREASED THE AMOUNT OF ON-SITE
 FUEL NEEDS TO BE VERIFIED. PLEASE SEE THE MINIMUM FUEL
 REQUIRED AS STATED IN PREVIOUS REVIEW STILL NEEDS TO BE
 SHOWN AND IDENTIFIED ON PLANS. PLEASE SEE AS THERE ARE
 SEVERAL ITEMS WHICH IS NEEDED FOR ALL TRADES, THERE MAY
 BE NEW COMMENTS FROM OTHER TRADES IF NEW LARGER ON-SITE
 TANK IS NEEDED. ** AS STATED IN THE CODE, THE LEGALLY
 REQUIRED OR EMERGENCY SYSTEMS SHALL NOT RELY ON
 UTILITY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT IT IS UNCLEAR WHAT IS BEING DONE WITH
 THE GENERATOR. IS THIS UNIT GOING TO BE NEW OR EXISTING
 TO REMAIN?
 PLEASE SEE THE RISER SEEMS TO SHOW UNIT AS GAS AND
 DIESEL? PLEASE CLARIFY IS THIS NATURAL GAS? OR
 GASOLINE? PLEASE VERIFY.
 PLEASE SUBMIT THE FUEL CONSUMPTION RATE FOR THE
 GENERATOR AT FULL LOAD INCLUDING THE LOAD OF THE FIRE
 PUMP AT 100%.
 PLEASE SEE NFPA-20 9.6.2.2.
 PLEASE SEE 701.11B3
  
 8) NOTE: THIS NOTE REMAINS AS NO LOCKED ROTOR CURRENT
 INFORMATION COULD BE LOCATED FOR THE MAIN FIRE PUMP
 CONTROLLER. PLEASE SEE THE RISER WAS REVISED TO SHOW A
 1200AMP BREAKER WHICH DOES NOT SEEM TO BE CORRECT.
 PLEASE SEE THE REQUIRED OCP ON THE MAG-TRIP IS
 TYPICALLY THE SIZE OF THE BREAKER HOWEVER ONLY A
 MAG-TRIP WITH SETTINGS. THIS IS NOT ACTUALLY GOING TO
 BE A 1200AMP BREAKER?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE INFORMATION IS PROVIDED ON PLANS FOR
 THE LOCKED ROTOR OVER CURRENT PROTECTION ON THE PRIMARY
 SIDE OF THE FIRE PUMP.
 PLEASE SEE 695.4B1, NFPA-20 9.3.2.2.3.2
 PLEASE ALSO SEE OTHER SECTIONS UNDER 9.3 FOR THE FPC.
  
 9) NOTE: PLEASE SEE THE ADDRESS FOR THE PROJECT IS
 REQUIRED TO BE ON PLANS. PLEASE SEE THE ADDRESS OF 505
 BANYAN BLVD SHOULD BE ON PLANS. PLEASE KNOW THAT ANY
 SHEETS WHICH MAY ALREADY BE PASSED AND CONTAINS CITY
 STAMPS MAY *PRINT, STAMP OR BY OTHER PERMANENT MEANS*
 THE ADDRESS ON TITLE BLOCKS.
 FAC 61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
2007-06-21 06:59:452007-02-21 06:59:45
 REVIEW IN PROGRESS
2007-06-20 21:07:422007-06-20 21:07:42
 IN ELEC FOR REVIEW.