Date Text
2008-07-01 08:04:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT 358-9 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, THEY SHALL ALSO INDICATE THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET.FAC
 61G15-23.002(1)(2) & FS 471.025.
 ****RESPONSE NOTED, NOW SHEET 1 OF 1 HAS BEEN DELETED
 BUT THE INDEX ON SHEETS A01.02 & 1 OF 6A STILL SHOWS
 SHEET 358.9. PLEASE CORRELATE.
  
 3. OK
  
 4. SHT A01.3 SECONDARY ROOF DRAINS REQUIRED FOR THE
 AREA NEAR STAIR G1, PUMP ROOM, LAWN EQUIP. ETC.
 SECTIONS 1107.1 & 1107.2.
 ****RESPONSE NOTED, BUT SECONDARY ROOF DRAINS ARE NOT
 LOCATED ON SHT P-1B.
  
 5. SHT A01.3 THERE IS NO PRIMARY OR SECONDARY ROOF
 DRAINS INDICATED IN THE AREA OF STAIR G2, EMERGENCY
 GENERATOR ROOM AND LIFT AS REQUIRED IN SECTIONS 1101.2,
 1107.1 & 1107.2.
 ****RESPONSE NOTED, BUT THERE ARE NO PRIMARY OR
 SECONDARY ROOF DRAINS SHOWN ON SHT P-1B. SHEET A01.3
 SHOWS THE PRIMARY ROOF DRAIN BUT NO SECONDARY ROOF
 DRAIN.
  
 6. OK
  
 7. SHT A01.3ROOF DRAINS ARE SHOWN IN AREAS INDICATED
 AS MULCH AREAS.MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE HOW THE MULCH WILL BE KEPT FROM DRAINING INTO
 THE ROOF DRAINS AND OR CLOGING THE ROOF DRAINS AND
 PREVENTING THEM FROM DRAINING PROPERLY.PLEASE SUBMIT
 A DETAIL FOR THE DRAINS IN THESE AREAS. SECTION 104.6.
 ****RESPONSE NOTED, BUT THE DETAIL D/A01.6 SHOWS ROCK
 AROUND THE DRAIN THEN MULCH, WHERE AS THE ROOF DECK
 PLAN SHOW ONLY GRAVEL. PLEASE CORRELATE. ALSO THE CODE
 REQUIRES THAT THE ROOF DRAIN STRAINERS SHALL HAVE AN
 AVAILABLE INLET AREA, ABOVE THE ROOF, OF NOT LESS THAN
 ONE AND ONE-HALF TIMES THE AREA OF THE CONDUCTOR OR
 LEADER TO WHICH THE DRAIN IS CONNECTED. PLEASE INDICATE
 HOW THE STAINLESS STEEL MESH WILL PROVIDE THE REQUIRED
 AVAILABLE INLET AREA. SECTION 1105.1.
  
 8. SHT A01.3ROOF DRAINAGE INDICATES DETAILS A/A803 &
 D/A803. SECTION 1105.1 STATES ROOF DRAINS SHALL HAVE
 STRAINERS EXTENDING NOT LESS THAN 4 INCHES ABOVE THE
 SURFACE OF THE ROOF IMMEDIATELY ADJACENT TO THE ROOF
 DRAINS. STRAINER SHALL HAVE AN AVAILABLE INLET AREA,
 ABOVE THE ROOF, OF NOT LESS THAN ONE AND ONE-HALF TIMES
 THE AREA OF THE CONDUCTOR OR LEADER TO WHICH THE DRAIN
 IS CONNECTED. PLEASE INDICATE HOW THIS AND THE FACT
 THAT THE ROOF DRAIN WILL BE COVERED WITH ROCKS WILL
 MEET THIS CODE REQUIREMENT. THERE IS A CONCERN THAT THE
 GRASS CLIPPINGS, DIRT, MOSS BUILD UP ETC WILL
 EVENTUALLY KEEP THE DRAIN FROM DRAINING AS INTENDED.
 PLEASE SUBMIT INFORMATION ON HOW THIS WILL BE
 ADDRESSED. SECTION 104.6.
 ****RESPONSE NOTED, BUT THE INTENT OF THE CODE IS NOT
 ADDRESSED. THE REQUIRED STRAINER IS NOT SHOWN AND THE
 AVAILABLE INLET AREA IS IN QUESTION AS THERE IS
 DRAINAGE ROCKS OVER THE ROOF DRAINS. SECTION 1105.1.
 ALSO THE CONCERN THAT THE STAINLESS STEEL MESH WILL
 FURTHER DIMINISH THE INLET AREA HAS TO BE ADDRESSED.
  
