2007-12-03 09:45:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN EQUIPMENT LISTING SHOWS THE A/C
 SYSTEM AS A 12 SEER, SEE 2004 FBC 13-607.1.ABC.3.2.1
 MINIMUM SEER IS 13. PLEASE CORRECT.
  
 2) COULD NOT FIND THE MODEL NUMBERS LISTED ON THE
 MECHANICAL PLAN FOR THE A/C SYSTEM ON THE ARI DIRECTORY
 WEB SITE. PLEASE CORRECT MODEL NUMBERS OR SUBMIT ARI
 REFERENCE NUMBER.
  
 3) THE SUPPLY AIR DUCT (FLEX) FROM THE MIXING BOX TO
 THE BATHROOM NEEDS TO BE SIZED, SEE YELLOW HIGH LIGHT
 ON MECHANICAL PLAN.
  