Plan Review Notes
Plan Review Notes For Permit 07030479
Permit Number 07030479
Review Stop G
Sequence Number 2
Notes
Date Text
2007-06-29 11:31:16DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. THE MANUFACTURER'S RECOMMENDED SETBACK IN THE
 INSTALLATIOM MANUAL ON PAGE #5, 1.3 GENERATOR LOCATION,
 STATES "A GOOD RULE IS TO ALLOW FIVE FEET OF SPACE ON
 ALL SIDES". THERE IS NOT THE RECOMMENDED CLEARANCE
 BETWEEN THE GENERATOR AND THE RESIDENCE.
  
 NOTE: NO FUTHER ACTION CAN BE TAKEN REGARDING ISSUING
 THIS PERMIT AS LONG AS THERE IS A PREVIOUS APPLICATION
 OPEN (#06060449) FOR THIS INSTALLATION. THE OWNER MUST
 CONTACT ADRIANNA MCKENZIE, SUPERVISER, LICENSE/PERMITS,
 CONTRUCTION SERVICES DEPARTMENT(561-805-6681) TO CLEAR
 THIS MATTER UP.
  
 2.NOTE: THE RESUBMITTED DRAWING IS INDICATING THE
 EXISTING AS WELL AS THE PROPOSED GENERATOR BTU LOAD.
 BUT IT IS FAILING TO INDICATE THE LONGEST LENGTH OF THE
 SYSTEM OR THE LOCATION OF THE MP REGULATORS TO THE
 EXISTING APPLIANCES. PLEASE CLARIFY THIS AND PLEASE
 KNOW THAT THE GENERATOR LOCATION MAY CHANGE DUE TO
 CLEARENCES. (SEE COMMENT #1).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721