2007-04-23 07:16:20 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) THE LICENSE NUMBER FOR THE ARCHITECTURAL FIRM IS |
| MISSING FROM THE TITLE BLOCK. SEE FAC 61G1-16.004. |
| |
| 4) FBC TABLE R301.5 REQUIRES EXTERIOR BALCONIES TO HAVE |
| A LIVE LOAD OF 60 PSF. PLEASE CORRECT THE STRUCTURAL |
| NOTE ON SHEET A2. |
| |
| 5) ON SHEET A2 COLUMNS C8 ARE INCORRECTLY SPECIFIED AT |
| THE FRONT ENTRY. |
| |
| 6) SPECIFY THE SIZES OF THE ATTIC ACCESSES ON THE |
| PLANS. |
| |
| 7) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, |
| INSTALLATION INSTRUCTIONS AND LISTING INFORMATION FOR |
| THE ISOKERN FLUELESS FIREPLACE. |
| |
| 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS, |
| INSTALLATION INSTRUCTIONS AND LISTING INFORMATION FOR |
| THE GAS BBQ ON THE LOGGIA. NOTE: THE CEILING OF THE |
| LOGGIA IS COVERED WITH FLAMMABLE MATERIAL. |
| |
| 9) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE SPRAY FOAM INSULATION |
| THAT WILL BE INSTALLED IN THE VENTLESS ATTIC. |
| |
| 10) PROVIDE ADDITIONAL INFORMATION FOR THE CHIMNEY. IS |
| THIS A DECORATIVE ASSEMBLY OR WILL IT BE FUNCTIONING? |
| PROVIDE DETAILS FOR THE CHIMNEY CAP SHOWN ON THE |
| ELEVATIONS ON A8. THE ELEVATION SHOWS A STUCCO BAND |
| WHICH IS NOT SHOWN ON THE STRUCTURAL DETAILS. THE |
| TRUSSES WILL BE REQUIRED TO BE DESIGNED FOR THE CHIMNEY |
| ATTACHMENT. |
| |
| 11) SHOW COMPLIANCE WITH R502.12 DRAFTSTOPPING |
| REQUIRED. |
| WHEN THERE IS USABLE SPACE BOTH ABOVE AND BELOW THE |
| CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS |
| SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED |
| SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 M 2 ). |
| DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO |
| APPROXIMATELY EQUAL AREAS. WHERE THE ASSEMBLY IS |
| ENCLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING |
| MEMBRANE BELOW DRAFTSTOPPING SHALL BE PROVIDED IN |
| FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING |
| CIRCUMSTANCES: |
| 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. 2. |
| FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB OR |
| PERFORATED MEMBERS. |
| SPECIFY THE LOCATION OF DRAFTSTOPPING AND MATERIAL THAT |
| WILL BE USED. SEE R502.12.1. |
| |
| 12) PLEASE REVISE ROOF SHEATHING FASTENING NOTES ON A7. |
| THE 2006 REVISIONS TO THE 2004 FBC REQUIRES RING SHANK |
| NAILS TO BE USED IN ALL ROOF ZONES. FBC R803.2.3.1 |
| |
| 13) SPECIFY THE TREAD DEPTH OF THE STAIRS ON SHEET A11. |
| SEE R311.5.3.2. |
| |
| 14) SPECIFY THE ATTACHMENT THAT WILL BE USED FOR THE |
| MONIER CONCRETE ROOF TILES. CIRCLE THE APPROPRIATE |
| FASTENER OR ADHESIVE ON THE PRODUCT APPROVAL. |
| |
| 15) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS. |
| |
| 16) SUBMIT DRAWING #IRC-5316-175-45 WHICH IS REQUIRED |
| TO ACCOMPANY THE PRODUCT APPROVAL FOR THE OVERHEAD |
| GARAGE DOOR. |
| |
| 17) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL |
| MULLIONS, RAISED PANEL/HALF GLASS DOORS AT THE GARAGE |
| AND LAUNDRY ROOM, THE 4' X 8' MAHOGANY ENTRY DOOR AND |
| THE FIXED GLASS TRANSOM WINDOW ABOVE WINDOW A. |
| |
| 18) THE FLORIDA COVERSHEET SUBMITTED FOR THE MARVIN |
| IMPACT CASEMENT WINDOW IS NOT THE CORRECT ONE FOR NOA |
| 02-1113.04. IF THERE IS NO FL# THAT CORRESPONDS TO IT, |
| THE NOA IS ACCEPTABLE WITHOUT THE FL COVERSHEET. |
| HOWEVER, IT IS STILL REQUIRED TO BE APPROVED IN WRITING |
| BY THE DESIGNER OF RECORD. |
| |
| 19) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| CASEMENT WINDOWS DO NOT HAVE DESIGN PRESSURES ON PAGE 7 |
| OF THE NOA THAT ARE ACCEPTABLE FOR WINDOWS A & K AS |
| SPECIFIED IN THE SCHEDULE ON A5. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |