2007-03-16 08:47:09 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} 210.52(B)(2) ISLAND COUNTER SPACES AT LEAST ONE |
| RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER |
| SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR |
| GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR |
| GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN |
| ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE |
| RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE |
| RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND |
| INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN |
| 210.52(C)(4). |
| |
| 2} 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS |
| 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE |
| INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A |
| RECEPTACLE OUTLET IN THAT SPACE. |
| |
| 2} THE CONDENSER DISCONNECTS DO NOT MEET 110.26 |
| CLEARANCE REQUIREMENTS. |
| |
| 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| CHANGE. |
| |
| 4} NOTE #20 INCORRECTLY REFERENCES 2204 FBC AND 907 |
| NFPA-72. THE CORRECT REFERENCE STANDARDS PER 2004 FBC |
| ARE R313 RESIDENTIAL AND CHAPTER 11NFPA-72, 2002 |
| EDITION. PLEASE CORRECT FOR CLARITY IN THE FIELD. |
| |
| 5} A RECEPTACLE, AS WELL AS THE LIGHT INDICATED ON |
| SHEET E-2, IS REQUIRED IN THE ATTIC FOR SERVICING THE |
| AIR HANDLER PER 210.63 NEC AND M1305.1.3.1 FBC. |
| |
| 6} A RECEPTACLE PER 210.52(D) IS REQUIRED IN BATH #1 |
| SHEET E-2. |
| |
| NOTE: THE #2 EQUIPMENT GROUND RAN WITH THE PANEL |
| FEEDERS, ALTHOUGH NOT A VIOLATION, IS ONLY REQUIRED TO |
| BE #6CU. IF IT REMAINS #2 ON THE PLAN IT MUST BE |
| INSTALLED OR A REVISION WILL BE REQUIRED TO MAKE THE |
| CHANGE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |