Plan Review Notes For Permit 07030577 |
Permit Number |
07030577 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-16 10:26:21 | DENIED BY BUILDING | | | | 1)THE STATE HAS NOT GIVEN FINAL APPROVAL TO THE | | PROTECTO WRAP UNDERLAYMENT. THE STATUS IS LISTED AS | | APPLIED FOR,AT THIS TIME. IN ORDER TO USE THIS | | PRODUCT IN THIS JURISDICTION, THE MANUFACTURER OR | | DISTRIBUTOR IS REQUIRED TO APPLY FOR LOCAL PRODUCT | | APPROVAL IN ACCORDANCE WITH FLORIDA BUILDING COMMISSION | | RULE 9B-72. SEE ATTACHED APPLICATION. | | | | 2) THE PRODUCT INFORMATION SUBMITTED FOR THE ALTUSA | | CLAY TILE IS OUTDATED. THE NOA HAS BEEN SUPERCEEDED BY | | NOA 05-0901.06 AND THE NEW STATE NUMBER IS FL# 5559. | | PLEASE SUBMIT THE CURRENT PRODUCT APPROVALS. | | | | 3) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO | | INSTALL THE CLAY ROOF TILE. CIRCLE THE APPROPRIATE ITEM | | ON THE NOA. | | | | 4) THE NOA SUBMITTED FOR THE GAF MODIFIED ROOF SYSTEM | | HAS TWO DIFFERENT APPROVED ASSEMBLIES FOR SBS OVER AN | | INSULATED WOOD DECK. SPECIFY WHICH ONE WILL BE | | INSTALLED AND SPECIFY THE FASTENING OPTION AND MAXIMUM | | DESIGN PRESSURE THAT WILL BE USED. CIRCLE THE | | APPROPRIATE ITEMS ON THE NOA. SUBMIT RAS 117 | | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON | | PAGE 32 FOR ROOF ZONES THAT REQUIRE ENHANCED FASTENING | | DUE TO HIGHER UPLIFT PRESSURES. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|