2007-03-30 16:59:10 | DENIED |
| REFERENCE: |
| |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PLEASE REFERENCE PLUMBING COMMENT #1 IN RELATION TO |
| FIRM LICENSE NUMBER REQUIRED IN TITLE BLOCK. |
| |
| 2. 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| NOTE: THE SUBMITTED GAS ISOMETRIC ON SHEET M-3 DOES NOT |
| REFLECT THE FLOOR PLANS ON SHEETS A-3 AND A-4. GAS |
| ISOMETRIC INDICATES TWO RANGES IN DIFFERENT LOCATIONS |
| BUT THE FLOOR PLANS ONLY INDICATE ONE RANGE IN THE |
| KITCHEN. PLEASE CLARIFY ON THE RESUBMITTAL. |
| |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: CORRESPONDING LENGTHS OF CUT SECTIONS ARE NOT |
| INDICATED. |
| |
| 4. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: NOT ALL PIPE SIZES ARE INDICATED AND IF BLACK |
| STEEL PIPE IS BEING INSTALLED UNDERGROUND PLEASE ADD |
| THE FOLLOWING TO "GAS NOTES" ON SHEET M-3. |
| |
| A} PER FBC-2004 FUEL GAS SECTION 404.8.2 PROTECTIVE |
| COATINGS AND WRAPPING. PIPE PROTECTIVE COATINGS AND |
| WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND |
| SHALL BE FACTORY APPLIED. |
| |
| |
| 5. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| BEING USED ON THE RESUBMITTAL. |
| |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| 7. CLEARLY SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM ON THE ISOMETRIC |
| PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| 8. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS OF |
| APPLIANCES (CUT SHEETS) VARIFYING BTU LOADS AND SHOWING |
| LISTINGS FROM A NATIONALLY RECOGNIZED TESTING |
| LABORATORY (NRTL). |
| |
| 9. PLEASE CLARIFY WHAT THE NIPPLE AND HARD CAP ON THE |
| RUN OF THE TEE FOR THE POOL HEATER IS. IS THIS SUPPOST |
| TO BE A SEDIMENT TRAP? IF SO ITS IN THE WRONG LOCATION. |
| PLEASE CLARIFY ON THE RESUBMITTAL. |
| |
| 10. PLEASE DELETE THE SEDIMENT TRAP BEING INDICATED |
| UNDERGROUND ON THE RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |