Plan Review Notes For Permit 07030592 |
Permit Number |
07030592 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-08-02 08:32:02 | PROVISO; | | THE GAS PLAN, PAGE P3.10 MUST BE REVISED WITHIN 30 DAYS | | THE FOLLOWING INFORMATION NEEDS TO BE CHANGED ARE ADDED | | TO PLAN; | | A) DEVELOPED LENGHT FROM TANK TO | | GENERATOR. | | B) PIPE SIZE, WELDED OR SCREW PIPE. | | C) SUBMIT REGUATOR SPEC SHEETS. (MOST LP | | SYSTEMS HAVE A FIRST AND SECOND STAGE REGULATOR) | | D) SLEAVE PIPE THRU WALL. | | E) DETAIL REQUIRED FOR TANK PAD AND TIE | | DOWN. | | F) SHUT OFF VALVES REQUIRED DOWN STREAM OF | | REGULATORS AND UNIONS. ( SHOW ON RISER DIAGRAM) | | G) IF TANK REQUIRES PROTECTION FROM DAMAGE | | SHOW AND SPEC. ON DRAWINGS. |
|