Plan Review Notes
Plan Review Notes For Permit 07030460
Permit Number 07030460
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-24 16:05:06** DENIED 2ND REVIEW **
  
  
 ** PLEASE SEE THERE ARE STILL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING.
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS TO
 INFORMATION NOW BEING SUBMITTED WHICH WAS ON PREVIOUS
 PLANS OR SUBMITTED WITH PREVIOUS DOCUMENTS.
 ** PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS.
  
 1)NOTE: PLEASE SUBMIT THREE COMPLETE SETS OF PLANS
 AND SUPPORTING DOCUMENTS. IN THE PLANS SUBMITTED, SOME
 ROLLS WERE NOT FASTENED TOGETHER, SOME WERE STAPLED
 BACKWARDS. PLEASE BE SURE ALL SETS ARE IN A NEAT AND
 ORDERLY FASHION WITH ALL SHEETS CONNECTED.
 ** PLEASE BE SURE THE SUBMITTALS ARE PLACED INTO SETS
 IN A NEAT AND ORDERLY FASHION. BINDERS OR FOLDERS OF
 SOME KIND WITH DOCUMENTS IN ORDER LABELED OR TABBED
 WITH INFORMATION WILL EXPEDITE THE REVIEW IN A MORE
 TIMELY FASHION.
 PLEASE SEE FBC ADMIN SECTION 106.1, 106.1.3, 106.5
  
 2) NOTE: PLEASE SEE MANY TITLE BLOCKS ARE MISSING THE
 REQUIRED LICENSE AND PRINTED NAME INFORMATION PER FAC
 61G1-16.004 AND FS 481.219.
 MANY OF THE SHEETS WERE REVISED WITH HAND DRAWN
 INFORMATION HOWEVER MANY WERE NOT.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY THOSE TRADES.
  
 3) NOTE: PLEASE SEE THE SUBMITTED FLORIDA BUILDING CODE
 FOR ENERGY EFFICIENCIES FLA-COM ENERGY CALCULATIONS ARE
 NOT COMPLIANT.
 IN FACT THERE ARE NUMEROUS ITEMS ON PLANS WHICH ARE NOT
 EVEN SHOWN IN THE CALCULATIONS. THERE ARE SEVERAL ITEMS
 FOR BUILDING COMPONENTS WHICH WILL BE NOTED BY THIS
 REVIEWER AND IS REQUIRED WHETHER OR NOT THE COMMENTS
 ARE MADE BY THE OTHER TRADES.
 THE INPUT DATA REPORTWILL BE NOTED BELOW AS THE IDR
 FOR THE REMAINDER OF THIS COMMENT.
 PLEASE SEE 13-101, 13-400.3.A, 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO EXTERIOR DOORS. HOW
 IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW MANY
 EXTERIOR DOORS?
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO FLOORS IN THIS
 BUILDING. HOW IS THIS POSSIBLE WHEN THE BUILDINGS
 CLEARLY CONTAIN FLOORS?
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO SKYLIGHTS, YET THE
 PLANS CLEARLY SHOWS A VERY LARGE SKYLIGHT AT THE FRONT
 OF THE BUILDING!
  
 FOR EXAMPLE:
 PLEASE SEE THE JURISDICTION LISTED IN SHOWN AS PALM
 BEACH COUNTY. THIS SHOULD BE THE CITY OF WEST PALM
 BEACH, PALM BEACH COUNTY.
  
 FOR EXAMPLE;
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR WHICH SHOWS
 ONLY 75W FIXTURES. HOW IS THIS POSSIBLE WHEN THE PLANS
 CLEARLY SHOW DOZENS OF FIXTURES WHICH ARE SIMPLY NOT
 PLACED INTO THE IDR? ALL FIXTURES SHOWN ON THE IDR FOR
 EXTERIOR LIGHTS WHICH ARE SHOWN AS 75WATTS. PLEASE SEE
 SHEET E-2: PLEASE SEE THE PLANS CLEARLY SHOW 455W,
 195W, 55W, 250W ETC. WHERE ARE ALL THESE FIXTURES?
 13-415.2, 13-415.2.ABC.1.3
  
