Plan Review Notes For Permit 07030516 |
Permit Number |
07030516 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-14 17:12:20 | DENIED BY BUILDING | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING ON THE | | PERMIT APPLICATION. | | | | 2)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. | | | | 3) THE MAXIMUM DESIGN PRESSURE LISTED ON PAGE 43OF | | THE NOAOF -52 PSF IS TOO LOW FOR THE PERIMETER AND | | CORNER AREAS. GENERAL LIMITATION #7 ALLOWS ENHANCED | | FASTENING IN ACCORDANCE WITH RAS 117.HOWEVER, THE NOA | | REQUIRES THAT THE RAS 117 CALCULATIONS BE PREPARED, | | SIGNED AND SEALED BY A FLORIDA REGISTERED ENGINEER, | | ARCHITECT OR REGISTERED ROOF CONSULTANT. SUBMIT SIGNED | | AND SEALED RAS 117 CLACULATIONS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|