 9. SHT A01.3 OVERFLOW DRAINS DETAILS B/A803 & C/A803 DO
 NOT MEET THE INTENT OF THE CODE TO BE USED ONLY IN CASE
 OF BLOCKAGE OF THE PRIMARY ROOF DRAINS. THESE DETAILS
 INDICATE THAT THE DRAINS ARE FLUSH WITH THE ROOF AND
 WILL DRAIN WHEN THE PRIMARY ROOF DRAINS DRAIN AND NOT
 AFTER THE BUILDUP OF A BLOCKED PRIMARY DRAIN. DRAINS
 INDICATED IN DETAIL C/A803 ARE SHOWN TO BE NEXT TO AN
 AREA THAT HAS MULCH IN IT. PLEASE CLARIFY AND INDICATE
 HOW THE MULCH WILL NOT BLOCK THE DRAINS. SECTION
 1107.1.
 ****RESPONSE NOTED, BUTTHE COMMENT WAS FOR THE
 OVERFLOW DRAINS AT THE PUTTING GREEN/CHIPPING GREEN
 AREA. ADDING THE NOTE DOES NOT CHANGE THE FACT THAT THE
 DRAINS ARE STILL SHOWN LEVEL WITH THE GREEN SURFACE.
 ALSO THE PLANTER DRAINS ARE INDICATED AS DRAINING INTO
 THE OVERFLOW DRAINS IN DETAIL "B". THIS WILL ALLOW
 STORM WATER TO DRAIN INTO THE OVERFLOW DRAINS AND WILL
 HAVE STORM WATER DRAINING EVERY TIME IT RAINS AND WILL
 NOT INDICATE THAT THERE IS A BLOCKAGE IN THE PRIMARY
 ROOF DRAIN SYSTEM AS INTENDED. SECTION 1107.
  
 10. OK
  
 11. SHT A01.3 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT
 CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM
 ROOF AREAS ABOVE.
 ****RESPONSE NOTED, BUT NO CALCULATION FOR THE AREAS BY
 THE STAIRS AND WATER FEATURE AND THE STAIRS AND THE
 GENERATOR ROOM WERE SUBMITTED.
  
 12. OK
 13. OK
  
 14. SHT A101 SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES IN ALL TOILET ROOMS. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.17, 11-4.18, 11-4.19 AND 11-4.22 WITH ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT COMMENT DID NOT ADDRESS THE
 COMMON TOILET ROOMS. THE RESPONSE ADDRESSED FHA-98
 REQUIREMENTS FOR THE UNITS.
  
 15. OK
 16. OK
 17. OK
  
 18. SHT A201 UNITS A & A REV. INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--THE WING
 WALL NEXT TO THE W/C IN THE MASTER BATH TO BE A MAXIMUM
 2'0" PER PAGE 7.44.--LAVS SHALL BE CENTERED ON THE
 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH WITH REMOVABLE BASE CABINET SHALL BE
 INDICATED.--SHOW THE CLEAR FLOOR SPACE FOR THE
 W/C'S. PAGE 7.43.--RANGE SHALL BE CENTERED ON THE
 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGES 7.4 &
 7.9. --THE OPENING FOR THE W/C'S IN BATH 2 SHALL BE
 33" AND MUST SHOW 18" OFF THE TUB OR LAV TO THE CENTER
 OF THE FIXTURE AND 15" MIN. OFF THE OTHER FIXTURE.
 PAGES 7.43, 7.44 & 7.45.--MINIMUM CLEARANCES
 BETWEEN ALL COUNTERS, APPLIANCES, BASE CABINETS AND
 WALLS SHALL BE 40". PAGES 7.8, 7.11, 7.22 & 7.23. 36"
 IS SHOWN. PLEASE SHOW COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.
  
 19. SHT A203 UNITS B & B REV. INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE
 CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH PER
 PAGE 7.43.--THE W/C IN THE MASTER BATH SHALL BE 18"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE PER PAGE
 6.5.--LAVS SHALL BE CENTERED ON THE 48" DIMENSION
 OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR FORWARD
 APPROACH WITH REMOVABLE BASE CABINET SHALL BE
 INDICATED.--BATH #2 OPENING FOR THE W/C SHALL BE
 MINIMUM 33". INDICATE MEASURMENT FROM THE CENTERLINE OF
 THE W/C TO THE SIDE OF THE VANITY PER PAGES 7.43, 7.44
 & 7.45.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS AND WALLS SHALL BE 40".
 (SHOWN AS 36"). PAGES 7.8, 7.11, 7.22 & 7.23. 36".
 PLEASE SHOW COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--OPENING FOR W/C NOT SHOWN ON SHT A204 FOR
 SECOND BATHROOM. ALSO SHOW BACKING FOR GRAB BARS IN
 SECOND BATHROOM. REQUIREMENT 6.
  
