2007-06-28 16:50:46 | BUILDING PLAN REVIEW |
| PERMIT: 07030592 |
| ADD: 505 BANYAN BLVD |
| CONT: THE WEITZ CO |
| TEL: (561)722-8837 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2NDREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) COMPLIED. |
| |
| 3) 2ND REQUEST, FOR THE THRESHOLD INSPECTOR TO SIGN AN |
| ORIGINAL AGREEMENT, NOT A PHOT-COPY, HAROLD PISKURA HAS |
| PUT A LOCK ON THE PERMIT UNTIL THIS MATTER IS RESOLVED. |
| WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER |
| OF THE SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY |
| BE ISSUED. |
| |
| 4-6) COMPLIED. |
| |
| 7) PARTIALLY COMPLIED, FL BLD CODE 1609.1.4: |
| COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD |
| OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS |
| ,I(NCOMPLETE) REPORTS ARE AS FOLLOWS: |
| ROOFING ASSEMBLIES, JOHN MANVILLE MODIFIED BITUMEN |
| OVER CONCRETE , |
| THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE |
| FOLLOW ITEMS: |
| ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. |
| |
| _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| USED. |
| |
| _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| _2&3__ . |
| |
| _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, |
| SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT |
| REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A |
| REVISED |
| FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| SUBMITTED. |
| |
| ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9, NO |
| ENHANCEDFASTENING ALLOWED. |
| |
| 8) COMPLIED. |
| |
| 9) SECOND REQUEST," JOHN MANVILLE MODIFIED BITUMEN" |
| PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 10-11) COMPLIED. |
| |
| 12) NEW COMMENT, SUBMITTAL FOR ALUMINUM LIGHT POLE FOR |
| TOP OF ROOF DECK DESIGN BY HAPCO ALUMINUM LIGHT POLES |
| DESIGNED TO THE ASCE 7-98 |
| NOT THE CURRENT ASCE 7-02. PLEASE SEE SUBMITTALS, ONLY |
| TWO SEALED DOCUMENTS WERE LOCATED, REQUIRES THREE. |
| |
| BUILDING PLAN REVIEW II |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |