2007-03-20 17:45:10 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE CORRECT THE ELECTRICAL NOTES AS FOLLOWS: |
| #2 REFERENCES THE "SOUTH FLORIDA BUILDING CODE", |
| WHICH IS NO LONGER IN USE. THE STATE OF FLORIDA PER 553 |
| FS HAS ADOPTED THE 2004 FBC AND ALL REFERENCED |
| MATERIAL. |
| #3 PER 210.8(A)(6) ALL COUNTER TOP RECEPTACLES |
| SHALL BE GFCI PROTECTED. |
| #4 SMOKE ALARMS MUST BE AFCI PROTECTED. THE NOTE |
| REFERENCES "SMOKE DETECTORS, NOT SMOKE ALARMS. SEE THE |
| DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, |
| CLARIFY IF USING DETECTORS OR |
| ALARMS, TO AVOID CONFUSION IN THE FIELD. |
| #7 REFERENCES A CODE ARTICLE FROM 1996.THE 2005 NEC |
| WAS ADOPTED BY THE FLORIDA LEGISLATURE EFFECTIVE 8 |
| DECEMBER 2006. |
| |
| 2} THE "EXISTING" SERVICE IS IN VIOLATION OF 250.66, |
| MUST HAVE A #6 EQUIPMENT GROUND RAN WITH THE FEEDERS |
| FROM THE DISCONNECT SHOWN ON THE RISER (BUT NOT ON THE |
| FLOOR PLAN) TO THE PANEL. THE EXISTING #6 GEC IS |
| REQUIRED TO BE #4 PER 250.66. ALSO VERIFY IT BEING RAN |
| IN A 2" CONDUIT. |
| |
| 3} THE REQUIRED BATH CIRCUITS PER 210.11(C)(3) ARE NOT |
| LISTED ON THE PANEL SCHEDULE. |
| |
| 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE |
| DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES |
| ARE APPLICABLE. |
| |