Plan Review Notes For Permit 07030543 |
Permit Number |
07030543 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-09-28 11:11:25 | 2007 FBC W/2006 REVISIONS | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) THE DECORATIVE CHIMNEY THAT HAS BEEN DELETED IS | | STILL SHOWN ON THE ELEVATIONS ON SHEET A9. PLEASE | | CORRECT. | | | | 3) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL MULLIONS | | AND THE FIXED GLASS TRANSOM WINDOW ABOVE THE FRONT | | WINDOWS (MARK A). | | | | 4) THE 32" X 68" (MARK A) WINDOWS EXCEED THE MAXIMUM | | SIZE LISTED IN THE PRODUCT APPROVAL NOA FOR THE SINGLE | | OPERABLE CASEMENT WINDOWS. PLEASE SUBMIT A PRODUCT | | APPROVAL FOR THESE WINDOWS OR REVISE THE SIZE. SEE THE | | DESIGN LOAD CAPACITY TABLES ON SHEET 7 OF NOA NO. | | 02-1113.04. | | | | 5) NOTE: THE PRODUCT APPROVALS SUBMITTED FOR THE | | WINDOWS HAVE BEEN TESTED FOR LARGE MISSILE IMPACT AND | | STORM PANELS ARE NOT REQUIRED. ALSO THE WINDOWS ARE | | REQUIRED TO MEET THE WINDLOAD PRESSURES REGARDLESS OF | | BEING SHUTTERED. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|