2007-03-14 15:07:30 | DENIED BY BUILDING | | | | 1)WPB ADMIN CODE 106.3* PRODUCT | | APPROVALS. THOSE PRODUCT WHICH ARE | | REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 2) THE MAXIMUM DESIGN PRESSURE LISTED ON THE NOA IS | | -52.5 PSF FOR THE SELECTED SYSTEM. THIS IS TOO LOW FOR | | THE PERIMETER AND CORNER AREAS. SUBMIT SIGNED AND | | SEALED RAS 117 CALCULATIONS FROM A FLORIDA REGISTERED | | ENGINEER, ARCHITECT OR REGISTERED ROOF CONSULTANT FOR | | ENHANCED FASTENING AS ALLOWED BY GENERAL LIMITATION | | NUMBER 7 ON THE NOA. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|