 FOR EXAMPLE:
 PLEASE EXPLAIN HOW MANY OF THE CONTROL METHOD SHOWN IN
 THE IDR ARE SHOWN AS *MANUAL ON/OFF* WHEN T IN FACT THE
 CODE REQUIRES SOME SORT OF AUTOMATED CONTROLS ON MANY
 OF THESE ITEMS?
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE MANY LIGHTING FIXTURES ON THE
 FIXTURE LEGEND AND ON PLANS WHICH DO NOT SHOW UP IN THE
 IDR FOR INTERIOR LIGHTS.
 PLEASE LOOK AT THE WATTAGE/VA RATINGS OF FIXTURES ON
 THE LEGEND. WHERE ARE THE 2-F32T8, 3-F32T8, 4-F32T8??
 ETC. WHERE ARE THE 60W FIXTURES?
 13-415.2.ABC.1.1, .1.2
 THIS IS ONLY A FEW AS NOTED AND IS IN NO WAY ALL.
  
 *** AS NOTED, THESE ARE SOME EXAMPLES ONLY AND ARE IN
 NO WAY AN EXHAUSTED LIST OF ALL ITEMS WHICH DO NOT
 CORRELATE. THESE ARE GIVEN AS A BENEFIT ONLY.
  
 4) NOTE: PLEASE SEE 13-413.1.ABC.2.1, 13-413.1.ABC.2.2
 FOR DRAWING AND REQUIRED NOTES TO BE PLACED ON PLANS.
 PLEASE SEE THE FOLLOWING SECTIONS AND PLACE NOTES ON
 PLANS ACCORDINGLY. NOTES SHOULD REFLECT THE WORDING IN
 THE CODE.
  
 5) NOTE: PLEASE SUBMIT THE COMPLETED VOLTAGE DROP
 CALCULATIONS AS REQUIRED PER FBC 13-413.1.ABC.1.1 AND
 .1.2. THE SUBMITTED CALCULATIONS DO NOT PROVIDE THE
 WORST CASE SCENARIOS AS THESE STOP AS A DISTANCE AND DO
 NOT INCLUDE THE LONGEST RUNS TO THE LAST DEVICE/BRANCH
 CIRCUIT.
 THE CALCULATIONS SHOW LENGTH OF 100FT YET THE BUILDING
 ALONE IS TALLER THAN 100FT.
  
