Plan Review Notes For Permit 07030530 |
Permit Number |
07030530 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-27 15:41:38 | *** DENIED *** | | 1) PLEASE SUBMIT ENERGY CALCULATIONS,SEE 2004 FBC | | 13-101.2.2. | | | | 2) MECHANICAL PERMIT NUMBER 07030532 APPLIED FOR BUT NO | | MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE | | SUBMIT MECHANICAL PLANS FOR REVIEW, SEE 2004 FBC CITY | | WPB AMEND. 106.3.5.4 (10). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|