2007-12-03 09:45:57 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) MECHANICAL PLAN EQUIPMENT LISTING SHOWS THE A/C | | SYSTEM AS A 12 SEER, SEE 2004 FBC 13-607.1.ABC.3.2.1 | | MINIMUM SEER IS 13. PLEASE CORRECT. | | | | 2) COULD NOT FIND THE MODEL NUMBERS LISTED ON THE | | MECHANICAL PLAN FOR THE A/C SYSTEM ON THE ARI DIRECTORY | | WEB SITE. PLEASE CORRECT MODEL NUMBERS OR SUBMIT ARI | | REFERENCE NUMBER. | | | | 3) THE SUPPLY AIR DUCT (FLEX) FROM THE MIXING BOX TO | | THE BATHROOM NEEDS TO BE SIZED, SEE YELLOW HIGH LIGHT | | ON MECHANICAL PLAN. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|