 20. SHT A205 UNIT C. INDICATE THE BACKING FOR THE TUB
 IN THE MASTER BATH PER PAGE 6.10.-- SHOW THE CLEAR
 FLOOR SPACE FOR THEUSABLE W/C PER PAGE 7.43.-- SHOW
 THE CLEAR FLOOR SPACE FOR THE TUBS OR SHOWERS PER PAGES
 7.53 THRU 7.56.--W/C'S SHALL BE 1'6" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE PER PAGE 6.5.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN M/B &
 BATHROOM 3. REQUIREMENT 6.
  
 21. SHT A207 UNITS D & D REV.INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE
 CLEAR FLOOR SPACE FOR THE USABLE W/C PER PAGE 7.43.--
 SHOW THE OPENING FOR THE W/C IN BATH #2 TO BE A MINIMUM
 OF 33". THE W/C SHALL BE 1'6" OFF ONE FIXTURE TO THE
 CENTERLINE OF THE FIXTURE AND 15" MINIMUM OFF THE OTHER
 FIXTURE OR VANITY CABINET PER PAGES 7.43 THRU 7.45.--
 MINIMUM CLEARANCES BETWEEN ALL COUNTERS, APPLIANCES,
 BASE CABINETS & WALLS SHALL BE 40". PAGES 7.8, 7.11,
 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN
 BATHROOM 2. REQUIREMENT 6.
  
 22. SHT A209 UNITS PHA & PHA REV. INDICATE THE BACKING
 FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW
 THE CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH
 PER PAGE 7.43.--THE WING WALL NEXT TO THE W/C IN
 THE MASTER BATH SHALL BE A MAXIMUM OF 2'0" PER PAGE
 7.44.--THE LAVS SHALL BE CENTERED ON THE 48"
 DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH.--A MINIMUM 33" OPENING IS
 REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE
 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE,
 AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY
 CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES
 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW
 COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN
 BATHROOM 2. REQUIREMENT 6.
  
 23. SHT A212 UNITS PHB & PHB REV. INDICATE THE BACKING
 FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW
 THE CLEAR FLOOR SPACE FOR THE USABLE W/C IN THE MASTER
 BATH PER PAGE 7.43.--THE W/C IN THE MASTER BATH
 SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE PER PAGE 6.5.--THE LAVS SHALL BE CENTERED
 ON THE 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE
 7.48 OR FORWARD APPROACH.--A MINIMUM 33" OPENING IS
 REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE
 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE,
 AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY
 CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES
 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW
 COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN
 BATHROOM 2. REQUIREMENT 6.
  
 24. OK
  
 25. SHT A215 INDICATE THE BACKING FOR THE TUB IN BOTH
 BATHS PER PAGE 6.10.--SHOW THE CLEAR FLOOR SPACE
 FOR THE W/C IN BOTH BATHS PER PAGE 7.43.--THE W/C
 IN BOTH BATHS SHALL BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE PER PAGE 6.5.--THE LAVS
 IN THE MASTER BATH SHALL BE CENTERED ON THE 48"
 DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH. PLEASE SHOW COMPLIANCE. ****RESPONSE
 NOTED, BUT RESPONSE ONLY SHOWS STANDARD TUB BACKING
 REQUIREMENTS. THE BACKING FOR LARGER TUBS WITH DECKS
 HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & 6.11.--
 SHOW THE BACKING FOR THE GRAB BARS IN M/B & BATHROOM 3.
 REQUIREMENT 6.
  
 26. OK
  
 27. SHT A404 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT THE FLUSH CONTROLS SHALL BE
 LOCATED ON THE WIDE SIDE OF THE TANK. THIS IS NOT
 INDICATED.
 B. OK
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ****RESPONSE NOTED, BUT THE KNEE CLEARANCE, (29"), IS
 NOT NOTED ON PLANS.
 B. OK
  
 28. SHT A405 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 W/C'S:
 A. OK
 B. OK
 C. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT THE FLUSH CONTROLS SHALL BE
 LOCATED ON THE WIDE SIDE OF THE TANK. THIS IS NOT
 INDICATED.
 __STALLS:
 A. OK
 __LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ****RESPONSE NOTED, BUT THE KNEE CLEARANCE, (29"), IS
 NOT NOTED ON PLANS.
 B. OK
 C. OK
 __FOR THE SHOWER:
 A. OK
 B. OK
  
 29. OK
 30. OK
 31. OK
 32. OK
  
 33.SHT A805 DETAIL A INDICATES A TRENCH DRAIN. PLEASE
 INDICATE WHERE THIS CAN BE FOUND ON THE FLOOR PLAN.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT TRENCH DRAIN DETAIL STILL
 SHOWN.
  