 6) NOTE: PLEASESEE THE PREVIOUS REVIEW REQUESTED THE
 MANUFACTURES SPECS/CUT SHEETS FOR THE FIRE PUMP AND
 FIRE PUMP CONTROLLER AMOUNT OTHERS EQUIPMENT SPECS. THE
 SUBMITTALS FOR THE FIRE PUMP AND CONTROLLER ARE NOW
 SHOWING THE FIRE PUMP AS DIESEL YET THE ELECTRICAL
 PLANS INDICATES THE FIRE PUMP AND FPC AS ELECTRICAL.
 AS THE INFORMATION IS NOT CLEAR ON PLANS WHICH ONE WILL
 BE USED IT IS UNCLEAR WHICH ONE NEEDS TO BE REVIEWED.
 PLEASE SEE FOR EXAMPLE IF A DIESEL PUMP IS USED THERE
 ARE SEVERAL REQUIREMENTS IN NFPA-20 WHICH ARE NOT THE
 SAME AS THE ELECTRICAL REQUIREMENTS SUCH AS VENTILATION
 ETC.
 THE SPRINKLER PLANS DO NOT SHOW ENOUGH INFORMATION FOR
 THE FIRE PUMP OR CONTROLLER.
 PLEASE COORDINATE ALL INFORMATION AND SUPPORTING
 DOCUMENTS.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 7) NOTE: PLEASE SEE THE CORRIDORS DO NOT INDICATE ANY
 OF THE FIXTURES FOR EMERGENCY EGRESS WITH BATTERY BACK
 UP.
 PLEASE SEE PREVIOUS NOTES AS THE BUILDING BEING
 OCCUPIED PER HOUSE BILL 7121 WILL REQUIRE THESE ON THE
 GENERATOR HOWEVERAS THE BUILDING IS NOW BECOMING
 OCCUPIED UNDER NORMAL CONDITIONS UNDER EMERGENCY POWER
 THE EMERGENCY EGRESS LIGHTS SHALL BE BATTERY BACK UP TO
 MEET THE MINIMUM 1FT CANDLE. THE STAIRS WERE REVISED
 HOVER FIXTURES D1 AND D2 WERE NOT REVISED TO INDICATE
 ANY BACK UP.
 PLEASE ALSO SEE THE PHOTO-METRICS SUBMITTED DO NOT MAKE
 SENSE. PLEASE TAKE A LOOK AT THE LIGHTING LEVELS SHOWN
 ONE SHEET E6-A. HOW CAN THE SAME LIGHT FIXTURES WHICH
 ARE SHOWN UNDER NORMAL AND UNDER EMERGENCY HAVE A
 DECREASED LIGHTING LEVEL? THESE ARE 75W MR16 BULBS
 BASED ON FIXTURE LEGEND; THESE WILL OPERATE AND PUT OUT
 THE SAME LUMEN LEVEL UNDER EITHER SOURCE OF POWER.
 THESE ARE NOT SHOWN WITH BACK UP BALLAST WHICH SOME
 TIMES MAY BE USED ON FLUORESCENT FIXTURES WITH A LOWER
 LUMEN OUTPUT.
 PLEASE SEE THE D1 FIXTURES ARE ALSO BEING INCLUDED ON
 THE LEVELS UNDER EMERGENCY. THIS IS NOT POSSIBLE BASED
 ON FIXTURES ETC.
 IF BUILDING IS OCCUPIED UNDER EMERGENCY POWER A SINGLE
 MEANS OF A OVER CURRENT PROTECTION DEVICE WOULD LEAVE
 ALL EGRESS PATHS IN TOTAL DARKNESS.
 PLEASE COMPLETE LEVELS FOR ALL WALKING SURFACES.
 FOR EXAMPLE:
 PLEASE SEE THE FRONT ENTRANCE STAIRS WHICH SHOW
 LIGHTING LEVELS ON ONE PART OF STAIRS ONLY YET THE
 STAIR WIDTH IS QUITE SUBSTANTIAL.
 PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2 ETC.
  
 8) NOTE: PLEASE COORDINATE ALL FIXTURES ON PLANS.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO LIFE SAFETY
 LIGHTING LEVELS AND ENERGY CALCULATIONS AS FIXTURES ON
 PLANS, FIXTURE LEGEND ETC DO NOT CORRELATE.
 ** PLEASE KEEP IN MIND NEW FEDERAL LAW WHICH WAS PASSED
 WHICH WILL MAKE ALL INCANDESCENT LIGHT OBSOLETE.
  
 (9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL
 CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
  
 10) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES WITH
 RESPECT TO HB 7121 AND MINIMUM REQUIRED FUEL BACK UP
 FOR THE GENERATOR. THIS INFORMATION WAS PROVIDED
 HOWEVER THE ITEMS WHICH ARE REQUIRED TO BE ON THE
 GENERATOR WILL BE ALL REQUIRED LIFE SAFETY SYSTEMS IF
 BUILDING IS GOING TO BE OCCUPIED. THE NORMAL OCCUPANCY
 UNDER EMERGENCY POWER WILL REQUIRE THE LIFE SAFETY
 SYSTEMS SUCH AS VENTILATION, CO SENSORS, ETC.
 ** EVEN AS SHOWN IF THE EMERGENCY GENERATOR IS RUNNING
 AND EMERGENCY PANELS ARE BEING FED FROM THE BACK UP
 SOURCE, ALL LOADS ON PANELS WOULD BE *ON*.HOW IS IT
 THAT ALL THESE OTHER LIFE SAFETY REQUIRED LOADS WOULD
 BE TURNED OFF? LOAD SHEDDING?
 HOW CAN REQUIRED LIFE SAFETY SYSTEMS BE ON ANY LOAD
 SHEDDING?
 THESE SCENARIOS ARE NOT POSSIBLE. ALL SYSTEMS ON THE
 LIFE SAFETY OR LEGALLY REQUIRED SYSTEMS SHALL BE ALL BE
 ON THE BACK UP SOURCE DURING BUILDING OCCUPANCY.
  
 11) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES WITH
 RESPECT TO THE MINIMUM LEVELS REQUIRED FOR HORNS AND
 STROBES. THE RESPONSE WAS TO SEE REVISED NOTES ON PLANS
 HOWEVER THE REVISE NOTES ONLY QUOTED THE CODE SECTIONS.
 IN FACT THE WORDING ONLY STATED THE CANDELA LEVELS. IN
 EITHER CASE THE CODES OR IN THIS CASE CODES ARE NOT
 PERMITTED TO BE QUOTED IN LIEU OF ACTUALLY MINIMUM
 LEVELS REQUIRED.
 PLEASE BE SURE TO SEE THE LEVELS IN THE FBC AS NOTED
 AND PLEASE BE SURE TO GO OVER DESIGN FOR LEVELS NEEDED
 IN LOCATIONS AS WELL AS THE LOCATIONS REQUIRED FOR
 ADA.
 FBC 11-4.28.1,.2 AND .3.CANDELAS ARE .3(4).
  
 12) NOTE: PLEASE KNOW AS THE FIRE PUMP HAS NOT YET BEEN
 CLEARED UP TOP WHETHER OR NOT THE FIRE PUMP IS
 ELECTRICAL OR DIESEL THE FUEL REQUIRED ON THE GENERATOR
 CAN NOT BE CONFIRMED TO MEET NFPA-20 9.6.2.2
  
 13) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE
 POOL REQUIRED EQUAL-POTENTIAL BONDING GRID. THE PLANS
 DO CONTAIN A DETAIL AND SHOW ALMOST ALL REQUIRED ITEMS
 HOWEVER THEY DO NOT SHOW THE DETAIL FOR ONE OF THE
 REQUIRED METHODS UNDER THE NEW CODE.
 NO GRID, NO GROUND RING WITH FOUR BONDING LOCATIONS
 ETC.
 PLEASE SEE 680.26 OF THE 2005 NEC WITH THE FLORIDA
 BUILDING COMMISSION UPDATE FOR THE EXECUTIVE ORDER
 SENATE BILL 2836 RELEASED DATED JUNE 19, 2007.
 SEPARATELY).
  
 14) NOTE: PLEASE VERIFY WHERE THE INFORMATION IS FOR
 SITE LIGHTING POLES. PREVIOUS NOTE:
 PLEASE PROVIDE WIND LOADS AND INFORMATION FOR SITE/ROOF
 TOP POLES WHICH ARE REQUIRED TO MEET FBC 140MPH.
 THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE FBC 3006.2 AS EACH ELEVATOR
 EQUIPMENT ROOM SHALL CONTAIN A DEDICATE AIR
 CONDITIONING SYSTEM. THIS IS A NEW NOTE HOWEVER
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 16) NOTE: PLEASE SEE LIGHTING CONTROLS IN SOME AREAS DO
 NOT MEET FBC 13-415.1.ABC.1.1, .1.2. NOT ALL AREAS IN
 THIS BUILDING ARE 24HRS OR REQUIRED FOR SECURITY.
 PLEASE SEE LOCATIONS SUCH AS COMMON ARE BATHROOMS,
 STORAGE ROOMS ETC.
 PLEASE BE SURE TO SEE FBC 1016.1 AND LS 101 7.8.1.2.2
 WHEN OCCUPANCY DEVICES ARE USED IN AREAS OF EGRESS THE
 DEVICES ARE REQUIRED TO BE FAIL SAFE ON.
  
 17) NOTE: PLEASE VERIFY HOW ALL EXTERIOR LIGHTS MEET
 FBC 13-415.1.ABC.1.4. IF ANY ON TIME CLOCK, PLEASE BE
 SURE TO SPECIFY THE REQUIRED ASTRONOMICAL TIME CLOCK
 WITH THE MINIMUM 10HR BATTERY BACK UP.
  
 18) NOTE: PLEASE SEE NFPA-110, NFPA-101 AS ANY
 COMMUNICATION SYSTEMS SUCH AS THE PHONE EQUIPMENT WHICH
 REQUIRE LINE VOLTAGE TO POWER SYSTEMS SHALL BE ON
 BATTERY BACK UP AND/OR ON GENERATOR CIRCUITS. ANY
 COMMUNICATION SYSTEMS USED FOR FIRE LIFE SAFETY ARE
 ALSO REQUIRED TO CONTAIN BACK UP POWER.
 SOME PHONE BOARD RECEPTACLES ARE SHOWN ON NORMAL POWER
 PANELS AT THIS TIME.
 THIS IS A NEW COMMENT.
 4.4.1 TYPICALLY, LEVEL 1 SYSTEMS ARE INTENDED TO
 AUTOMATICALLY SUPPLY ILLUMINATION OR POWER, OR BOTH, TO
 CRITICAL AREAS AND EQUIPMENT IN THE EVENT OF FAILURE OF
 THE PRIMARY SUPPLY OR IN THE EVENT OF DANGER TO
 ELEMENTS OF A SYSTEM INTENDED TO SUPPLY, DISTRIBUTE,
 AND CONTROL POWER AND ILLUMINATION ESSENTIAL FOR SAFETY
 TO HUMAN LIFE.
 LEVEL 1 SYSTEMS GENERALLY ARE INSTALLED IN PLACES OF
 ASSEMBLY WHERE ARTIFICIAL ILLUMINATION IS REQUIRED BY
 OTHER STANDARDS FOR SAFE EXITING AND FOR PANIC CONTROL
 IN BUILDINGS SUBJECT TO OCCUPANCY BY LARGE NUMBERS OF
 PEOPLE.
 EMERGENCY SYSTEMS CAN ALSO PROVIDE POWER FOR SUCH
 FUNCTIONS AS VENTILATION WHEN ESSENTIAL TO MAINTAIN THE
 FOLLOWING, AS WELL AS OTHER SIMILAR FUNCTIONS:
 (1)LIFE
 (2)FIRE DETECTION AND ALARM SYSTEMS
 (3)ELEVATORS
 (4)FIRE PUMPS
 (5)PUBLIC SAFETY COMMUNICATIONS SYSTEMS
 (6)INDUSTRIAL PROCESSES WHERE CURRENT
 INTERRUPTION WOULD PRODUCE SERIOUS LIFE SAFETY OR
 HEALTH HAZARDS
  
 19) NOTE: PLEASE SEE SOME AREAS WHICH ARE MISSING SOME
 RECEPTACLES PER 210.52. SOME ARE REDLINED ON PLANS.
 THESE COULD BE REDLINED ON PROJECT AS THEY ARE MINOR IN
 NATURE AND ONLY ONE OR SO IN UNITS D, A, PHA ARE
 MISSING ON 2FT OR MORE OF WALL IN BETWEEN KITCHEN AND
 DINING ROOM.
  
 20)NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT THE
 LIGHTING CONTROLS FOR UNITS WHICH CONTAIN UPPER
 ROOF/LEVEL SPIRAL STAIRS. PLEASE SEE SEVERAL OF THESE
 SHOWS A STANDARD SINGLE POLE SWITCH AT THE LOWER LEVEL.
 THESE APPEAR TO BE A MISPRINT AS THE SINGLE POLE SWITCH
 IN SOME AREAS WHICH CONTROL THE HALF SWITCHED
 RECEPTACLE ACTUALLY SHOWS A THREE WAY SWITCH. THE
 DESIGNATIONS SEEM TO BE REVERSED.
 PLEASE ADJUST.
 210.70, LS 101 7.8
  
 21) NOTE: PLEASE SEE THE LOADS FOR STORAGE TYPE WATER
 HEATERS ARE REQUIRED TO BE SHOWN AND FIGURED INTO
 CALCULATIONS AT 125%.
 PLEASE SEE THE PREVIOUS REVIEW COMMENTS WHICH INCLUDED
 THE TEXT WHICH WAS EXTRACTED DIRECTLY FROM THE 2005
 NEC. PLEASE READ THE LAST SENTENCE IN THE CODE
 COMMENTARY AS THIS STATES THE LOADS WILL HAVE AN AFFECT
 ON THE FEEDERS AND THE SERVICES. THUS THE CONTINUOUS
 LOADS OF 125%.
 PLEASE SEE THE FOLLOWING WHICH IS SHOWN DIRECTLY FROM
 THE NEC.
  
