 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} 210.52(B)(2) ISLAND COUNTER SPACES AT LEAST ONE
 RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER
 SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN
 ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE
 RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE
 RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND
 INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN
 210.52(C)(4).
  
 2} 210.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS
 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.
  
 2} THE CONDENSER DISCONNECTS DO NOT MEET 110.26
 CLEARANCE REQUIREMENTS.
  
 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 4} NOTE #20 INCORRECTLY REFERENCES 2204 FBC AND 907
 NFPA-72. THE CORRECT REFERENCE STANDARDS PER 2004 FBC
 ARE R313 RESIDENTIAL AND CHAPTER 11NFPA-72, 2002
 EDITION. PLEASE CORRECT FOR CLARITY IN THE FIELD.
  
 5} A RECEPTACLE, AS WELL AS THE LIGHT INDICATED ON
 SHEET E-2, IS REQUIRED IN THE ATTIC FOR SERVICING THE
 AIR HANDLER PER 210.63 NEC AND M1305.1.3.1 FBC.
  
 6} A RECEPTACLE PER 210.52(D) IS REQUIRED IN BATH #1
 SHEET E-2.
  
 NOTE: THE #2 EQUIPMENT GROUND RAN WITH THE PANEL
 FEEDERS, ALTHOUGH NOT A VIOLATION, IS ONLY REQUIRED TO
 BE #6CU. IF IT REMAINS #2 ON THE PLAN IT MUST BE
 INSTALLED OR A REVISION WILL BE REQUIRED TO MAKE THE
 CHANGE.
  