2007-04-11 16:12:55 | BUILDING PLAN REVIEW |
| PERMIT: 07030592 |
| ADD: 505 BANYAN BLVD |
| CONT: THE WEITZ CO |
| TEL: (561)722-8837 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| OF A BUILDING PERMIT FOR THE |
| CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURL INSPECTION |
| PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE |
| BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 3)WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 4)W.P.B. AMENDMENT 105.13.4.4 ALL |
| PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CON- |
| TAIN A STATEMENT THAT, TO THE BEST OF |
| THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY WITH |
| THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 5) SHEET LS!.0.0 |
| |
| 5A) APPLICABLE CODES PLANS SUBMITTED AFTER DEC.8/ 2006 |
| SHALL REVIEWED UNDER THE 2004 BASE FBC WITH 2006 |
| AMENDMENTS. |
| |
| 5B) BUILDING TYPE & FIRE RESISTANCE, NOTE # 1 USES |
| TABLE 600 AS A REFRENCE, THIS IS FROM THE FBC 2001 |
| CODE, PLEASE CORRECT. |
| |
| 5C) BUILDING TYPE & FIRE RESISTANCE, NOTE # 3, USES A |
| CODE SECTION TABLE 705.2.1 IN REFRENCE TO SHAFTS, THIS |
| ALSO IS A REFRENCE TO THE 2001 FBC BASE CODE, PLEASE |
| CORRECT. |
| |
| 5D)PLANS INDICATE THE OPEN AREA CALCULATIONS LISTED |
| UNDER 406.3.3.1.PLEASE PROVIDE THE INTERIOR WALL PER |
| CENTAGES OF OPEN AREAS WITH UNIFORMLY DISTRIBUTED |
| OPENINGS. |
| |
| 5E) OCCUPANCY CLASSIFICATION: PLANS INDICATE A MIXED |
| USE BUILDING, S2, OFFICE AND INDUSTRIAL USAGE. |
| PLANS ALSO INDICATE BELOW THE AREA OF REFUGE THIS |
| BUILDING IS NOT FIRE SPRINKLERED! |
| 2004 EXISTING BUILDING CODE CHAPTER NINE |
| ADDITIONS 901.2 CREATION OREXTENTION OF |
| NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR EXTEND |
| ANY NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE |
| ADDITION IS BEING MADE WITH |
| REGARDS TO ACCESSIBILITY, STRUCTURAL STRENGTH, |
| FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF |
| MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| |
| LS1.0.0 CLEARLY INDICATES THIS IS A MIXED USE |
| BUILDING AND NOT ONLY TO BE USED FOR S-2 OPEN AIR |
| PARKING. SINCE THIS IS A MIXED USE BUILDING OVER THREE |
| STORIES THE EXEMPTION FOUND UNDER 903.6(2) ELIMINATING |
| THE FIRE SPRINKLERS NO |
| LONGER STANDS. |
| SINGLE USE 406.3.5.1 |
| WHEN THE OPEN PARKING GARAGE IS USED EXCLUSIVELY |
| FOR THE PARKING OR STORAGE OF PRIVATE MOTOR VEHICLES, |
| WITH NO OTHER USES IN THE BUILDING, THE AREA AND HEIGHT |
| SHALL BE PERMITTED TO COMPLY WITH TABLE 406.3.5 , ALONG |
| WITH |
| INCREASES ALLOWED BY SECTION 406.3.6 . |
| EXCEPTION: THE GRADE-LEVEL TIER IS PERMITTED TO |
| CONTAIN AN OFFICE, WAITING AND TOILET ROOMS HAVING A |
| TOTAL COMBINED AREA OF NOT MORE THAN 1,000 SQUARE FEET |
| (93 M 2 ). SUCH AREA NEED NOT BE SEPARATED FROM THE |
| OPEN PARKING |
| GARAGE. |
| THE OFFICE AREA ON THE FIRST FLOOR IS 1,425 SQ |
| FT. |
| 903.6.1 |
| ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN |
| HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC |
| SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| 903.1 . |
| EXCEPTIONS: |
| (2)A STAND-ALONE PARKING GARAGE CONSTRUCTED |
| WITH NONCOMBUSTIBLE MATERIALS, THE DESIGN OF WHICH IS |
| SUCH THAT ALL LEVELS OF THE GARAGE ARE UNIFORMLY OPEN |
| TO THE ATMOSPHERE ON ALL SIDES WITH THE PERCENTAGES OF |
| OPENINGS |
| EQUAL TO OR GREATER THAN THOSE SPECIFIED IN SECTION |
| 406.3 . SUCH GARAGES SHALL BE SEPARATED FROM ANY OTHER |
| STRUCTURE BY NOT LESS THAN 20 FEET (6096 MM). A |
| STAND-ALONE PARKING GARAGE IS ONE THAT IS SOLELY FOR |
| THE PARKING OF |
| VEHICLES AND DOES NOT HAVE ANY OTHER OCCUPANCY |
| GROUP IN THE BUILDING. |
| THIS BUILDING SHALL REQUIRE FIRE SPRINKLERS |
| 903.6.1. |
| ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN |
| HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC |
| SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| 903.1 . |
| |
| 6)FP1.00 NOTE# 1 INDICATES FIRE SPRINKLER HEADS TO |
| BE INSTALLED IN ACCORDANCE WITH NFPA 14, THIS IS FOR |
| STAND PIPES, NFPA 13 IS FOR FIRE SPRIKLERS. |
| |
| 7)FL BLD CODE 1609.1.4: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| INSPECTOR) OF PRODUCT |
| TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| 7A) WINDOWS |
| 7B) EXTERIOR HOLLOW METAL DOORS |
| 7C) LOUVERS |
| 7D) ROOFING ASSEMBLIES |
| |
| 8)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 9)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 10)A.8.0.0 THE DOOR SCHEDULEINDICATES THE USE OF |
| GLAZED PANELS IN THE 1 1/2 HR RATED DOORS, PLEASE |
| PROVIDE THE SIZE OF PANELS AND TYPE OF GLAZING TO BE |
| USED INT THESE PANELS? |
| TABLE 715.4& TABLE 715.4.3. |
| |
| 11) SHEET A4.0.2 TYPICAL ROOF DETAIL INDICATES O.S. |
| TAKEN TO MEAN OVERFLOW SCUPPERS IF THIS IS CORRECT THE |
| RAINWATER COLLECTION HEAD IS DRAWN OFF TO THE SIDE NOT |
| IN LINE WITH THE OVERFLOW SCUPPERS. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |