Plan Review Notes
Plan Review Notes For Permit 07030592
Permit Number 07030592
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-23 19:07:13****** UNSAT ******
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOTYET
 BEEN SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
 ** PLEASE SEE COMMENTS IN REVIEW WITH RESPECT TO SOME
 AREAS OF PLANS WHICH REFLECT THE SOUTH FLORIDA BUILDING
 CODE SFBC. THIS HAS NOT BEEN IN EFFECT SINCE 3/1/02.
  
 2) NOTE: PLEASE SEE THE *S* SHEETS WHICH IS MISSING
 INFORMATION ON TITLE BLOCKS FOR FIRM. PLEASE SEE
 MISSING THE CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED PER FAC 61G15-23.002, AND FS 471.023. THIS IS
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE TITLE BLOCK FOR GARTEK ENGINEERING
 IS SMALL AND INFORMATION IS NOT CLEAR. PLEASE SEE TITLE
 BLOCK AND ADJUST FONT/PRINTING.
  
 4) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR STAIR TOWERS
 WHICH INDICATE THE MINIMUM OF 10FT CANDLES UNDER NORMAL
 AND 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE THE FIXTURES AS SHOWN DO NOT PROVIDE
 ENOUGH INFORMATION FOR TYPE OF FIXTURE. PLEASE SEE A
 BATTERY BACK UP FIXTURE WILL BE REQUIRED FOR THE
 MINIMUM LEVELS FOR EGRESS UNDER EMERGENCY CONDITIONS.
 PLEASE SEE LS 101 7.8, 7.9, 7.8.1.3, 7.9.2.2. PLEASE
 SEE THAT THE FAILING OF A SINGLE DEVICE, OCP, SWITCH
 ETC SHALL NOT LEAVE ANY ONE EGRESS AREA IN TOTAL
 DARKNESS.
 PLEASE INDICATE ON PLANS IF THE EXISTING GENERATOR
 ROOM, FIRE PUMP ROOM AND MAIN ELECTRICAL ROOM CONTAIN
 EMERGENCY BATTERY BACK UP FIXTURES OF SOME TYPE. IF
 EXISTING PLEASE SHOW, IF NOT, PLEASE KNOW THESE WILL BE
 REQUIRED.
 NEC 700.12E, 700.16, NFPA-101101 7.8, 7.9, NFPA-110
 7.3.1
  
 5) NOTE: PLEASE SEE THE FA SHEETS AS THESE INDICATE THE
 HORN AND STROBE DEVICES FROM THE SFBC AND OTHER CODES
 WHICH ARE NO LONGER IN EFFECT.
 PLEASE SEE THE MINIMUM LEVELS FOR THESE DEVICES SHALL
 BE STATED PER FBC 2004 11-4.28.1,.2 AND .3(4).
  
 6) NOTE: PLEASE SEE THE *CODED NOTES* FOR THE PARKING
 BOOTHS DO NOT PROVIDE THE MINIMUM CIRCUITING FOR THE
 NEW ELECTRICAL WHICH IS BEING INSTALLED AT BOOTHS. DO
 THEY INCREASE IN LOAD? ARE THESE GOING TO BE NEW UNITS
 WHICH WILL CONTAIN ALL NEW ELECTRICAL AND PANELS?
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2
  
 7) NOTE: PLEASE SUBMIT A COMPLETE FIXTURE LEGEND OF ALL
 FIXTURES AND CORRELATE WITH PLANS.
 PLEASE ALSO SEE THE 2004 FBC W/ 2006 REVISIONS TO
 CHAPTER 13 FOR THE POWER ALLOWANCES PERMITTED AND
 PERFORMANCE CALCULATIONS PER 13-415.2.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP PER
 13-413.1ABC.1 FOR BRANCH CIRCUITS INSTALLED AS NEW.
 PLEASE SEE ALL OF CHAPTER 13 FOR LIGHTING AND
 CONTROLS.
 PLEASE SEE THAT NOT ENOUGH INFORMATION IS PROVIDED FOR
 LIGHTING CONTROLS, PANELS, SCHEDULING ETC.
 FBC 106.1.2
  
