2007-03-27 11:35:10*** DENIED ***
 1) PLEASE SHOW THE SIZE OFF THE RETURN AIR GRILL TO THE
 AIR HANDLER UNIT.
  
 2) ELECTRICAL PLANS ARE CALLING FOR A 7.5 KW
 ELECT.HEATER, AND THE MECHANICAL PLANS ARE CALLING FOR
 A 10 KW HEATER THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) THE MECHANICAL PLANS ARE CALLING FOR A 5 TON A/C
 SYSTEM WHICH IS TO LARGE. MANUAL J CALCULATIONS ARE
 CALLING FOR 18,235 SENSIBLE BTU'S, AND THE MECHANICAL
 PLANS ARE CALLING FOR 38,500 SENSIBLE BTU'S, THE PLANS
 CAN ONLY CALL FOR 15% MORE THAN THE MANUAL J
 CALCULATIONS, SEE 2004 FBC 13-607.1.ABC.1.1 (12-8-06
 REVISION). PLEASE CORRECT.
  
 4) THE ENERGY CALCULATIONS ARE CALLING FOR A 30 SEER
 A/C SYSTEM, AND THE MECHANICAL PLANS ARE CALLING FOR A
 13 SEER, THE TWO MUST COINCIDE, PLEASE CORRECT.
  