2008-07-01 08:04:37 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| MUNICIPAL CODE WPB |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| |
| 2. SHT 358-9 ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF |
| PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING |
| BUSINESS, THEY SHALL ALSO INDICATE THE NAME, ADDRESS |
| AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| ENGINEERING BUSINESS ON EACH SHEET.FAC |
| 61G15-23.002(1)(2) & FS 471.025. |
| ****RESPONSE NOTED, NOW SHEET 1 OF 1 HAS BEEN DELETED |
| BUT THE INDEX ON SHEETS A01.02 & 1 OF 6A STILL SHOWS |
| SHEET 358.9. PLEASE CORRELATE. |
| |
| 3. OK |
| |
| 4. SHT A01.3 SECONDARY ROOF DRAINS REQUIRED FOR THE |
| AREA NEAR STAIR G1, PUMP ROOM, LAWN EQUIP. ETC. |
| SECTIONS 1107.1 & 1107.2. |
| ****RESPONSE NOTED, BUT SECONDARY ROOF DRAINS ARE NOT |
| LOCATED ON SHT P-1B. |
| |
| 5. SHT A01.3 THERE IS NO PRIMARY OR SECONDARY ROOF |
| DRAINS INDICATED IN THE AREA OF STAIR G2, EMERGENCY |
| GENERATOR ROOM AND LIFT AS REQUIRED IN SECTIONS 1101.2, |
| 1107.1 & 1107.2. |
| ****RESPONSE NOTED, BUT THERE ARE NO PRIMARY OR |
| SECONDARY ROOF DRAINS SHOWN ON SHT P-1B. SHEET A01.3 |
| SHOWS THE PRIMARY ROOF DRAIN BUT NO SECONDARY ROOF |
| DRAIN. |
| |
| 6. OK |
| |
| 7. SHT A01.3ROOF DRAINS ARE SHOWN IN AREAS INDICATED |
| AS MULCH AREAS.MORE INFORMATION IS REQUIRED. PLEASE |
| INDICATE HOW THE MULCH WILL BE KEPT FROM DRAINING INTO |
| THE ROOF DRAINS AND OR CLOGING THE ROOF DRAINS AND |
| PREVENTING THEM FROM DRAINING PROPERLY.PLEASE SUBMIT |
| A DETAIL FOR THE DRAINS IN THESE AREAS. SECTION 104.6. |
| ****RESPONSE NOTED, BUT THE DETAIL D/A01.6 SHOWS ROCK |
| AROUND THE DRAIN THEN MULCH, WHERE AS THE ROOF DECK |
| PLAN SHOW ONLY GRAVEL. PLEASE CORRELATE. ALSO THE CODE |
| REQUIRES THAT THE ROOF DRAIN STRAINERS SHALL HAVE AN |
| AVAILABLE INLET AREA, ABOVE THE ROOF, OF NOT LESS THAN |
| ONE AND ONE-HALF TIMES THE AREA OF THE CONDUCTOR OR |
| LEADER TO WHICH THE DRAIN IS CONNECTED. PLEASE INDICATE |
| HOW THE STAINLESS STEEL MESH WILL PROVIDE THE REQUIRED |
| AVAILABLE INLET AREA. SECTION 1105.1. |
| |
| 8. SHT A01.3ROOF DRAINAGE INDICATES DETAILS A/A803 & |
| D/A803. SECTION 1105.1 STATES ROOF DRAINS SHALL HAVE |
| STRAINERS EXTENDING NOT LESS THAN 4 INCHES ABOVE THE |
| SURFACE OF THE ROOF IMMEDIATELY ADJACENT TO THE ROOF |
| DRAINS. STRAINER SHALL HAVE AN AVAILABLE INLET AREA, |
| ABOVE THE ROOF, OF NOT LESS THAN ONE AND ONE-HALF TIMES |
| THE AREA OF THE CONDUCTOR OR LEADER TO WHICH THE DRAIN |
| IS CONNECTED. PLEASE INDICATE HOW THIS AND THE FACT |
| THAT THE ROOF DRAIN WILL BE COVERED WITH ROCKS WILL |
| MEET THIS CODE REQUIREMENT. THERE IS A CONCERN THAT THE |
| GRASS CLIPPINGS, DIRT, MOSS BUILD UP ETC WILL |
| EVENTUALLY KEEP THE DRAIN FROM DRAINING AS INTENDED. |
| PLEASE SUBMIT INFORMATION ON HOW THIS WILL BE |
| ADDRESSED. SECTION 104.6. |
| ****RESPONSE NOTED, BUT THE INTENT OF THE CODE IS NOT |
| ADDRESSED. THE REQUIRED STRAINER IS NOT SHOWN AND THE |
| AVAILABLE INLET AREA IS IN QUESTION AS THERE IS |
| DRAINAGE ROCKS OVER THE ROOF DRAINS. SECTION 1105.1. |
| ALSO THE CONCERN THAT THE STAINLESS STEEL MESH WILL |
| FURTHER DIMINISH THE INLET AREA HAS TO BE ADDRESSED. |
| |
| 9. SHT A01.3 OVERFLOW DRAINS DETAILS B/A803 & C/A803 DO |
| NOT MEET THE INTENT OF THE CODE TO BE USED ONLY IN CASE |
| OF BLOCKAGE OF THE PRIMARY ROOF DRAINS. THESE DETAILS |
| INDICATE THAT THE DRAINS ARE FLUSH WITH THE ROOF AND |
| WILL DRAIN WHEN THE PRIMARY ROOF DRAINS DRAIN AND NOT |
| AFTER THE BUILDUP OF A BLOCKED PRIMARY DRAIN. DRAINS |
| INDICATED IN DETAIL C/A803 ARE SHOWN TO BE NEXT TO AN |
| AREA THAT HAS MULCH IN IT. PLEASE CLARIFY AND INDICATE |
| HOW THE MULCH WILL NOT BLOCK THE DRAINS. SECTION |
| 1107.1. |
| ****RESPONSE NOTED, BUTTHE COMMENT WAS FOR THE |
| OVERFLOW DRAINS AT THE PUTTING GREEN/CHIPPING GREEN |
| AREA. ADDING THE NOTE DOES NOT CHANGE THE FACT THAT THE |
| DRAINS ARE STILL SHOWN LEVEL WITH THE GREEN SURFACE. |
| ALSO THE PLANTER DRAINS ARE INDICATED AS DRAINING INTO |
| THE OVERFLOW DRAINS IN DETAIL "B". THIS WILL ALLOW |
| STORM WATER TO DRAIN INTO THE OVERFLOW DRAINS AND WILL |
| HAVE STORM WATER DRAINING EVERY TIME IT RAINS AND WILL |
| NOT INDICATE THAT THERE IS A BLOCKAGE IN THE PRIMARY |
| ROOF DRAIN SYSTEM AS INTENDED. SECTION 1107. |
| |
| 10. OK |
| |
| 11. SHT A01.3 SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH |
| DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT |
| CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM |
| ROOF AREAS ABOVE. |
| ****RESPONSE NOTED, BUT NO CALCULATION FOR THE AREAS BY |
| THE STAIRS AND WATER FEATURE AND THE STAIRS AND THE |
| GENERATOR ROOM WERE SUBMITTED. |
| |
| 12. OK |
| 13. OK |
| |
| 14. SHT A101 SHOW THE CLEAR FLOOR SPACE FOR ALL |
| ACCESSIBLE FIXTURES IN ALL TOILET ROOMS. SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16, |
| 11-4.17, 11-4.18, 11-4.19 AND 11-4.22 WITH ALL |
| SUBSECTIONS. |
| ****RESPONSE NOTED, BUT COMMENT DID NOT ADDRESS THE |
| COMMON TOILET ROOMS. THE RESPONSE ADDRESSED FHA-98 |
| REQUIREMENTS FOR THE UNITS. |
| |
| 15. OK |
| 16. OK |
| 17. OK |
| |
| 18. SHT A201 UNITS A & A REV. INDICATE THE BACKING FOR |
| THE TUB IN THE MASTER BATH PER PAGE 6.10.--THE WING |
| WALL NEXT TO THE W/C IN THE MASTER BATH TO BE A MAXIMUM |
| 2'0" PER PAGE 7.44.--LAVS SHALL BE CENTERED ON THE |
| 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR |
| FORWARD APPROACH WITH REMOVABLE BASE CABINET SHALL BE |
| INDICATED.--SHOW THE CLEAR FLOOR SPACE FOR THE |
| W/C'S. PAGE 7.43.--RANGE SHALL BE CENTERED ON THE |
| 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGES 7.4 & |
| 7.9. --THE OPENING FOR THE W/C'S IN BATH 2 SHALL BE |
| 33" AND MUST SHOW 18" OFF THE TUB OR LAV TO THE CENTER |
| OF THE FIXTURE AND 15" MIN. OFF THE OTHER FIXTURE. |
| PAGES 7.43, 7.44 & 7.45.--MINIMUM CLEARANCES |
| BETWEEN ALL COUNTERS, APPLIANCES, BASE CABINETS AND |
| WALLS SHALL BE 40". PAGES 7.8, 7.11, 7.22 & 7.23. 36" |
| IS SHOWN. PLEASE SHOW COMPLIANCE. |
| ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD |
| TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS |
| WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & |
| 6.11. |
| |
| 19. SHT A203 UNITS B & B REV. INDICATE THE BACKING FOR |
| THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE |
| CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH PER |
| PAGE 7.43.--THE W/C IN THE MASTER BATH SHALL BE 18" |
| OFF THE WALL TO THE CENTERLINE OF THE FIXTURE PER PAGE |
| 6.5.--LAVS SHALL BE CENTERED ON THE 48" DIMENSION |
| OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR FORWARD |
| APPROACH WITH REMOVABLE BASE CABINET SHALL BE |
| INDICATED.--BATH #2 OPENING FOR THE W/C SHALL BE |
| MINIMUM 33". INDICATE MEASURMENT FROM THE CENTERLINE OF |
| THE W/C TO THE SIDE OF THE VANITY PER PAGES 7.43, 7.44 |
| & 7.45.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS, |
| APPLIANCES, BASE CABINETS AND WALLS SHALL BE 40". |
| (SHOWN AS 36"). PAGES 7.8, 7.11, 7.22 & 7.23. 36". |
| PLEASE SHOW COMPLIANCE. |
| ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD |
| TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS |
| WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & |
| 6.11.--OPENING FOR W/C NOT SHOWN ON SHT A204 FOR |
| SECOND BATHROOM. ALSO SHOW BACKING FOR GRAB BARS IN |
| SECOND BATHROOM. REQUIREMENT 6. |
| |
| 20. SHT A205 UNIT C. INDICATE THE BACKING FOR THE TUB |
| IN THE MASTER BATH PER PAGE 6.10.-- SHOW THE CLEAR |
| FLOOR SPACE FOR THEUSABLE W/C PER PAGE 7.43.-- SHOW |
| THE CLEAR FLOOR SPACE FOR THE TUBS OR SHOWERS PER PAGES |
| 7.53 THRU 7.56.--W/C'S SHALL BE 1'6" OFF THE WALL |
| TO THE CENTERLINE OF THE FIXTURE PER PAGE 6.5. |
| ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD |
| TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS |
| WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & |
| 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN M/B & |
| BATHROOM 3. REQUIREMENT 6. |
| |
| 21. SHT A207 UNITS D & D REV.INDICATE THE BACKING FOR |
| THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE |
| CLEAR FLOOR SPACE FOR THE USABLE W/C PER PAGE 7.43.-- |
| SHOW THE OPENING FOR THE W/C IN BATH #2 TO BE A MINIMUM |
| OF 33". THE W/C SHALL BE 1'6" OFF ONE FIXTURE TO THE |
| CENTERLINE OF THE FIXTURE AND 15" MINIMUM OFF THE OTHER |
| FIXTURE OR VANITY CABINET PER PAGES 7.43 THRU 7.45.-- |
| MINIMUM CLEARANCES BETWEEN ALL COUNTERS, APPLIANCES, |
| BASE CABINETS & WALLS SHALL BE 40". PAGES 7.8, 7.11, |
| 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW COMPLIANCE. |
| ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD |
| TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS |
| WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & |
| 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN |
| BATHROOM 2. REQUIREMENT 6. |
| |
| 22. SHT A209 UNITS PHA & PHA REV. INDICATE THE BACKING |
| FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW |
| THE CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH |
| PER PAGE 7.43.--THE WING WALL NEXT TO THE W/C IN |
| THE MASTER BATH SHALL BE A MAXIMUM OF 2'0" PER PAGE |
| 7.44.--THE LAVS SHALL BE CENTERED ON THE 48" |
| DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR |
| FORWARD APPROACH.--A MINIMUM 33" OPENING IS |
| REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE |
| 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE, |
| AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY |
| CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS, |
| APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES |
| 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW |
| COMPLIANCE. |
| ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD |
| TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS |
| WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & |
| 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN |
| BATHROOM 2. REQUIREMENT 6. |
| |
| 23. SHT A212 UNITS PHB & PHB REV. INDICATE THE BACKING |
| FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW |
| THE CLEAR FLOOR SPACE FOR THE USABLE W/C IN THE MASTER |
| BATH PER PAGE 7.43.--THE W/C IN THE MASTER BATH |
| SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE |
| FIXTURE PER PAGE 6.5.--THE LAVS SHALL BE CENTERED |
| ON THE 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE |
| 7.48 OR FORWARD APPROACH.--A MINIMUM 33" OPENING IS |
| REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE |
| 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE, |
| AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY |
| CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS, |
| APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES |
| 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW |
| COMPLIANCE. |
| ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD |
| TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS |
| WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & |
| 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN |
| BATHROOM 2. REQUIREMENT 6. |
| |
| 24. OK |
| |
| 25. SHT A215 INDICATE THE BACKING FOR THE TUB IN BOTH |
| BATHS PER PAGE 6.10.--SHOW THE CLEAR FLOOR SPACE |
| FOR THE W/C IN BOTH BATHS PER PAGE 7.43.--THE W/C |
| IN BOTH BATHS SHALL BE 18" OFF THE WALL TO THE |
| CENTERLINE OF THE FIXTURE PER PAGE 6.5.--THE LAVS |
| IN THE MASTER BATH SHALL BE CENTERED ON THE 48" |
| DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR |
| FORWARD APPROACH. PLEASE SHOW COMPLIANCE. ****RESPONSE |
| NOTED, BUT RESPONSE ONLY SHOWS STANDARD TUB BACKING |
| REQUIREMENTS. THE BACKING FOR LARGER TUBS WITH DECKS |
| HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & 6.11.-- |
| SHOW THE BACKING FOR THE GRAB BARS IN M/B & BATHROOM 3. |
| REQUIREMENT 6. |
| |
| 26. OK |
| |
| 27. SHT A404 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR |
| W/C'S: |
| A. 11-4.16.5 FLUSH CONTROLS |
| ****RESPONSE NOTED, BUT THE FLUSH CONTROLS SHALL BE |
| LOCATED ON THE WIDE SIDE OF THE TANK. THIS IS NOT |
| INDICATED. |
| B. OK |
| __FOR LAVS: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| ****RESPONSE NOTED, BUT THE KNEE CLEARANCE, (29"), IS |
| NOT NOTED ON PLANS. |
| B. OK |
| |
| 28. SHT A405 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR |
| W/C'S: |
| A. OK |
| B. OK |
| C. 11-4.16.5 FLUSH CONTROLS |
| ****RESPONSE NOTED, BUT THE FLUSH CONTROLS SHALL BE |
| LOCATED ON THE WIDE SIDE OF THE TANK. THIS IS NOT |
| INDICATED. |
| __STALLS: |
| A. OK |
| __LAVS: |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| ****RESPONSE NOTED, BUT THE KNEE CLEARANCE, (29"), IS |
| NOT NOTED ON PLANS. |
| B. OK |
| C. OK |
| __FOR THE SHOWER: |
| A. OK |
| B. OK |
| |
| 29. OK |
| 30. OK |
| 31. OK |
| 32. OK |
| |
| 33.SHT A805 DETAIL A INDICATES A TRENCH DRAIN. PLEASE |
| INDICATE WHERE THIS CAN BE FOUND ON THE FLOOR PLAN. |
| SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT TRENCH DRAIN DETAIL STILL |
| SHOWN. |
| |
| 34. SHT A806 THE SQUARE FOOTAGE FOR ALL EXTERIOR |
| PLANTERS SHALL INDICATE 1/2 THE AREA OF ALL VERTICAL |