 8) NOTE: PLEASE SUBMIT WIND LOADS FOR ROOF TOP LIGHTING
 POLES SHOWING THE MINIMUM LOADS FOR POLES AND FIXTURES
 WITH THEIR EFFECTIVE PROJECTED AREAS (EFA) TO MEET THE
 MINIMUM OF THE FBC 140 MPH WIND LOADS.
 THIS INFORMATION WILL BE REVIEWED BY THE STRUCTURAL
 PLANS EXAMINER.
 FBC 106.1.2
  
 9) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE'S SPECS/CUT
 SHEETS FOR ALL NEW EQUIPMENT BEING INSTALLED FOR THE
 GENERATOR, FIRE PUMP, FIRE PUMP CONTROLLER, AND ATS(S)
 .
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH NEED TO BE
 REVIEWED FOR CODE COMPLIANCE WHICH CAN NOT BE DONE AT
 THIS TIME.
 PLEASE ALSO BE SURE ALL INFORMATION SUBMITTED CONTAINS
 LISTINGS FROM ANRTL.
 110.3, 90.7.
  
 10) NOTE: PLEASE PROVIDE NOTES ON RISER FOR SIGNAGE AS
 REQUIRED PER 230.2E, 700.8, 701.9 ETC.
  
 11) NOTE: PLEASE SEE THAT IT IS UNCLEAR WHAT IS BEING
 DONE WITH THE GENERATOR. IS THIS UNIT GOING TO BE NEW
 OR EXISTING TO REMAIN?
 PLEASE SEE THE RISER SEEMS TO SHOW UNIT AS GAS AND
 DIESEL? PLEASE CLARIFY IS THIS NATURAL GAS? OR
 GASOLINE? PLEASE VERIFY.
 PLEASE SUBMIT THE FUEL CONSUMPTION RATE FOR THE
 GENERATOR AT FULL LOAD INCLUDING THE LOAD OF THE FIRE
 PUMP AT 100%.
 PLEASE SEE NFPA-20 9.6.2.2.
 PLEASE SEE 701.11B3
  
 12) NOTE: PLEASE SUBMIT ONLY ONE ELECTRICAL RISER WHICH
 WILL BE ON THE PERMITTED RECORD SET OF PLANS. IF THE
 OTHER OPTION (1 OR 2) IS DONE INSTEAD THEN REVISED
 PLANS WILL BE REQUIRED THAT TIME. THE RECORD SET OF
 PLANS MUST CONTAIN ONE OPTION.
 PLEASE KNOW THE REVIEW WILL BE DONE ON THE ONE
 SUBMITTED.
  
 13) NOTE: PLEASE SEE RISER AS IT APPEARS TO SHOW THE
 SERVICE ENTRANCE CONDUCTORS BEING RUN OVER HEAD TO THE
 FIRE PUMP/FPC.
 PLEASE SEE NFPA-70 695.6A AS THESE WILL BE REQUIRE DOT
 BE RUN OVER HEAD IF THIS IS THE CASE.
 PLEASE ALSO SEE NFPA-20 9.3.1*
  
 14) NOTE: PLEASE BE SURE INFORMATION IS PROVIDED ON
 PLANS FOR THE LOCKED ROTOR OVER CURRENT PROTECTION ON
 THE PRIMARY SIDE OF THE FIRE PUMP.
 PLEASE SEE 695.4B1, NFPA-20 9.3.2.2.3.2
 PLEASE ALSO SEE OTHER SECTIONS UNDER 9.3 FOR THE FPC.
  
