Plan Review Notes
Plan Review Notes For Permit 07030460
Permit Number 07030460
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-07-08 14:52:021. THE FIRE DEPARTMENT CONNECTIONS (FDC'S) ON THE SITE
 SHALL BE EQUIPPED WITH KNOX-BOX LOCKING CAPS.
  
 2. THE USE OF PROPANE AND CHARCOAL GRILLS IN
 MULTI-FAMILY BUILDINGS ARE NOT PERMITTED. ONLY LISTED
 ELECTRIC TYPE EQUIPMENT IS ALLOWED.
  
 3. ON PAGE A601 EXIT DIRECTION MARKINGS LEAD TO
 OPENINGS. THESE LARGE OPENINGS CANNOT CONTAIN GATES OT
 OTHER DEVICES WHICH WILL NOT ALLOW FOR EXITING.
  
 4. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON PAGE
 E-8.
  
 5. THE PROPOSED FIRE STANDPIPE SYSTEM FOR THE DOCKS
 SHALL COMPLY WITH NFPA 303. SEPARATE PLANS AND PERMITS,
 AND FDC ARE REQUIRED.
  
 6. ON PAGE SP-1.1 THE TYPICAL FIRE CABINET SHALL BE
 EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS. ALL STANDPIPE
 CONNECTIONS SHALL ALSO BE EQUIPPED WITH THESE DEVICES.
  
 7. ON PAGE AC-15 SMOKE CONTROL SYSTEM SEQUENCE OF
 OPERATIONS INDICATES THAT SMOKE DETECTORS WILL ACTIVATE
 A SUPERVIOSRY SIGNAL. DUCT SMOKE DETECTORS SHALL
 ACTIVATE A GENERAL ALARM AND NOT A SUPERVISORY SIGNAL.
  
 8. ALL ASSOCIATED DAMPERS SHALL BE DROP TESTED TO
 ENSURE PROPER OPERATION AFTER INSTALLATION.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM EQUIPMENT PLANNED FOR
 BUILDINGS 1 & 2.
  
 10. PLEASE CORRECT BUILDING CODE AND FIRE DEFICIENCIES
 AS IDENTIFIED BY THE CONSTRUCTION SERVICES PLAN
 REVIEWER.
  
 11. ALL CONSTRUCTION METHODS AND INSTALLATION METHODS
 ARE SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX