2007-04-10 12:56:17BUILDING PLAN REVIEW
 PERMIT: 07030499
 ADD: 1039 18TH STREET
 CONT: DREAMALITIES CONSTRUCTION
 TEL: (561)842-5500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)WPB AMENDMENTS 108.3*THE VALUE IS LOW. IF IN THE
 OPINION OF THE BUILDING OFFICIAL THE CLAIMED VALUATION
 IS UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL
 BE DENIED. FOR PERMITTING PURPOSES, THE VALUE SHALL
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH NORMAL SITE WORK, ARCHITECTURAL AND
 DESIGN FEES. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS.
  
 5)R802.1.6TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SEC. R802.1.6.1, SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION. TRUSS DESIGN DRAWINGS SHALL INCLUDE, AT A
 MINIMUM, (1) DESIGN WIND SPEED AND EXPOSURE CATETORY
 (2) SLOPE OR DEPTH, SPAN AND SPACING, (3) LOCATION OF
 ALL JOINTS (4)REQUIRED BEARING WIDTHS. (5) DESIGN
 LOADS AS APPLICABLE. (5.1) TOP CHORD LIVE LOAD (5.2)
 TOP CHORD DEAD LOAD (5.3) BOTTON CHORD LIVE LOAD (5.4)
 BOTTOM CHORD DEAD LOAD. ETC.
  
 6)R319.1 LOCATION REQUIRED.
 IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY
 TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE
 THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY -RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS. (1)WOOD JOISTS OR THE BOTTOM OF A
 WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES (457
 MM) OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM)
 TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED
 AREA LOCATED WITHIN THE PERIPHERY OF THE BUILDING
 FOUNDATION.
 (2)ALL WOOD FRAMING MEMBERS THAT REST ON CONCRETE OR
 MASONRY EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8
 INCHES (203 MM) FROM THE EXPOSED GROUND. (5)WOOD
 SIDING, SHEATHING AND WALL FRAMING ON THE EXTERIOR OF A
 BUILDING HAVING A CLEARANCE OF LESS THAN 6 INCHES (152
 MM) FROM THE GROUND.
  
 7)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE THE STATE COVER SHEET
 FOR THE PRODUCT APPROVALS.
  
 8)THE ENERGY CALCULATION SHEETS ARE NOT LEGIBLE.
 PROVIDE CLEAR AND LEGIBLE INFORMATION. SEE NEW FORMS IN
 PACKAGE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  