Plan Review Notes For Permit 07030589 |
Permit Number |
07030589 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-17 17:12:09 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | A. THE FOLLOWING INFORMATION IS REQUIRED: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. NOT ALL CUT SECTIONS SHOWN. | | | | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | 3. SUBMIT MANUFACTURE SHEET FOR ALL GAS REGULATORS. | | INDICATE THE MODEL NUMBER OF EACH REGULATOR. | | | | 4. CPVC IS NOT AN APPROVED MATERIAL FOR THE REGULATOR | | VENTS. VENTS SHALL BE OF A NON-COMBUSTABLE MATERIAL. | | SECTION 410.3. | | | | 5. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE | | REGULATORS. SECTION 409.4. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|