| WALLS. IN THE CASE OF PLANTERS AGAINST THE BUILDING |
| THIS WILL INCLUDE THE 1/2 THE AREA OF THE BUILDING UP |
| TO THE PARAPETS OF THE ROOF. PLEASE SUBMIT THE |
| CALCULATIONS FOR THESE PLANTER DRAINS PER TABLE |
| 1106.3. |
| ****RESPONSE NOTED, BUT CLARIFICTION REQUIRED AS NO |
| PLANTER CALCULATIONS WERE SUBMITTED. |
| |
| 35. OK |
| 36. OK |
| 37. OK |
| 38. OK |
| 39. OK |
| |
| 40. SHT P-1B PLAN INDICATED ON SHEET INDEX HAS NOT BEEN |
| SUBMITTED. SUBMIT A 2ND FLOOR/ROOF PLAN FOR THE GARAGE. |
| SHOW ALL ROOF DRAINS, SECONDARY ROOF DRAINS, WATER |
| SUPPLY & BACKFLOW FOR THE WATERFALL ETC. SECTION |
| 106.1.2. |
| ****RESPONSE NOTED, BUT NO SECONDARY ROOF DRAINS WERE |
| SHOWN FOR AREAS 2, 3, 5, 16, 17 & 19. |
| |
| 41. OK |
| 42. OK |
| 43. OK |
| 44. OK |
| 45. OK |
| 46. OK |
| 47. OK |
| |
| 48. SHT P-3 SHOWS 4 PLANTER DRAINS BUT ONLY SHOWS |
| PIPING AND SQUARE FOOTAGE TO 2 PLANTER DRAINS. PLEASE |
| SHOW THE PIPING & SF TO ALL PLANTER DRAINS. SECTION |
| 1101.2. |
| ****RESPONSE NOTED, BUT THE INDOOR PLANTER ON THE SOUTH |
| SIDE OF THE LOBBY SHALL CONNECT TO THE STORM, NOT THE |
| SECONDARY DRAIN. |
| |
| 49. SHT P-3 RWL SHOWS 1730SF, BUT SAME RWL IS INDICATED |
| AS DRAINING 2010SF ON THE LEVELS ABOVE AND BELOW. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE SHEET NOW SHOWS 2010SF, |
| WHILE THE LEVELS ABOVE AND BELOW INDICATE 1849SF. |
| PLEASE CORRELATE. |
| |
| 50. OK |
| 51. OK |
| |
| 52. SHT P-7 SINKS FOR 3 UNITS ARE NOT SHOWN DRAINING TO |
| ANY RISER DIAGRAMS. PLEASE INDICATE WHERE THESE SINKS |
| ARE DRAINING TO AND SHOW THE CONNECTION ON THE RISER |
| DIAGRAM WHEN INDICATING WHERE THE SINKS ARE DRAINING |
| TO. SECTION 106.1.1. INDICATE TOTAL FIXTURE UNITS FOR |
| STACK WHEN ADDING THE SINK. TABLE710.1(2). ****RESPONSE |
| NOTED, BUT SHT P-7 SHOWS THE SINK IN AREA #3 CONNECTING |
| TO RISER #8 AND THE SINK IN AREA #16 CONNECTING TO |
| RISER #25. PLEASE CORRELATE. |
| |
| 53. OK |
| 54. OK |
| 55. OK |
| 56. OK |
| 57. OK |
| 58. OK |
| 59. OK |
| 60. OK |
| |
| 61. SHT P-12 PH UNIT "C" & PH UNIT "B" SUBMIT WATER |
| RISER DIAGRAMS. SECTION 106.3.5.1.3(3)(10)(13). |
| ****RESPONSE NOTED, BUT NO WATER SUPPLY SHOWN TO MASTER |
| BATH WATER CLOSET ON THE RISER DIAGRAM. |
| |
| 62. OK |
| 63. OK |
| 64. OK |
| 65. OK |
| 66. OK |
| 67. OK |
| 68. OK |
| 69. OK |
| |
| 70. SHT P-13 RISER 11 THE PIPING FOR THE SECOND FLOOR |
| FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, COMMENT ADDRESSED. (NEW) THE WASH |
| MACHINE SHALL CONNECT BELOW THE LAUNDRY SINK. SECTION |
| 901.2. |
| |
| 71. OK |
| 72. OK |
| 73. OK |
| 74. OK |
| 75. OK |
| 76. OK |
| |
| 77. SHT P-15GAS PIPING RISER DIAGRAM. PLEASE SUBMIT |
| THE CALCULATION FOR EQUATION 4-2.--SUBMIT |
| MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BTU LOAD FOR THE BOILER IS NOT |
| INDICATED ON MANUFACTURE SHEETS. I WILL PROVISO THAT |
| THE BTU LOAD WILL BE VERIFIED AT TIME OF GAS FINAL. BTU |
| LOAD SHALL BE SHOWN ON THE BOILER TO BE APPROVED. |
| |
| 78. OK |
| 79. OK |
| 80. OK |
| 81. OK |
| 82. OK |
| 83. OK |
| 84. OK |
| 85. OK |
| 86. OK |
| 87. OK |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND, |
| AS WELL AS THE RETURN OF THE RED LINED SET OF PLANS |
| FROM THE FIRST REVIEW, WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |