Plan Review Notes
Plan Review Notes For Permit 07030592
Permit Number 07030592
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-28 16:50:46BUILDING PLAN REVIEW
 PERMIT: 07030592
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TEL: (561)722-8837
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) 2ND REQUEST, FOR THE THRESHOLD INSPECTOR TO SIGN AN
 ORIGINAL AGREEMENT, NOT A PHOT-COPY, HAROLD PISKURA HAS
 PUT A LOCK ON THE PERMIT UNTIL THIS MATTER IS RESOLVED.
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER
 OF THE SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY
 BE ISSUED.
  
 4-6) COMPLIED.
  
 7) PARTIALLY COMPLIED, FL BLD CODE 1609.1.4:
 COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD
 OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS
 ,I(NCOMPLETE) REPORTS ARE AS FOLLOWS:
 ROOFING ASSEMBLIES, JOHN MANVILLE MODIFIED BITUMEN
 OVER CONCRETE ,
 THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A
 REVISED
 FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9, NO
 ENHANCEDFASTENING ALLOWED.
  
 8) COMPLIED.
  
 9) SECOND REQUEST," JOHN MANVILLE MODIFIED BITUMEN"
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10-11) COMPLIED.
  
 12) NEW COMMENT, SUBMITTAL FOR ALUMINUM LIGHT POLE FOR
 TOP OF ROOF DECK DESIGN BY HAPCO ALUMINUM LIGHT POLES
 DESIGNED TO THE ASCE 7-98
 NOT THE CURRENT ASCE 7-02. PLEASE SEE SUBMITTALS, ONLY
 TWO SEALED DOCUMENTS WERE LOCATED, REQUIRES THREE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]