2007-03-22 13:03:51 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM INDICATES A NEW 150 AMP PANEL AND
 A PANEL INSIDE THE HOUSE. THE PLAN INDICATES EXISTING
 METER AND MAIN PANEL "A" ON THE OUTSIDE OF THE HOUSE.
 PLEASE CORRELATE AND IF THE PANEL IS INSIDE SHOW THE
 LOCATION ON THE PLAN.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} 250.50 GROUNDING ELECTRODE SYSTEM
 ALL GROUNDING ELECTRODES AS DESCRIBED IN 250.52(A)(1)
 THROUGH (A)(6) THAT ARE PRESENT AT EACH BUILDING OR
 STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE
 GROUNDING ELECTRODE SYSTEM.SEE 250.52(A)(3) FOR
 FOOTER STEEL, AS IT WILL BE PRESENT AT THE NEW
 ADDITION. THIS IS THE BEST GROUNDING ELECTRODE THAT CAN
 BE USED.
  
 4} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 THERE ARE 5 NEW CIRCUITS IN THE "SCOPE OF WORK" NOTES,
 ONLY 3 IN THE "LOAD SUMMARY. THERE MUST BE A MINIMUM OF
 3 FOR LIGHTING, 1 FOR THE BATH PER 210.11(C)(3), 3 FOR
 THE TANKLESS @ 100 AMPS (24000 WATTS/240), 1 FOR THE
 NEW MICROWAVE, AND THE NAMEPLATE ON THE NEW OVEN SHOULD
 BE VERIFIED @ 7500W.
  
 5} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 6} THE NOTE ABOUT SMOKE DETECTORS AND PALM BEACH COUNTY
 DO NOT APPLY TO WEST PALM BEACH OR THEIS PROJECT. SEE
 R313.1.1 RESIDENTIAL BUILDING CODE. ALSO LOCATE ON
 PLANS.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  