Plan Review Notes
Plan Review Notes For Permit 07030530
Permit Number 07030530
Review Stop B
Sequence Number 2
Notes
Date Text
2007-12-05 11:29:58BUILDING REVIEW SECOND CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT).
  
 2- AFTER DRAWINGS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT. (REPEAT COMMENT).
  
 3- A)REVISE GENERAL CONSTRUCTION NOTE REGARDING
 CONCRETE BLOCK COMPRESSIVE STRENGTH. SEE SEC. R606.4
 2004 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED.
 ***IT WAS CHANGED TO 100PSI. THIS IS INCORRECT. REVISE
 AS REQUIRED.
  
 B)WIND LOAD AFFIDAVIT CHART: * CLARIFY WHY
 INTERNAL PRESSURE COEFFICIENT IS 0.
 ***REVISED AFFIDAVIT STATES THAT USING SHUTTERS TO
 PROTECT AGAINST WIND-BORNE DEBRIS.BUILDING WAS
 DESIGNED AS ENCLOSED,THAT'S WHY SHUTTERS OR IMPACT
 GLAZING IS USED TO CONSIDERED THE BUILDING AS ENCLOSED.
 THERE ARE STILL INTERNAL PRESSURES TO BE CONSIDERED.
 SEE FIGURE 6-5 OF ASCE 7-02 AND REVISED AS REQUIRED.
  
 C) PROVIDE COMPLETE INFORMATION FOR GUARDRAIL AT
 REAR AREASHOWING COMPLIANCE WITH TABLE R301.5AND
 SEC. R312 OF 2004 FLORIDA RESIDENTIALCODE.
 INFORMATION SUBMITTED DOESN'T PROVIDE ALL THIS
 INFORMATION.MISSING INFORMATION COMPLYING WITH TABLE
 R301.5 AND PICKETS SPACING SO A 4" SPHERE CAN'T PASS
 THRU.
  
 D) PROVIDE FINISH REAR PORCH ELEVATION AND GRADE
 ELEVATION TO VERIFY IF GUARDRAIL ISREQUIRED. SEC.
 R312OF 2004 FLORIDA RESIDENTIAL CODE. SEE SURVEY FOR
 FINISH ELEVATIONS SHOWN.
  
 E) NUMBER OF TREADS SHOWN ON REAR PORCH PLAN DON'T
 MATCH NUMBER OF RISERS SPECIFIED ON PLAN. REVISE AS
 REQUIRED. PLAN SHOWS FOUR RISERS.
  
 4- SHEET A3:
 A) PROVIDE CRAWL SPACE VENTILATION AND ACCESS.SEE
 SEC. R4082004 FLORIDA RESIDENTIAL CODE FOR MIN. SIZES
 AND LOCATION.
 ***INFORMATION SUBMITTED IS INCOMPLETE. PROVIDE CRAWL
 SPACE VENTILATION CALCULATIONS TO VERIFY THAT THE TWO
 PROPOSED 16"X16" OPENINGS ARE ADEQUATE. ALSO, PROVIDE
 ACCESS AS REQUIRED BY SEC. R408.3.SPECIFY SIZE OF
 OPENING TO GO FROM ONE SIDE OF THE CRAWL SPACE TO THE
 OTHER.INFORMATION SUBMITTED ONLY SHOWS A 16" DEEP
 LINTEL, BUT IT DOESN'T SPECIFY SIZE OF OPENING.IN
 ADDITION, STILL NEED TO PROVIDE ACCESS TO THE CRAWL
 SPACE FROM THE OUTSIDE OR INSIDE. SEE SEC. R312 AND
 REVISE AS REQUIRED.
  
 B) TYPICAL WALL SECTION:CLARIFY NOTE REGARDING
 FOOTING REINFORCEMENT CONCRETE COVER.3" & 2" COVER AT
 BOTTOM?. SEE SEC. R403 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR MIN. COVERING REQUIRED.
 *** MINIMUM 3" COVERING REQUIRED IS AT BOTTOM AND SIDE
 ALSO. REVISE AS REQUIRED OR SPECIFY WHICH CODE SECTION
 STATES THAT 2" SIDE COVER IS REQUIRED.
  
  
 5- SHEET A4:
 A) R4412IS NOT AN STANDARDTEST METHOD FOR WIND
 RESISTANCE OF ASPHALT SHINGLES WITH A WIND VELOCITY OF
 140MPH (MINIMUM).REVISE NOTE AS REQUIRED. WHERE IS
 THIS INFORMATION TAKEN FROM?.
  
 6- SHEET A5:REVISE ROOF SHEATHING NAILING SCHEDULE.
 SEE SEC. R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE AND
 REVISEFASTENER SPACING AS REQUIRED FOR ROOF ZONE 3.
  
 7- REVISEENERGY CALCULATIONS:
 A) THERE IS NOT CONCRETE SLAB ON GRADE. SEE PLANS
 AND REVISE AS REQUIRED.
  
 B)FILL IN ALLTHE INFORMATION ON TOP OF FORM.
  
 8- ENGINEERING FIRM TO PROVIDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER IN ALL DRAWINGS AS REQUIRED BY
 SEC. 61G15-23..002 OF FLORIDA ADMINISTRATIVE CODE.
 *** PROVIDE THE CERTIFICATE OF AUTHORIZATION NUMBER
 OR REMOVE THE SAGE NAME FROM THE TITLE BLOCK.OR GET
 FLORIDA BOARD OF PROFESSIONAL ENGINEERSAPPROVAL TO
 USE THE SAGE NAME.
  
 9- SPECIFY ALL LOADS INCLUDING LIVE AND DEAD LOADS AS
 REQUIRED BY SEC. R301 AND TABLE R301.5OF 2004 FLORIDA
 RESIDENTIAL CODE.
 *** MISSING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5
  
 10- PROVIDE SOIL TEST REPORT. (REPEAT COMMENT).
  
 11- SURVEYSUBMITTED:
 A) MISSING REAR DECK.
  
 B) NOTE #6 DOESN'T ALLOW THIS DRAWING TO BE USED FOR
 CONSTRUCTION.
  
 12- BRING DRAWINGS FOR HISTORIC APPROVAL AND STAMPING
 PRIOR TO SUBMITTING THEM TO THIS OFFICE. (REPEAT
 COMMENT).
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) ALL TRUSS CONNECTORS SPECIFIED ON PLANS. (REPEAT
 COMMENT).
  
 B) ROOF SHINGLES. NOA 04-0820.01 SUBMITTED WAS
 SUPERSEDED BY DADE COUNTY. SEE ATTACHED COPY. (REPEAT
 COMMENT).
 NEED TO PROVIDE NOA THAT SUPERSEDED ABOVE ONE.
  
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 *** ENGINEER RESPONSE LETTER SAID THAT NOTE WAS
 ADDED. NO INFORMATION WAS FOUND IN THIS PACKAGE.
 IF SEPARATE LETTER IS PROVIDED TO SHOW REVIEW OF
 PRODUCT APPROVALS, THEN, PLEASEMAKE SURE CORRECT NOA
 NUMBERS,COMPANY NAME, SPECIFIC PRODUCT, MODEL, ETC.
 IS LISTED AND MATCHING PRODUCT APPROVALS SUBMITTED TO
 AVOID CONFLICTS OR UNNECESSARY DELAYS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712