Plan Review Notes
Plan Review Notes For Permit 07030569
Permit Number 07030569
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-03 09:53:25RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND
 2004 FBC.
  
 1- ONLY ONE SET OF PLANS WAS SIGNED AND SEALED.BOTH
 SETS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT.
  
 2- OLD TITLE BLOCK WITH AA0002284 NUMBER WAS
 RESUBMITTED WITH REVISED DRAWINGS.REVISE TITLE BLOCK
 SHOWING ONLY THE NAME OF THE ARCHITECT AND HISFLORIDA
 LICENSE NUMBER AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 3- AFTER ALL DRAWINGS ARE REVISED, BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD (561)233-5115.BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
 NOTE: THIS MIGHT BE DONE LATER ON TIME OF PERMIT PICK
 UP.
  
 4- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 CRAWL SPACESEC. R408 OF 2004 FLORIDA RESIDENTIAL
 CODE.PLANS DON'T COMPLY WITH VENTILATION LOCATION
 SEC. R408.1 AND SEC. R408.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.ALSO,NEED TO PROVIDE ACCESS AS REQUIRED BY
 SEC. R408.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: PLEASE MAKE SURE THIS INFORMATION IS
 COORDINATED WITH ALL ARCHITECTURAL AND STRUCTURAL PLANS
 AND ELEVATIONS TO AVOID CONFLICTS AND DELAYS IN THE
 REVIEW PROCESS.
  
 5- PROVIDE COMPLETE SPECS SHOWING HOW COMPLYING WITH
 SEC. R319.1 OF 2004 FLORIDA RESIDENTIAL CODE REGARDING
 PROTECTION OF WOOD AGAINST DECAY.COPYING THIS CODE
 SECTION IN THE PLANS DOESN'T ANSWER THE QUESTION.
 CLEARLY SPECIFY HOW PROTECTING THE WOOD TO COMPLY WITH
 THIS SECTION.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 6- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.DESIGNER OF
 RECORD NEEDS TO SPECIFY FASTENING. PRODUCT APPROVAL IS
 JUST TO DEMONSTRATE THAT IT MEETS THE DESIGNER OF
 RECORD SPECIFICATIONS.REPEAT COMMENT. THIS COMMENT
 WAS NOT ADDRESSED AT ALL.
  
 7- A) PLANS WERE REVISED TO HAVE ICYNENE INSULATION.
 NEED TO PROVIDE COMPLETE SPECS FOR YCENENE INSULATION
 INSTALLATION TO VERIFY THAT INSULATION VALUES SHOWN ON
 THE ENERGY CALCULATIONS ARE MET. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) SPECIFY ICYNENE R VALUE IN ALL PLANS AND BUILDING
 SECTIONS TO SHOW COMPLIANCE WITH ENERGY CALCULATIONS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- SHEETS A-6 AND A-7:
 A) PLEASE MAKE SURE THAT FLOOR JOIST SIZE AND
 SPACINGSHOWN ON ALL ARCHITECTURAL SECTIONSMATCH
 STRUCTURAL DRAWINGS.
  
 B) CLARIFY IF EXTERIOR WALLS ARE GOING TO BE 2X4'S
 OR 2X6'S TO VERIFY COMPLIANCE WITH INSULATION VALUES
 SPECIFIED ON ENERGY CALCULATIONS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) SPECIFY CLEARANCE FROMGRADE TO BOTTOM OF FLOOR
 JOIST TO VERIFY COMPLIANCE WITH SEC. R319 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 9- SOIL TEST REPORT:
 A) BOTH COPIES NEED TO HAVE ENGINEER'S ORIGINAL
 SEAL, SIGNATURE AND DATE AS REQUIRED BY SEC.
 61G15-23.002FLORIDA ADMINISTRATIVE CODE.
  
 B) ENGINEERING FIRM NEEDS TO WRITE IN ALL SHEETS THE
 FIRM'S CERTIFICATE OF AUTHORIZATIONNUMBER AS REQUIRED
 BY SEC. 61G15-23.002(2) OF FLORIDA STATUTE.
  
 C) THERE IS A TYPO ON THE ADDRESS. REVISE HOUSE
 NUMBER ASREQUIRED.
  
 10- PROPERTY IS LOCATED ON HISTORICAL SITE.PLEASE
 BRING ALL PLANS FOR HISTORICAL APPROVAL PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCARULE
 9B-72 FOR:
 A) CLAY TILE.NOA #02-1115.02 SUBMITTED WAS
 SUPERSEDED. SEE ATTACHED COPY OF MIAMI DADE PRODUCT
 APPROVAL DIVISION. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004.
 REPEAT COMMENT. NOT ADDRESSED ON PREVIOUS CHECKLIST.
  
 13- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM
 (REPEAT COMMENT, NOT ADDRESSED).
  
 B) THERE IS NOT SLAB ON GRADE.SEE PLANS AND REVISE
 AS REQUIRED. (REPEAT COMMENT, NOT ADDRESSED).
  
 C) COORDINATE R VALUE WITH YCENENE INSULATION.
  
 D) ENGINEER WHO PREPARED CALCULATIONS NEEDS TO
 PROVIDE ALL HIS INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND FLORIDA ADMINISTRATIVE CODE.
 (REPEAT COMMENT, NOT ADDRESSED).
  
 E) OVERHANG LENGTH AND HEIGHT IS INCORRECT.(REPEAT
 COMMENT, NOT ADDRESSED).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712