Plan Review Notes For Permit 07030530
Permit Number 07030530
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-20 17:45:10 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE CORRECT THE ELECTRICAL NOTES AS FOLLOWS:
 #2 REFERENCES THE "SOUTH FLORIDA BUILDING CODE",
 WHICH IS NO LONGER IN USE. THE STATE OF FLORIDA PER 553
 FS HAS ADOPTED THE 2004 FBC AND ALL REFERENCED
 MATERIAL.
 #3 PER 210.8(A)(6) ALL COUNTER TOP RECEPTACLES
 SHALL BE GFCI PROTECTED.
 #4 SMOKE ALARMS MUST BE AFCI PROTECTED. THE NOTE
 REFERENCES "SMOKE DETECTORS, NOT SMOKE ALARMS. SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR
 ALARMS, TO AVOID CONFUSION IN THE FIELD.
 #7 REFERENCES A CODE ARTICLE FROM 1996.THE 2005 NEC
 WAS ADOPTED BY THE FLORIDA LEGISLATURE EFFECTIVE 8
 DECEMBER 2006.
  
 2} THE "EXISTING" SERVICE IS IN VIOLATION OF 250.66,
 MUST HAVE A #6 EQUIPMENT GROUND RAN WITH THE FEEDERS
 FROM THE DISCONNECT SHOWN ON THE RISER (BUT NOT ON THE
 FLOOR PLAN) TO THE PANEL. THE EXISTING #6 GEC IS
 REQUIRED TO BE #4 PER 250.66. ALSO VERIFY IT BEING RAN
 IN A 2" CONDUIT.
  
 3} THE REQUIRED BATH CIRCUITS PER 210.11(C)(3) ARE NOT
 LISTED ON THE PANEL SCHEDULE.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]