Date Text
2007-04-02 13:27:58DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1.SHEET D-1 INDICATES REMOVAL OF THE ACCESS DOOR TO
 THE BATH TUB PLUMBING. PER FBC-2004 PLUMBING, SECTION
 405.8 SLIP JOINT CONNECTIONS: FIXTURES WITH CONCEALED
 SLIP JOINT CONNECTIONS SHALL BE PROVIDED WITH AN ACCESS
 PANEL OR UTILITY SPACE AT LEAST 12 INCHES IN ITS
 SMALLEST DEMINSION OR OTHER APPROVED ARRANGEMENT SO AS
 TO PROVIDE ACCESS TO THE SLIP JOINT CONNECTIONS FOR
 INSPECTION AND REPAIR.
  
 2. SHEETS A-3 AND A-6 INDICATEPARAPET WALLS ON THE
 PROPOSED NEW ADDITION.
 PLEASE PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF
 WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE THE
 FOLLOWING INFORMATION PER THE FOLLOWING CODE
 REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPET) DRAINING TO DOWNSPOUTS AND
 SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 PLUMBING,
 SECTION 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE
 FOLLOWING INFORMATION IS REQUIRED FOR THE WASHING
 MACHINE:
  
 (A)802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL
 (B)406.3 WASTE CONNECTION. THE TRAP AND FIXTURE
 DRAIN FOR AN AUTOMATIC CLOTHES WASHER STANDPIPE SHALL
 BE A MINIMUM OF 2 INCHES IN DIAMETER. PLEASE INDICATE
 THIS ON THE RESUBMITTAL.
 (C) 708.9ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS.
 PLEASE CLEARLY INDICATE ON THE RESUBMITTAL THAT THE
 CLEANOUT IS TO THE OUTSIDE OF THE BUILDING DUE TO SHEET
 A-1 INDICATING "NEW STACK WASH/DRY".
  
 4. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 SIZE ALL PIPING AND TRAPS PER FBC-2004 CHAPTER 1,
 SECTION 106.3.5.4 ON THE RESUBMITTAL.
  
 5. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PER
 FBC-2004 PLUMBING, SECTION 604.9 WATER HAMMER ARRESTORS
 REQUIRED FOR QUICK CLOSING VALVES.
 NOTE: WASHING MACHINE AND NEW DISHWASHER INDICATED ON
 (SHEET A-1) REQUIRE WATER HAMMER ARRESTORS. PLEASE NOTE
 THIS ON THE RESUBMITTAL. PLEASE CLEARIFY IF THE NEW
 REF. FRZ. INDICATED ON (SHEET A-1) HAS AN ICE MAKER OR
 WATER DIS. ON THE RESUBMITTAL. IF ITS DOES WATER HAMMER
 ARRESTORS ARE REQUIRED AND NEED TO BE NOTED ON THE
 RESUBMITTAL.
  
 6. SHEET P-1 ISOMETRIC WATER DIAGRAM: PLEASE INDICATE
 EXPANSION CONTROL FOR WATER HEATER PER FBC-2004
 PLUMBING, SECTION 607.3.
  
 7. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PLEASE
 INDICATE FOR NEW HOSE BIBB "REFERENCE GENERAL PLUMBING
 NOTE #14 FOR VACUUM BREAKER" ON THE RESUBMITTAL.
  
 8. PER FBC-2004 CHAPTER 1, SECTION 106.3 THE JOB
 ADDRESS NEEDS TO APPEAR ON ALL TITLE BLOCKS.
  
 9. SHEET P-2 PLEASE DELETE THE FLOOR/HUB DRAIN DETAIL,
 PLUMBING LEGEND AND TRAP PRIMER DIAGRAM ON THE
 RESUBMITTAL DUE TO THE FACT THAT THERE ARE NIETHER
 INDICATED ON THE PLANS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  