Plan Review Notes For Permit 07030516 |
Permit Number |
07030516 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-03-19 13:16:43 | DENIED BY BUILDING | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING ON THE | | PERMIT APPLICATION. | | | | 2) TWO FASTENING OPTIONS ARE GIVEN ON PAGE 32 OF THE | | NOA. SPECIFY WHICH ONE WILL BE USED BY CIRCLING THE | | APPROPRIATE ONE. | | | | 3) THE MAXIMUM DESIGN PRESSURE FOR THIS ASSEMBLY IS | | -52.5 PSF. THIS DESIGN PRESSURE IS TOO LOW FOR ROOF | | ZONES 2 AND 3. ENHANCED FASTENING, AS ALLOWED BY | | GENERAL LIMITATION #7 ON PAGE 34 WILL BE REQUIRED IN | | THESE ZONES. SUBMIT RAS 117 CALCULATIONS FOR THESE | | AREAS. SEE #7 ON PAGE 34 OF THE NOA. NOTE: RAS 117 | | LIMITS THE MINIMUM FASTENER SEPARATION TO NOT LESS THAN | | 4" O.C. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|