2007-03-14 17:26:14DENIED BY BUILDING
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING ON THE
 PERMIT APPLICATION.
  
 2)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 3) THE MAXIMUM DESIGN PRESSURE OF -45 PSF ON PAGE 30 OF
 THE NOA IS TOO LOW FOR ROOF ZONES 2 AND 3 AND GENERAL
 LIMITATION #9 DOES NOT ALLOW ANY INCREASES. SEE PAGE 34
 OF NOA.
  