Plan Review Notes
Plan Review Notes For Permit 07030592
Permit Number 07030592
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-11 16:12:55BUILDING PLAN REVIEW
 PERMIT: 07030592
 ADD: 505 BANYAN BLVD
 CONT: THE WEITZ CO
 TEL: (561)722-8837
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 4)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 5) SHEET LS!.0.0
  
 5A) APPLICABLE CODES PLANS SUBMITTED AFTER DEC.8/ 2006
 SHALL REVIEWED UNDER THE 2004 BASE FBC WITH 2006
 AMENDMENTS.
  
 5B) BUILDING TYPE & FIRE RESISTANCE, NOTE # 1 USES
 TABLE 600 AS A REFRENCE, THIS IS FROM THE FBC 2001
 CODE, PLEASE CORRECT.
  
 5C) BUILDING TYPE & FIRE RESISTANCE, NOTE # 3, USES A
 CODE SECTION TABLE 705.2.1 IN REFRENCE TO SHAFTS, THIS
 ALSO IS A REFRENCE TO THE 2001 FBC BASE CODE, PLEASE
 CORRECT.
  
 5D)PLANS INDICATE THE OPEN AREA CALCULATIONS LISTED
 UNDER 406.3.3.1.PLEASE PROVIDE THE INTERIOR WALL PER
 CENTAGES OF OPEN AREAS WITH UNIFORMLY DISTRIBUTED
 OPENINGS.
  
 5E) OCCUPANCY CLASSIFICATION: PLANS INDICATE A MIXED
 USE BUILDING, S2, OFFICE AND INDUSTRIAL USAGE.
 PLANS ALSO INDICATE BELOW THE AREA OF REFUGE THIS
 BUILDING IS NOT FIRE SPRINKLERED!
 2004 EXISTING BUILDING CODE CHAPTER NINE
 ADDITIONS 901.2 CREATION OREXTENTION OF
 NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR EXTEND
 ANY NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH
 REGARDS TO ACCESSIBILITY, STRUCTURAL STRENGTH,
 FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF
 MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 LS1.0.0 CLEARLY INDICATES THIS IS A MIXED USE
 BUILDING AND NOT ONLY TO BE USED FOR S-2 OPEN AIR
 PARKING. SINCE THIS IS A MIXED USE BUILDING OVER THREE
 STORIES THE EXEMPTION FOUND UNDER 903.6(2) ELIMINATING
 THE FIRE SPRINKLERS NO
 LONGER STANDS.
 SINGLE USE 406.3.5.1
 WHEN THE OPEN PARKING GARAGE IS USED EXCLUSIVELY
 FOR THE PARKING OR STORAGE OF PRIVATE MOTOR VEHICLES,
 WITH NO OTHER USES IN THE BUILDING, THE AREA AND HEIGHT
 SHALL BE PERMITTED TO COMPLY WITH TABLE 406.3.5 , ALONG
 WITH
 INCREASES ALLOWED BY SECTION 406.3.6 .
 EXCEPTION: THE GRADE-LEVEL TIER IS PERMITTED TO
 CONTAIN AN OFFICE, WAITING AND TOILET ROOMS HAVING A
 TOTAL COMBINED AREA OF NOT MORE THAN 1,000 SQUARE FEET
 (93 M 2 ). SUCH AREA NEED NOT BE SEPARATED FROM THE
 OPEN PARKING
 GARAGE.
 THE OFFICE AREA ON THE FIRST FLOOR IS 1,425 SQ
 FT.
 903.6.1
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1 .
 EXCEPTIONS:
 (2)A STAND-ALONE PARKING GARAGE CONSTRUCTED
 WITH NONCOMBUSTIBLE MATERIALS, THE DESIGN OF WHICH IS
 SUCH THAT ALL LEVELS OF THE GARAGE ARE UNIFORMLY OPEN
 TO THE ATMOSPHERE ON ALL SIDES WITH THE PERCENTAGES OF
 OPENINGS
 EQUAL TO OR GREATER THAN THOSE SPECIFIED IN SECTION
 406.3 . SUCH GARAGES SHALL BE SEPARATED FROM ANY OTHER
 STRUCTURE BY NOT LESS THAN 20 FEET (6096 MM). A
 STAND-ALONE PARKING GARAGE IS ONE THAT IS SOLELY FOR
 THE PARKING OF
 VEHICLES AND DOES NOT HAVE ANY OTHER OCCUPANCY
 GROUP IN THE BUILDING.
 THIS BUILDING SHALL REQUIRE FIRE SPRINKLERS
 903.6.1.
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1 .
  
 6)FP1.00 NOTE# 1 INDICATES FIRE SPRINKLER HEADS TO
 BE INSTALLED IN ACCORDANCE WITH NFPA 14, THIS IS FOR
 STAND PIPES, NFPA 13 IS FOR FIRE SPRIKLERS.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 7A) WINDOWS
 7B) EXTERIOR HOLLOW METAL DOORS
 7C) LOUVERS
 7D) ROOFING ASSEMBLIES
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10)A.8.0.0 THE DOOR SCHEDULEINDICATES THE USE OF
 GLAZED PANELS IN THE 1 1/2 HR RATED DOORS, PLEASE
 PROVIDE THE SIZE OF PANELS AND TYPE OF GLAZING TO BE
 USED INT THESE PANELS?
 TABLE 715.4& TABLE 715.4.3.
  
 11) SHEET A4.0.2 TYPICAL ROOF DETAIL INDICATES O.S.
 TAKEN TO MEAN OVERFLOW SCUPPERS IF THIS IS CORRECT THE
 RAINWATER COLLECTION HEAD IS DRAWN OFF TO THE SIDE NOT
 IN LINE WITH THE OVERFLOW SCUPPERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]