Date |
Text |
2007-04-02 13:27:58 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1.SHEET D-1 INDICATES REMOVAL OF THE ACCESS DOOR TO |
| THE BATH TUB PLUMBING. PER FBC-2004 PLUMBING, SECTION |
| 405.8 SLIP JOINT CONNECTIONS: FIXTURES WITH CONCEALED |
| SLIP JOINT CONNECTIONS SHALL BE PROVIDED WITH AN ACCESS |
| PANEL OR UTILITY SPACE AT LEAST 12 INCHES IN ITS |
| SMALLEST DEMINSION OR OTHER APPROVED ARRANGEMENT SO AS |
| TO PROVIDE ACCESS TO THE SLIP JOINT CONNECTIONS FOR |
| INSPECTION AND REPAIR. |
| |
| 2. SHEETS A-3 AND A-6 INDICATEPARAPET WALLS ON THE |
| PROPOSED NEW ADDITION. |
| PLEASE PROVIDE A ROOF PLAN THAT INDICATES HOW THE ROOF |
| WILL BE PITCHED TO PROPERLY DRAIN, AND INDICATE THE |
| FOLLOWING INFORMATION PER THE FOLLOWING CODE |
| REFERENCES. |
| A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF |
| AND VERTICAL WALLS (PARAPET) DRAINING TO DOWNSPOUTS AND |
| SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 PLUMBING, |
| SECTION 1106. |
| B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004 |
| PLUMBING, SECTION 1106.2 |
| C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION |
| 1106.4 |
| D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING, |
| SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004 |
| PLUMBING, TABLE 1106.7. |
| E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004 |
| PLUMBING, SECTION 1107. |
| A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING, |
| SECTION 1107.1. |
| B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING, |
| SECTION 1107.2. |
| |
| 3. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM THE |
| FOLLOWING INFORMATION IS REQUIRED FOR THE WASHING |
| MACHINE: |
| |
| (A)802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| TRAPPED. STANDPIPES SHALL |
| EXTEND A MINIMUM OF 18 INCHES (457MM) |
| AND A MAXIMUM OF 42 INCHES (1066MM) |
| ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| PROVIDED TO ALL STANDPIPES AND DRAINS |
| FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE |
| RESUBMITTAL |
| (B)406.3 WASTE CONNECTION. THE TRAP AND FIXTURE |
| DRAIN FOR AN AUTOMATIC CLOTHES WASHER STANDPIPE SHALL |
| BE A MINIMUM OF 2 INCHES IN DIAMETER. PLEASE INDICATE |
| THIS ON THE RESUBMITTAL. |
| (C) 708.9ACCESS SHALL BE PROVIDED TO ALL CLEANOUTS. |
| PLEASE CLEARLY INDICATE ON THE RESUBMITTAL THAT THE |
| CLEANOUT IS TO THE OUTSIDE OF THE BUILDING DUE TO SHEET |
| A-1 INDICATING "NEW STACK WASH/DRY". |
| |
| 4. SHEET P-1 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE |
| SIZE ALL PIPING AND TRAPS PER FBC-2004 CHAPTER 1, |
| SECTION 106.3.5.4 ON THE RESUBMITTAL. |
| |
| 5. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PER |
| FBC-2004 PLUMBING, SECTION 604.9 WATER HAMMER ARRESTORS |
| REQUIRED FOR QUICK CLOSING VALVES. |
| NOTE: WASHING MACHINE AND NEW DISHWASHER INDICATED ON |
| (SHEET A-1) REQUIRE WATER HAMMER ARRESTORS. PLEASE NOTE |
| THIS ON THE RESUBMITTAL. PLEASE CLEARIFY IF THE NEW |
| REF. FRZ. INDICATED ON (SHEET A-1) HAS AN ICE MAKER OR |
| WATER DIS. ON THE RESUBMITTAL. IF ITS DOES WATER HAMMER |
| ARRESTORS ARE REQUIRED AND NEED TO BE NOTED ON THE |
| RESUBMITTAL. |
| |
| 6. SHEET P-1 ISOMETRIC WATER DIAGRAM: PLEASE INDICATE |
| EXPANSION CONTROL FOR WATER HEATER PER FBC-2004 |
| PLUMBING, SECTION 607.3. |
| |
| 7. SHEET P-1 ISOMETRIC WATER RISER DIAGRAM: PLEASE |
| INDICATE FOR NEW HOSE BIBB "REFERENCE GENERAL PLUMBING |
| NOTE #14 FOR VACUUM BREAKER" ON THE RESUBMITTAL. |
| |
| 8. PER FBC-2004 CHAPTER 1, SECTION 106.3 THE JOB |
| ADDRESS NEEDS TO APPEAR ON ALL TITLE BLOCKS. |
| |
| 9. SHEET P-2 PLEASE DELETE THE FLOOR/HUB DRAIN DETAIL, |
| PLUMBING LEGEND AND TRAP PRIMER DIAGRAM ON THE |
| RESUBMITTAL DUE TO THE FACT THAT THERE ARE NIETHER |
| INDICATED ON THE PLANS. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |