2007-03-14 17:12:20DENIED BY BUILDING
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING ON THE
 PERMIT APPLICATION.
  
 2)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 3) THE MAXIMUM DESIGN PRESSURE LISTED ON PAGE 43OF
 THE NOAOF -52 PSF IS TOO LOW FOR THE PERIMETER AND
 CORNER AREAS. GENERAL LIMITATION #7 ALLOWS ENHANCED
 FASTENING IN ACCORDANCE WITH RAS 117.HOWEVER, THE NOA
 REQUIRES THAT THE RAS 117 CALCULATIONS BE PREPARED,
 SIGNED AND SEALED BY A FLORIDA REGISTERED ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT. SUBMIT SIGNED
 AND SEALED RAS 117 CLACULATIONS.
  