Plan Review Notes
Plan Review Notes For Permit 07030543
Permit Number 07030543
Review Stop G
Sequence Number 1
Notes
Date Text
2007-03-30 16:59:10DENIED
 REFERENCE:
  
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE REFERENCE PLUMBING COMMENT #1 IN RELATION TO
 FIRM LICENSE NUMBER REQUIRED IN TITLE BLOCK.
  
 2. 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SUBMITTED GAS ISOMETRIC ON SHEET M-3 DOES NOT
 REFLECT THE FLOOR PLANS ON SHEETS A-3 AND A-4. GAS
 ISOMETRIC INDICATES TWO RANGES IN DIFFERENT LOCATIONS
 BUT THE FLOOR PLANS ONLY INDICATE ONE RANGE IN THE
 KITCHEN. PLEASE CLARIFY ON THE RESUBMITTAL.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: CORRESPONDING LENGTHS OF CUT SECTIONS ARE NOT
 INDICATED.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL PIPE SIZES ARE INDICATED AND IF BLACK
 STEEL PIPE IS BEING INSTALLED UNDERGROUND PLEASE ADD
 THE FOLLOWING TO "GAS NOTES" ON SHEET M-3.
  
 A} PER FBC-2004 FUEL GAS SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPING. PIPE PROTECTIVE COATINGS AND
 WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND
 SHALL BE FACTORY APPLIED.
  
  
 5. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED ON THE RESUBMITTAL.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. CLEARLY SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM ON THE ISOMETRIC
 PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 8. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS OF
 APPLIANCES (CUT SHEETS) VARIFYING BTU LOADS AND SHOWING
 LISTINGS FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL).
  
 9. PLEASE CLARIFY WHAT THE NIPPLE AND HARD CAP ON THE
 RUN OF THE TEE FOR THE POOL HEATER IS. IS THIS SUPPOST
 TO BE A SEDIMENT TRAP? IF SO ITS IN THE WRONG LOCATION.
 PLEASE CLARIFY ON THE RESUBMITTAL.
  
 10. PLEASE DELETE THE SEDIMENT TRAP BEING INDICATED
 UNDERGROUND ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  