2007-04-26 11:23:56DENIED
 REFERENCE: FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SURVEY SHEETS 2, 3 & 4 OF 4. ALL FINAL DRAWINGS,
 PLANS, SPECIFICATIONS, PLATS, OR REPORTS PREPARED ON
 ISSUED BY THE REGISTRANT SHALL BE SIGNED, DATED AND
 SEALED. FS 472.025.
  
 2. SHTS P2.50 & 2.60 MORE INFORMATION IS REQUIRED.
 INDICATE WHAT THE ABBREVIATION WDP STANDS FOR. THERE
 ARE 4 2" WDP'S SHOWN ON EACH FLOOR. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 3. SHT P2.60 SUBMIT A RISER DIAGRAM SHOWING THE TYPICAL
 PLANTER BOX DRAIN PIPING. SHOW PIPE SIZES AND INDICATE
 THE TERMINATION POINT.SECTION 106.3.5.1.3(7)(13).
  
 4. SHT P2.80 STORM RISER DIAGRAM. SHOW ALL DRAINS
 CONNECTING TO THE RISER DIAGRAMS FOR EACH ADDED LEVEL.
 SHOW ALL PIPE SIZES TO EACH DRAIN. SECTION
 106.3.5.1.3(7)(13) AND TABLE 1106.3.
  
 5. ALL SHEETS WITH THE GARTEK ENGINEERING TITLE BLOCK.
 SOME OF THE INFORMATION IS NOT LEGIBLE. PLEASE CHECK
 TITLE BLOCK AND MAKE SURE ALL INFORMATION CAN BE READ.
 SECTION 106.1.1.
  
 6. SHTS LP-1, LP-2, LD-1, IRR-1 & IRR-2. THE ADDRESS
 SUBMITTED TO THE STATE OF FLORIDA DBPR WEBSITE SHALL
 ALSO BE ADDED TO THE TITLE BLOCK OF THE LANDSCAPE
 ARCHITECTS. (SEE ATTACHED SHEET FROM DBPR WEBSITE).
  
 7. SHTS IRR-1 & IRR-2 SHOW THE LOCATION OF THE
 CONTROLLER & THE RAIN SENSOR. SECTION 106.3.5.1.3(9). -
 THE PLUMBING PLANS INDICATE 11 3/4" IRRIGATION RISERS,
 BUT THE IRRIGATION PLANS ONLY SHOW 1. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]