 34. SHT A806 THE SQUARE FOOTAGE FOR ALL EXTERIOR
 PLANTERS SHALL INDICATE 1/2 THE AREA OF ALL VERTICAL
 WALLS. IN THE CASE OF PLANTERS AGAINST THE BUILDING
 THIS WILL INCLUDE THE 1/2 THE AREA OF THE BUILDING UP
 TO THE PARAPETS OF THE ROOF. PLEASE SUBMIT THE
 CALCULATIONS FOR THESE PLANTER DRAINS PER TABLE
 1106.3.
 ****RESPONSE NOTED, BUT CLARIFICTION REQUIRED AS NO
 PLANTER CALCULATIONS WERE SUBMITTED.
  
 35. OK
 36. OK
 37. OK
 38. OK
 39. OK
  
 40. SHT P-1B PLAN INDICATED ON SHEET INDEX HAS NOT BEEN
 SUBMITTED. SUBMIT A 2ND FLOOR/ROOF PLAN FOR THE GARAGE.
 SHOW ALL ROOF DRAINS, SECONDARY ROOF DRAINS, WATER
 SUPPLY & BACKFLOW FOR THE WATERFALL ETC. SECTION
 106.1.2.
 ****RESPONSE NOTED, BUT NO SECONDARY ROOF DRAINS WERE
 SHOWN FOR AREAS 2, 3, 5, 16, 17 & 19.
  
 41. OK
 42. OK
 43. OK
 44. OK
 45. OK
 46. OK
 47. OK
  
 48. SHT P-3 SHOWS 4 PLANTER DRAINS BUT ONLY SHOWS
 PIPING AND SQUARE FOOTAGE TO 2 PLANTER DRAINS. PLEASE
 SHOW THE PIPING & SF TO ALL PLANTER DRAINS. SECTION
 1101.2.
 ****RESPONSE NOTED, BUT THE INDOOR PLANTER ON THE SOUTH
 SIDE OF THE LOBBY SHALL CONNECT TO THE STORM, NOT THE
 SECONDARY DRAIN.
  
 49. SHT P-3 RWL SHOWS 1730SF, BUT SAME RWL IS INDICATED
 AS DRAINING 2010SF ON THE LEVELS ABOVE AND BELOW.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE SHEET NOW SHOWS 2010SF,
 WHILE THE LEVELS ABOVE AND BELOW INDICATE 1849SF.
 PLEASE CORRELATE.
  
 50. OK
 51. OK
  
 52. SHT P-7 SINKS FOR 3 UNITS ARE NOT SHOWN DRAINING TO
 ANY RISER DIAGRAMS. PLEASE INDICATE WHERE THESE SINKS
 ARE DRAINING TO AND SHOW THE CONNECTION ON THE RISER
 DIAGRAM WHEN INDICATING WHERE THE SINKS ARE DRAINING
 TO. SECTION 106.1.1. INDICATE TOTAL FIXTURE UNITS FOR
 STACK WHEN ADDING THE SINK. TABLE710.1(2). ****RESPONSE
 NOTED, BUT SHT P-7 SHOWS THE SINK IN AREA #3 CONNECTING
 TO RISER #8 AND THE SINK IN AREA #16 CONNECTING TO
 RISER #25. PLEASE CORRELATE.
  
 53. OK
 54. OK
 55. OK
 56. OK
 57. OK
 58. OK
 59. OK
 60. OK
  
 61. SHT P-12 PH UNIT "C" & PH UNIT "B" SUBMIT WATER
 RISER DIAGRAMS. SECTION 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT NO WATER SUPPLY SHOWN TO MASTER
 BATH WATER CLOSET ON THE RISER DIAGRAM.
  
 62. OK
 63. OK
 64. OK
 65. OK
 66. OK
 67. OK
 68. OK
 69. OK
  
 70. SHT P-13 RISER 11 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION
 106.1.1.
 ****RESPONSE NOTED, COMMENT ADDRESSED. (NEW) THE WASH
 MACHINE SHALL CONNECT BELOW THE LAUNDRY SINK. SECTION
 901.2.
  
 71. OK
 72. OK
 73. OK
 74. OK
 75. OK
 76. OK
  
 77. SHT P-15GAS PIPING RISER DIAGRAM. PLEASE SUBMIT
 THE CALCULATION FOR EQUATION 4-2.--SUBMIT
 MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BTU LOAD FOR THE BOILER IS NOT
 INDICATED ON MANUFACTURE SHEETS. I WILL PROVISO THAT
 THE BTU LOAD WILL BE VERIFIED AT TIME OF GAS FINAL. BTU
 LOAD SHALL BE SHOWN ON THE BOILER TO BE APPROVED.
  
 78. OK
 79. OK
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
 85. OK
 86. OK
 87. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND,
 AS WELL AS THE RETURN OF THE RED LINED SET OF PLANS
 FROM THE FIRST REVIEW, WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  