Plan Review Notes
Plan Review Notes For Permit 07030479
Permit Number 07030479
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-12 11:34:44 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS FOR THE GENERATOR.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED.
  
 3} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW