Plan Review Notes
Plan Review Notes For Permit 07030530
Permit Number 07030530
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-16 18:02:43BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- AFTER DRAWINGS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT.
  
 3- SHEET A1:
 A) BUILDING DIMENSIONS AND SETBACKS DON'T MATCH
 THOSE DIMENSIONS SHOWN ON SURVEY. REVISE AS REQUIRED.
 B) REVISE INFORMATION GIVEN:* THIS IS NOT A
 MULTIFAMILY DWELLING.** THERE IS NOT NEW PORCH. SEE
 PLANS.
 C) REVISE DESIGN DATA: * DESIGN CONSIDERATION IS FOR
 IS FOR INTERIOR ZONES AND END ZONES, NOT INTERIOR AND
 EXTERIOR ZONES. REVISE AS REQUIRED.** UPDATE BUILDING
 CODE. SEE FBC 2004.
 D) THIS IS PENN STREET, NOT AVENUE. REVISE AS
 REQUIRED.
  
 4- SHEET A2:
 A) BUILDING DIMENSIONS DON'T MATCH SURVEY. REVISE AS
 REQUIRED.
 B) SPECIFY SAFETY GLASS FOR NEW BATHROOM WINDOW.
 SEC. R308.42004 FLORIDA RESIDENTIAL CODE.
 C) SPECIFY ATTIC ACCESS LOCATION AND SIZE. SEC. R807
 2004 FLORIDA RESIDENTIAL CODE.
 D) REVISE DESIGN DATA INFORMATION. SEE ITEM 3(C)
 ABOVE.
 E) WALL LEGEND CALLS FOR 2X4 BEARING WALL, WHILE
 FLOOR PLAN SHOWS 2X6 BEARING WALL. REVISE AS REQUIRED.
  
 F) REVISE GENERAL CONSTRUCTION NOTE REGARDING
 CONCRETE BLOCK COMPRESSIVE STRENGTH. SEE SEC. R606.4
 2004 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 G) WIND LOAD AFFIDAVIT CHART: * CLARIFY WHY INTERNAL
 PRESSURE COEFFICIENT IS 0.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.** AND, REVISE WIND PRESSURES
 ZONES, THEY ARE INTERIOR AND END ZONES, NOT INTERIOR
 AND EXTERIOR ZONES.
 F) PROVIDE COMPLETE INFORMATION FOR STEPS, LANDING,
 HANDRAIL AND GUARDRAIL AT REAR AREA BY SLIDING GLASS
 DOORS. SEE SEC. R311.5 AND R3122004 FLORIDA
 RESIDENTIAL CODE.
  
 5- SHEET A3:
 A) PROVIDE CRAWL SPACE VENTILATION AND ACCESS.SEE
 SEC. R4082004 FLORIDA RESIDENTIAL CODE FOR MIN. SIZES
 AND LOCATION.
 B) TYPICAL WALL FRAMING DETAIL/SECTION DOESN'T APPLY
 TO THIS PROJECT. SEE TYPICAL WALL SECTION AND REVISE AS
 REQUIRED TO MATCH.
 C) TYPICAL WALL SECTION:
 * SPECIFY HOW COMPLYING WITH SEC. R3192004 FLORIDA
 RESIDENTIAL CODE.
 ** SPECIFY HOW COMPLYING WITH SEC. R3202004
 FLORIDA RESIDENTIAL CODE.
 *** SPECIFY DESIGN CRITERIAFOR SOIL BEARING
 CAPACITY.
 **** IT'S NOT CLEAR IF USING PRE-ENGINEERED ROOF
 TRUSSES OR CONVENTIONAL ROOF FRAMING. INFORMATION IS
 MISLEADING AND DOESN'T MATCH ROOF FRAMING PLAN.
 ***** SIMPSON MAS CONNECTOR SPECIFIED TO FASTEN 2X6
 STUD AT BOTTOM DOESN'T WORK FOR THIS APPLICATION.
 REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 ****** CLARIFY NOTE REGARDING FOOTING REINFORCEMENT
 CONCRETE COVER.3" & 2" COVER AT BOTTOM?. SEE SEC.
 R403 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN. COVERING
 REQUIRED.
 ******* PROVIDE COMPLETE SPECS FOR FASTENING OF STUD
 WALL TO STEM WALL. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 D)PROVIDE INFORMATION FOR STEPS AT SLIDING GLASS
 DOORS FROM FAMILY ROOM.
 E)PROVIDE SECTION/DETAIL AT 16" DEEP LINTEL THAT
 PROVIDE ACCESS FROM ONE SIDE OF HOUSE TO THE OTHER. SEE
 FOUNDATION PLAN. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 F)REVISE SIZE OF CRAWL SPACE VENTILATION.
 COORDINATE WITH ITEM 3(A) ABOVE.
 G)REVISE ATTIC VENTING CALCULATIONS. INCLUDE SIZE
 SHOWN ON TYP. WALL SECTION AND SPECIFY NET CLEAR
 OPENING.
  
 6- SHEET A4:
 A) REVISE DESIGN DATA FOR WIND LOADS. SPECIFY
 CURRENT CODE AND THERE IS NOT EXTERIOR ZONE.
 B) ASTM D-3161 IS NOT A TEST METHOD FOR 140MPH.
 REVIEWSUCH STANDARD AND REVISE NOTE AS REQUIRED.
  
 7- SHEET A5:
 A) REVISE ROOF SHEATHING NAILING SCHEDULE. SEE SEC.
 R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 TYPE OF FASTENER ASREQUIRED.
 B) REVISE STRAP TYPE NAILING TABLE.NEED TO SPECIFY
 WOOD TO WOOD CONNECTORS OR WOOD TO MASONRY CONNECTORS
 AS REQUIRED.EG: CONNECTOR A DOESN'T WORK. NEED WOOD
 TO WOOD CONNECTOR.REVISE ALL SCHEDULE AS REQUIRED.
 C) PROVIDE COMPLETE DETAIL AND SPECS SHOWING COMPLIANCE
 WITH SEC. 2304.3.4 FBC 2004 AND SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004. DETAIL FOR TYP. GABLE END WALL
 IS INCOMPLETE (THERE ARE DETAILS THAT ARE NOT PROVIDED)
 AND DOESN'T COMPLY WITH THIS SECTION.
  
 8- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004.
  
 9- ENGINEERING FIRM TO PROVIDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER IN ALL DRAWINGS AS REQUIRED BY
 SEC. 61G15-23..002 OF FLORIDA ADMINISTRATIVE CODE.
  
 10- SPECIFY ALL LOADS INCLUDING LIVE AND DEAD LOADS AS
 REQUIRED BY SEC. R301 AND TABLE R301.5OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 11- PROVIDE SOIL TEST REPORT.
  
 12- PROVIDE SURVEYWITH ORIGINAL SIGNATURE AS REQUIRED
 BY CHAPTER 472FLORIDA STATUTE.
  
 13- BRING DRAWINGS FOR HISTORIC APPROVAL AND STAMPING
 PRIOR TO SUBMITTING THEM TO THIS OFFICE.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) ALL TRUSS CONNECTORS SPECIFIED ON PLANS.
 B) ROOF SHINGLES. NOA 04-0820.01 SUBMITTED WAS
 SUPERSEDED BY DADE COUNTY. SEE ATTACHED COPY.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 16- VALUE DECLARED ON THE PERMIT APPLICATION IS TOO
 LOW.OWES $856.50 FOR UPDATED VALUATION AND RADON
 FEES. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712