 *THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.*
  
 THE LAST SENTENCE STATES IMPACT ON FEEDERS, SERVICES.
 PLEASE SEE DEFINITIONS IN NEC 100 OF CONTINUOUS LOADS
 AND 215.3, 230.42 FOR FIGURING ADDITIONAL LOADS.
  
 22) NOTE: PLEASE CLARIFY WATER HEATERS SHOWN ON THE
 INPUT DATA REPORT OF THE ENERGY CALCULATIONS AND THOSE
 WHICH ARE SHOWN ON PLANS FOR HOUSE LOADS.
 PLEASE SEE A WH-3 IS SHOWN, WHERE ARE THE OTHERS?
 13-400.3.A, 13-412.1.ABC
  
 23) NOTE: PLEASE TALE A LOOK AT THE UNIT METER CENTER
 CALCULATIONS WHICH DO NOT LIST ANY WATER HEATERS AT
 ALL.
 NEC 220
  
 24) NOTE: PLEASE SEE NEC 700.9 AS WIRING AND POWER
 DISTRIBUTION TO EMERGENCY LOADS SHALL BE SEPARATED FROM
 OTHER LOADS FOR LEGALLY REQUIRED AND ANY OPTIONAL
 STAND-BY SYSTEMS.
 PLEASE SEE EXPLANATORY SECTION OF NEC AND NFPA-110
 THERE IS AN EXCEPTION TO EMERGENCY AND LEGALLY
 REQUIRED LOADS IN SAME PANEL HOWEVER THE PANEL AS SHOWN
 AND SUBMITTED DOES NOT INCLUDE THIS.
  
 24) NOTE: PLEASE SEE THE GENERATOR IS NOW SHOWN AT A
 SEPARATELY DERIVED SYSTEM TO ADDRESS PREVIOUS NOTE AS
 ATS WAS SHOWN AS 4-POLE, YET THE ATS IS NOW SHOWN AS
 3-POLE. HOW CAN THE GENERATOR BE SEPARATELY DERIVED
 WHEN THE ATS IS 3-POLE AND THERE IS NOT GROUNDING
 ELECTRODE SYSTEM FOR THE GENERATOR?
 PLEASE SEE 250.50, 250.20 ETC
 THE RESPONSE COMMENT REALLY DOES NOT APPLY TO THE
 PREVIOUS NOTE.
  
 25) NOTE: PLEASE SHOW THE OVER CURRENT PROTECTION ON
 THE GENERATOR FOR EACH OF THE BREAKERS AS SHOWN ON
 RISER. THE RISER NOTES DO NOT SEEM TO SHOW ANY
 INFORMATION AND UNABLE TO REVIEW SEVERAL CODE SECTIONS
 FROM CONDUCTOR SIZES, CONDUIT SIZES TO ANY MAGNETIC
 TYPE BREAKER FOR ANY ELECTRICAL FIRE PUMP.
 AS NOTED ABOVE IN NOTE #24, PLEASE PAY CLOSE ATTENTION
 TO WHETHER OR NOT THE GENERATOR WILL BE SEPARATELY
 DERIVED AS THESE BREAKERS AT THE GENERATOR MAY JUST
 BECOME THE FIRST MEANS OF DISCONNECT.
 240.4,310.16,445.13,250.24,250.6,250.24 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 26) NOTE: PLEASE KNOW AFTER THE LAST MEETING WITH
 ARCHITECT AND OWNER OF PROJECT IT WAS SAID A SEPARATE
 MEETING FOR MEP ENGINEERS AND PLANS REVIEW STAFF WAS
 GOING TO TAKE PLACE. TO DATE, AFTER THE LAST MEETING NO
 MEETING WAS EVER SCHEDULED WITH THIS REVIEWER AND NO
 PHONE CALLS WERE MADE TO GO OVER COMMENTS.
 IT IS SUGGESTED AT A MINIMUM IF THERE ARE ANY QUESTIONS
 TO AT LEAST CALL BY PHONE TO GO OVER COMMENTS. SOME
 CODE SECTIONS WERE REPEATED, SOME ARE NEW AND SOME HAVE
 YET TO BE ANSWERED.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]