Plan Review Notes
Plan Review Notes For Permit 07030506
Permit Number 07030506
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-26 07:18:04DENIED BY BUILDING
  
 1) SEE COMMENT NUMBER 2 FROM THE FIRST REVIEW.
 THE MAXIMUM DESIGN PRESSURE LISTED ON THE NOA IS -52.5
 PSF FOR THE SELECTED POLYGLASS ROOF SYSTEM. THIS IS TOO
 LOW FOR THE PERIMETER AND CORNER AREAS. SUBMIT SIGNED
 AND SEALED RAS 117 CALCULATIONS FROM A FLORIDA
 REGISTERED ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT FOR ENHANCED FASTENING AS ALLOWED BY GENERAL
 LIMITATION NUMBER 7 ON THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714