Plan Review Notes
Plan Review Notes For Permit 07030569
Permit Number 07030569
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-17 15:44:52BUILDING REVIEWW CHECKLIST:
 1- PROVIDE ARCHITECT'S FIRM LICENSE NUMBER IN THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE.
 ***NOTE: ARCHITECT'S TITLE BLOCK IS PEELING OFF FROM
 SHEET AND IS REVEALING ANOTHER ARCHITECT'S FIRM.
 UPDATE/REVISE ORIGINALSHEETS TO INCLUDE CORRECT AND
 CURRENT ARCHITECT'S FIRM NAME.
  
 2- AFTER ALL DRAWINGS ARE REVISED BRING THEMTO PALM
 BEACH COUNTY (2300 N. JOG RD. (561)233-5115) TO PAY
 IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF ADDITIONAL FEES ARE DUE.
  
 3- PROVIDE COMPLETE INFORMATIONSHOWING COMPLIANCE
 WITH CRAWL SPACE VENTILATION SIZE AND LOCATION AND
 ACCESS. SEE SEC. R408OF 2004 FLORIDA RESIDENTIAL CODE
 AND PROVIDE INFORMATION AS REQUIRED.
 ***NOTE: KEEP IN MIND THAT THERE IS AN INTERIOR STEM
 WALL FOR INTERIOR BEARING WALL. SHOW CROSS VENTILATION
 AND ACCESS TO BOTH SIDES OF CRAWL SPACE.
  
 4- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH
 SEC. R319.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- PROVIDE COMPLETE SPECS SHOWING COMPLIANCE WITH SEC.
 R320 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6- ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION NUMBER
 27190 IS UNDER A DELINQUENT STATUS ACCORDING TO THE
 DBPR WEBSITE.ENGINEER NEEDS TO CONTACT DBPR AND
 REVISE STATUS AS REQUIRED TO COMPLY WITH SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 7- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004TO VERIFY THAT
 PRODUCT APPROVAL MEETS THE CALCULATED UPLIFT LOADS.
  
 8-PROVIDE COMPLETE SPECS AND DETAILS SHOWING
 COMPLIANCE WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 9- SHEET SP-1: CLARIFY NOTE ON PROPOSED SITE PLAN
 REGARDING LOT GRADING. WHERE IS SEC. R104.3 TAKEN
 FROM?. ALSO, SPECIFY GRADING SO WATER IS NOT DRAINED
 INTONEIGHBOR'S PROPERTY.SEC. R401.3 2004 FLORIDA
 RESIDENTIAL CODE.
  
 10- SHEET A-1:
 A) FOOTING AND VENTILATION OPENINGS DON'T MATCH
 STRUCTURAL PLANS. REVISE AS REQUIRED.
 *NOTE: COORDINATE WITH ITEM #3 ABOVE.
 ***NOTE: REVISE INFORMATION ON EXTERIOR ELEVATIONS
 ALSO.
 B) REVISE CODE SECTION REFERENCED FOR WINDOW EGRESS.
 CORRECT CODE IS THE 2004 FLORIDA RESIDENTIAL CODE AND
 CORRECT SEC. IS SEC. R310. REVISE AS REQUIRED.
  
 11- SHEET A2:
 A) FLOOR AND ROOF JOIST SIZE AND SPACING TO MATCH
 STRUCTURAL DRAWINGS. REVISE AS REQUIRED.
 B) REVISE DESIGN CRITERIA. SEE 2004 FLORIDA
 RESIDENTIAL CODE AND 2004 FBC FOR CORRECT CODE
 SECTIONS.
 C) CLARIFY WHAT'S BWS 190MPH?
  
 12- SHEET A6 AND A7: COORDINATE SIZE AND SPACING OF
 FLOOR AND ROOF JOISTS WITH-STRUCTURAL DRAWINGS.
  
 13- SHEET S1:
 A) COORDINATE WITH ARCHITECT FOR CRAWL SPACE SIZE,
 LOCATION AND ACCESS. SEE ITEM #3 ABOVE.
 B) CLARIFY WHY 4" DROP SHOWN ON GROUND FLOOR PLAN.
 SEE ARCHITECTURAL PLANS.
 C) ENERGY CALCULATIONS CALL FOR R30 INSULATION ON
 ROOF.R30 INSULATION DOESN'T FEET ON 2X8 ROOF JOIST.
 REVISE AS REQUIRED.
  
 14- SHEET S2:
 A) TYPICAL INTERIOR WALL SECTION 06/S2: PROVIDE
 COMPLETE FASTENING SPECS OF FRAMED WALL TO STEM WALL.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- SHEET S3:
 A) CLARIFY WHY ROOFS ABOVE FRENCH DOORS IN REAR
 ELEVATIONARE CONSIDERED TO BE ON ZONE 2 FOR
 COMPONENTS AND CLADDING UPLIFT LOAD SKETCH. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004. ALSO, REVISE ROOF
 FASTENING SPECS FOR THESE ROOFS AS REQUIRED. SEE DETAIL
 09/S2.
 B) REVISE DETAILS 01/S3,02/S3 AND 03/S3TO MATCH
 ACTUAL CONDITIONS ON THIS PROJECT. SHOW THE STEM WALL
 AND COORDINATECONNECTORS AS SHOWN ON FRAMING PLANS
 AND OTHER DETAILS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 C) THERE IS SOME OVERLAPPING INFORMATION SHOWN ON
 STRUCTURAL NOTES RIGHT BELOW THE WATERPROOF MEMBRANES
 NOTE. REVISE AS REQUIRED.
 D) REVISE MASONRY NOTE #2. SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE FOR MIN. COMPRESSIVE STRENGTH
 REQUIRED.
  
 16- PROVIDE SOIL TEST REPORT.
  
 17- DESIGNER OF RECORD TO SPECIFYSOIL BEARING
 CAPACITYASSUMED FOR THE DESIGN OF THIS STRUCTURE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 18- PROVIDE COMPLETE SPECS FOR CONSTRUCTION OF NEW
 PATIO SLAB. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 19- AFTER ALL PLANS ARE REVISED,PLEASE BRING THEM TO
 THE FIFTH FLOOR TO THE HISTORIC DISTRICT DEPARTMENT FOR
 APPROVAL AND STAMPING. THEN, RE-SUBMIT THEMTO THIS
 OFFICE.
  
 20- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) FLAT ROOF SYSTEM:
 * NEED LEGIBLE NOA.
 ** NEED TO SPECIFY SPECIFIC FASTENING OPTION. SEE
 SHEET 28 OF 32.
 *** NEED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. SEE SHEET 32 OF 32.
  
 B) FIXED WINDOW WITH FROSTED GLASS. PICTURE WINDOW
 701 SUBMITTED IS FOR SINGLE HUNG WINDOWS AND IS
 EXPIRED.
 C) CLAY TILE.
  
 21- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 22- ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
 B) THERE IS NOT SLAB ON GRADE. SEE PLANS.
 C) NEED TO HAVE R19 ON EXTERIOR 2X6 FRAMED WALLS.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 E) ENGINEER WHO PREPARED CALCULATIONS NEEDS TO SIGN
 AND SEAL THEM AND PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
 F) OVERHANG LENGTH AND HEIGHT IS INCORRECT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712