Plan Review Notes
Plan Review Notes For Permit 07030499
Permit Number 07030499
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-26 10:40:20 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 2} SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED PER
 R313.1 FBC, (OUTSID EACH SLEEPING ROOM), & 11.8.3.5
 NFPA-72.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. ALSO SMOKE ALARMS TO
 BE AFCI PROTECTED PER 210.12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  