Date |
Text |
2008-06-02 14:51:52 | FAILED |
| |
| 1) REPEAT COMMENT - ORDINANCE NO. 3856-05 REQUIRES THE |
| SUBMITTAL OF A PHOTOMETRIC PLAN PRIOR TO BUILDING |
| PERMIT APPROVAL. |
| |
| 2) REPEAT COMMENT - AN APPROVED TREE ALTERATION PERMIT |
| IS REQUIRED.NOTE THAT THE TREE MITIGATION PLAN SHOWS |
| TREES REMAINING IN PLACE THAT ARE NOT DEPICTED ON THE |
| LANDSCAPE PLAN (EX. #20 & 21 ALONG NORTH PROPERTY LINE, |
| ETC).IT APPEARS THAT REMAINING TREE #72 IS IN A PAVED |
| AREA.ADDITIONALLY, THE NUMBER OF RELOCATED TREES IS |
| NOT ACCURATE BETWEEN THE MITIGATION PLAN AND THE |
| LANDSCAPE PLAN.PLEASE CONTACT BOB KUSSNER, LANDSCAPE |
| PLANNER, @ (561) 822-1435 FOR AN APPLICATION. |
| |
| 3) THE PARKING SPACE DETAIL ON SHEET A01.1 SHALL SHOW |
| THE STANDARD PARKING SPACE AS A MINIMUM OF 18 FEET IN |
| DEPTH.SHOWN AT 17 FEET 10 INCHES. |
| |
| 4) WHEN NORTHERNMOST HANDICAP PARKING SPACE WAS |
| RELOCATED, THE NUMBER OF SPACES PROVIDED WAS NOT |
| UPDATED TO STATE "6 SPACES" - SHEET A01.1. |
| |
| 5) THE LANDSCAPE PLAN WAS NOT UPDATED TO REFLECT THE |
| INSTALLATION OF THE HYDRANT IN AN ISLAND ALONG THE |
| NORTH PROPERTY LINE.THE PROPOSED TREE AND LANDSCAPE |
| WILL CONFLICT WITH THE HYDRANT.PLEASE NOTE THAT THE |
| FIRE LINE INSTALLED UNDERGROUND ALONG THE NORTHERN |
| PROPERTY LINE WILL CONFLICT WITH THE NORTHERN LANDSCAPE |
| BUFFER.THE FIRE LINE SHOULD RUN UNDER THE PAVING TO |
| AVOID THESE CONFLICTS. |
| |
| 6) PROVIDE THE PLANNING AND ZONING DEPARTMENT WITH NEW |
| CORRECTED SHEETS A01.1, A101, A302, A303 AND LP1 SO |
| THAT THE PLANS APPROVED BY THE MINOR AMENDMENT MAY BE |
| REVISED TO REFLECT THE BUILDING PLANS. |
| |
| 7) THE INFORMATION SUBMITTED WITH THE PERMIT HAD |
| GENERATOR SPECS.WHERE IS THE GENERATOR LOCATED? |
| |
| 8) PROVIDE EVIDENCE THAT THE FPL UTILITY EASEMENT HAS |
| BEEN ABANDONED. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1435. |