 15) NOTE: PLEASE SEE THE CONDUCTORS TO THE FPC FROM FPL
 AS THESE ARE NOT SHOWING A NEUTRAL CONDUCTOR TO THE
 FIRST MEANS OF DISCONNECT WHICH IS REQUIRED. THIS
 CONDUCTOR IS REQUIRED TO TERMINATE IN THIS FPC. PLEASE
 ALSO KNOW THAT THERE MAY VERY WELL BE THE NEED FOR THE
 NEUTRAL IN THE FPC. THE MANUFACTURE MAY REQUIRE FOR
 CONTROLS.
 PLEASE SEE THAT THE GENERATOR IS BEING NOTED AS A
 SEPARATELY DERIVED SYSTEM AS REQUIRED, PLEASE VERIFY IF
 THE NEUTRAL WILL BEBROUGHT FROM THE GENERATOR AS IF
 THIS IS A SD GENERATOR THEN THIS FPC WILL CONTAIN A
 FOUR POLE ATS.
 PLEASE SEE THE FOLLOWING COMMENT.
 PLEASE SEE RISER IS CURRENTLY SHOWING *EQUIPMENT
 GROUNDING CONDUCTOR* FROM THE FPL TRANSFORMER ETC.
 PLEASE SEE 250.6 FOR OBJECTIONABLE CURRENTS AS THE
 NEUTRAL IS REQUIRED TO BE BONDED AT THE FIRST MEANS OF
 DISCONNECT. 250.24.
 250.30, 250.20 ETC.
 PLEASE SEE THE FPC SEEMS TO SHOW A GROUNDING ELECTRODE
 BY ITSELF WITHOUT ANY CONNECTIONTO A MINIMUM
 SYSTEM(S) PER 250.50 OR BONDING TO THE OTHER SERVICES?
 PLEASE VERIFY THIS.
 250.92, 250.94, 250.66
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE ALTHOUGH GF PROTECTION IS NOT
 REQUIRED ON THE EMERGENCY SIDE OF THE EMERGENCY SYSTEM
 AND LEGALLY REQUIRED SYSTEMS, PROPER GROUND FAULT
 SENSING IS REQUIRED.
 PLEASE SEE NFPA-110 6.2.15** ISOLATION OF NEUTRAL
 CONDUCTORS. PROVISIONS SHALL BE INCLUDED FOR ENSURING
 CONTINUITY, TRANSFER, AND ISOLATION OF THE PRIMARY AND
 THE EPS NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE AN ATTACHED BRIEF EXPLANATION FROM *ASCO*
 WHITE PAPER: WHERE GROUND FAULT PROTECTION IS TRIGGERED
 BY THE CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATES SUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF IT IS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR IS FEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUS LOST."
 PLEASE KNOW BASED ON THE INFORMATION FROM SEVERAL OTHER
 MANUFACTURES ALSO AND THE CODE PLEASE BE SURE THE
 MANUFACTURES SPECS TO BE SUBMITTED ARE INDEED 4POLE ATS
 DEVICES AS NOTED FOR EACH RISER MENTIONS.
 PLEASE VERIFY THE FPC/ATS.
 PLEASE ALSO SEE GENERATOR GROUNDING DETAIL WILL BE
 REQUIRED TO BE REVISED.
 PLEASE SEE 250.20, 250.30, 250.66, 240.13, 230.95,
 700.7D, 700.26
  
 17) NOTE: PLEASE CORRELATE PLANS AS THE ELECTRICAL
 PLANS INDICATE A 150HP 480V FIRE PUMP AND THE FIRE
 PROTECTION SHEETS INDICATE A 125HP 480V PUMP. PLEASE
 KNOW AT THIS TIME REVIEW OF THE RISER CONDUCTORS CAN
 NOT BE DONE AS IT IS NOT KNOWN WHICH ONE IS BEING
 INSTALLED.
 FBC 106.1.2
  
 18) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.
 PLEASE INCLUDE LOAD CALCULATIONS FOR INCREASED LOADS IN
 A LOAD SUMMARY.
 215.5,215.3, 230.42. AND 220.
 FBC 106.3.5.1.2
  
 19) NOTE: PLEASE SEE OPTION #2 AS IT STILL INDICATES
 400AMP OCP ON THE 400AMP FEEDERS TO THE 200AMP ATS??
 AND 200AMP DISCONNECT ETC.
 PLEASE VERIFY AND COORDINATE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II