2007-03-30 13:44:31 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. FAC-61G1-16.004 TITLE BLOCK: |
| A TITLE BLOCK MUST APPEAR ON ALL |
| ARCHITECTURAL OR INTERIOR DESIGN |
| DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK |
| MUST, AT A MINIMUM, CONTAIN THE |
| FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED |
| SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE |
| PERSON SEALING THE DOCUMENT. |
| NOTE: IF "SMITH AND MOORE ARCHITECTS, INC." IS A FIRM |
| THEN THE FIRMS LICENSE NUMBER IS MISSING FROM THE TITLE |
| BLOCK ON ALL SHEETS. PLEASE CORRECT ON THE |
| RESUBMITTAL. |
| |
| 2. SHEET M-3 SANITARY ISOMETRIC RISER DIAGRAM: |
| |
| A} SECOND FLOOR "BATH #2 ROOM # 206", THE SANITARY |
| STACK MUST DRAIN DOWNSTREAM OF FIRST FLOOR "HIS BATH |
| ROOM # 113" PER FBC-2004 PLUMBING, SECTIONS 909.1 AND |
| 908.3. PLEASE CORRECT ON THE RESUBMITTAL. |
| |
| B} "HIS BATH ROOM # 113" FLOOR PLAN ON SHEET A-3 |
| INDICATES A SHOWER BUT ON THE RISER DIAGRAM A B.T. IS |
| INDICATED. PLEASE CORRELATE ON THE RESUBMITTAL. |
| |
| C} THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE |
| WASHING MACHINE ON THE RESUBMITTAL. |
| (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| WASHER SHALL BE A MINIMUM OF 2 INCHES |
| (51MM) IN DIAMETER. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| STACK A MINIMUM OF 3 INCHES (76MM) IN |
| DIAMETER. PLEASE CORRECT ON THE RESUBMITTAL. |
| (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| TRAPPED. STANDPIPES SHALL |
| EXTEND A MINIMUM OF 18 INCHES (457MM) |
| AND A MAXIMUM OF 42 INCHES (1066MM) |
| ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| PROVIDED TO ALL STANDPIPES AND DRAINS |
| FOR RODDING. PLEASE INDICATE THE STANPIPE FOR THE |
| WASHING MACHINE ON THE RESUBMITTAL. |
| |
| 3.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| LOCATIONS. |
| NOTE: NOT ALL PIPES OR TRAPS ARE SIZED AND NOT ALL |
| CLEANOUTS ARE INDICATED ON THE SANITARY RISER DIAGRAM |
| ON SHEET M-3. |
| (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| SHALL BE PROVIDED AT THE BASE OF EACH |
| WASTE OR SOIL STACK |
| (B) 708.3.5 BUILDING DRAIN AND BUILDING |
| SEWER JUNCTION. THERE SHALL BE A TWO-WAY |
| CLEANOUT NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND THE BUILDING SEWER. |
| (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| BE THE SAME NOMINAL SIZE AS THE PIPE |
| THEY SERVE UP TO 4 INCHES (102MM) |
| (D) 708.9 ACCESS. ACCESS SHALL BE |
| PROVIDED TO ALL CLEANOUTS. |
| NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT |
| FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) |
| |
| 4. SHEET M-3 PLUMBING NOTES: PLEASE DELETE "AIR |
| CHAMBER" FROM NOTE #11 ON THE RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |