2008-06-20 14:04:35 | |
| FLAGLER BEACH CLUB BUILDING# 3TOWER (15 STORY)& |
| PARKING STRUCTURES |
| |
| BUILDING PLAN REVIEW |
| |
| PERMIT: 07030460 |
| ADD: 5818 N FLAGLER DR(HIGH RISE BUILDING# 3) CONT: |
| SCOTT GROUP |
| TEL: (561)346-9888 |
| CONTACT NAT HEALY635-6935 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| ARCHITECT: DAVID LAWRENCE |
| T: (561)805-5793 |
| F: (561)805-5795 |
| |
| 2NDREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2-4) COMPLIED. |
| |
| 5) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF |
| WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS |
| LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION |
| CERTIFICATE WILL BE REQUIRED. MINIMUM BASE FLOOD |
| ELEVATION IS 7'-6". |
| |
| 6) COMPLIED. |
| |
| 7) 2ND REQUEST, .FL S S 713.13NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT.NOTE: |
| 713.24(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 8) 2ND REQUEST,THRESHOLD INSPECTOR:WPB AMENDMENT |
| 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN |
| CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| (561)805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT |
| MAY BE ISSUED. |
| |
| 9-15A) COMPLIED. |
| |
| 15B) INFORMATIONALONLY, NO COMMENT REQUIRED. 15B) |
| PLANS INDICATE POOL, DECKS, FENCES, GATES AND OTHER |
| SITE AMENITIES THAT WOULD BE COVERED UNDER SEPARATE |
| PERMITS ALTHOUGH THERE ARE FEATURES IN THESE PLANS, |
| OTHER TRADES MAY NOT COMMENT ON THESE ISSUES SINCE |
| THERE ARE NO PERMITS APPLIED FOR AT THIS TIME FOR THESE |
| ITEMS. |
| |
| 16-17) COMPLIED. |
| |
| 18A) SHEET A101A, THE SKYLIGHT DRIVE THROUGH PROVIDE |
| PRODUCT APPROVAL FOR WIND AND PROVIDE WHAT TYPE SAFETY |
| GLAZING WILL BE USED. 2405.2 ALLOWABLE GLAZING |
| MATERIALS AND LIMITATIONS. THE RESPONCE INDICATED THIS |
| WAS DELETED BUT ON SHEET A101 IS STILL INDICATED ON |
| PLANS, PLEASE ADVISE, 106.1.2 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 18B-D) COMPLIED. |
| |
| 18E) SEMI-COMPLIED, RESPONCE INDICATED THAT IN THE DOOR |
| SCHEDULE FOUND ON A400 DOOR NUMBERS 9, 13,16,17,18 & 19 |
| WERE 90 MINUTE DOORS AND FRAMES, THE DOOR SCHEDULE ALSO |
| INDICATES THESE DOOR FRAMES ARE TO BE ALUMINUM, PLEASE |
| PROVIDE UL OR OTHER RECONIZED AGENCY REPORT. 715.3.1 |
| NFPA 252 OR UL 10C. |
| |
| 19) SHEET A102 |
| |
| 19A)(1) 2ND REQUEST, SEE DETAIL B-3 SHEET A-402, THE |
| SLIDING GLASS DOOR TRACK ASSEMBLY AS SHOWN DOES NOT |
| MEET FAIR HOUSING GUIDELINES,FOR SECONDARY DOORS |
| (SLIDING GLASS DOORS) THE GUIDELINE SPECIFY THAT THE |
| THRESHOLDS AT THESE DOORS SHALL BE NO HIGHER THAN ? ?. |
| THE GUIDELINES FURTHER STATE THAT CHANGES IN LEVEL AT |
| THESE LOCATIONS MUST BE BEVELED WITH A SLOPE NO GREATER |
| THAN 1:2. |
| 19A)(2) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE |
| MAXIMUM ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING |
| GLASS DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO |
| WILL BE 4 INCHES TO THE FINISH DECK. |
| NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK |
| INTO THE DESIGN CRITERIA. |
| 19A)(3) THE STRUCTURAL PLANS WILL ALSO NEED TO |
| CORRELATE THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS |
| STATED ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS |
| DOORS. |
| 19A)(4) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK |
| IS TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS |
| WILL REQUIRE MECHANICAL FASTENING OF TRACK. |
| THE RESPONCE INDICATED HOW THEY WOULD MEET THE |
| ALTERNATIVE METHODS UNDER THE FAIR HOUSING GUIDELINES, |
| WHICH WILL NEED TO BE FILED WITH THE CLERK OF THE COURT |
| BEFORE ISSUANCE OF THIS PERMIT. |
| |
| 19B-19C) COMPLIED. |
| |
| 19D) 2ND REQUEST, PLANS FAIL TO IDENTIFY THE WALL TYPES |
| THAT SURROUND THE REFUSE SHOOT.707.13.3 REFUSE AND |
| LAUNDRY CHUTE ACCESS ROOMS. ACCESS OPENINGS FOR REFUSE |
| AND LAUNDRY CHUTES SHALL BE LOCATED IN ROOMS OR |
| COMPARTMENTS COMPLETELY ENCLOSED BY CONSTRUCTION THAT |
| HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR |
| AND OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED |
| BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING |
| OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR |
| AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE. |
| |
| A506.2 THE GROUND FLOOR DETAIL (A) WALL TYPE 9/ 800 |
| PLEASE REVISE TYPO TO 9/801. |
| |
| 19E-19G) COMPLIED. |
| |
| |
| 19H) 2ND REQUEST, PLANS INDICATE BETWEEN UNITS 2 |
| SEPARATE WALLS ONE WITH SOUND PROOFING THE OTHER IS A |
| TWO HR RATED WALL. PLEASE PROVIDE AN ASSEMBLY HOW THE |
| TWO WALLS WILL BE BUILT? |
| A203 & A206 BOTH INDICATE A WALL TYPE 8 BUT THERE IS NO |
| WALL DISIGNATION FOR THE SECOND WALL INDICATED ON THE |
| PLAN. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| |
| 19I) PROVIDE COMPLIANCE WITH:1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 19J) NO, 2ND REQUEST, PROVIDE COMPLIANCE WITH: 1207.3 |
| STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. NO STC RATING PROVIDED FOR DETAIL 9/A.801. |
| THE COMMON AREAS WILL NEED TO SHOW COMPLIANCE, THE |
| INDIVIDUAL UNITS WILL BE REVIEWED UNDER THE TENANT |
| BUILDOUT, PERMITS WILL BE REQUIRED FOR FLOOR FINISHES |
| OF UNITS. |
| |
| 20-24A) COMPLIED. |
| |
| 24B) SEMI-COMPLIED, PLANS STILL INDICATE GRILLS TO BE |
| INSTALLED SEE A108, PROVIDE MANUFACTURERS SPEC. 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 24C) PROVISO; SHOP DRAWINGS FOR CATWALKS TO BE REVIEWED |
| BY DESIGN PROFESSIONAL BEFORE SUBMITION TO THE BUILDING |
| DEPARTMENT. |
| |
| 24D-24F) COMPLIED. |
| |
| 24G) A107 THE PENTHOUSE UNITS DO HAVE THEIR OWN MEANS |
| OF EGRESS USING THE SPIRAL STAIRS (1009.9.3) THEY ARE |
| NOT ALLOWED TO USE THE DOORS BETWEEN UNITS FOR MEANS OF |
| EGRESS, 1013.2 EGRESS THROUGH INTERVENING ROOMS. |
| |
| 24H-26B)COMPLIED. |
| |
| 26C) SEMI-COMPLIED) SHEET A201 EGRESS WINDOWS THE |
| MINIMUM HEIGHT IS 24 INCHES, THE WORDING IS STILL |
| TWENTY-TWO INCHES PLEASE MAKE CORRECTION, 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 26D) COMPLIED. |
| |
| 27) SHEET A201; |
| |
| 27A) 2ND REQUEST , PLANS INDICATE A 3'-4" MINIMUM ENTRY |
| BETWWEN THE CABINETRY INTO THE KITCHEN, BUT THE FAIR |
| HOUSING NOTES ON SHEET A700 NOTE 5 USABLE KITCHENS |
| INDICATES THE MEASUREMENT IS TAKEN FROM THE EDGE OF |
| COUNTER TOPSTO THE HANDLES OF APPLIANCES, |
| REFRIGARATORS DEPHT MINIMUM IS 30 1/2 INCHES, RANGES 27 |
| INCHES. PLEASE ADJUST THE PLANS TO HAVE A CLEAR NET |
| OPENING OF |
| 3'-4". |
| 27B) COMPLIED. |
| |
| 27C) SEMI-COMPLIED, SEE 19A. |
| |
| 28-32A) COMPLIED. |
| |
| 32B) 2ND REQUEST, THE KITCHEN INDICATES A MINIMUM OF |
| 40" CLEAR BUT THE MEASUREMENT IS TO BE TAKEN FROM THE |
| EDGE OF THE COUNTER TOP TO THE HANDLE OF THE 27" DEEP |
| RANGE, SEE FAAIR HOUSING NOTE 5 LOCATED ON SHEET A700. |
| |
| 33-41A) COMPLIED. |
| |
| 41B) SEMI-COMPLIED, ATACHMENT DETAIL OF CURBING AS |
| SHOWN ON S7.2 INDICATES THE USE OF RFB, PLANS DO NOT |
| INDICATE WHO MAKES THIS ITEM? 106.1.2 ADDITIONAL |
| INFORMATION. |
| |
| 41C) 2ND REQUESTSHEET A804 PLANS MAKE REFERENCE TO |
| THE SFBC, PLEASE MAKE CORRECTION. |
| |
| 41-42) COMPLIED. |
| |
| 43A) SEMI-COMPLIED. PILING, SHEET S-3.02 NOTE 4 |
| REFERENCES THE 2001 FBC |
| 43B) S-3.02 NOTE# 10 INDICATES THE USE OF 16 INCH PILE |
| WHEREAS S-3.01 & S-3.02 BOTH INDICATE THE USE OF 18 |
| INCH PILE PLEASE CORRELATE PLANS, 106.1.2 ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 44) COMPLIED. |
| |
| 45) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF |
| PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| FOLLOWS: |
| ROOFING REPORT SUBMITTED IS FOR A WOOD DECK SEE A-306 |
| |
| 46) COMPLIED. |
| |
| 47) COMPLIED. |
| |
| 8) PLANS ARE TO SHOWCOMPLIANCE WITH: |
| 403.8 FIRE COMMAND . |
| A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL |
| BE PROVIDED IN A LOCATION APPROVED BY THE FIRE |
| DEPARTMENT. |
| |
| |
| |
| 403.10 STANDBY POWER. |
| A STANDBY POWER SYSTEM COMPLYING WITH SECTION 2702 |
| SHALL BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN |
| SECTION 403.10.2 . |
| |
| 403.10.1 SPECIAL REQUIREMENTS FOR STANDBY POWER |
| SYSTEMS. |
| IF THE STANDBY SYSTEM IS A GENERATOR SET INSIDE A |
| BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE |
| ROOM ENCLOSED WITH 2-HOUR FIRE-RESISTANCE-RATED FIRE |
| BARRIER ASSEMBLIES. SYSTEM SUPERVISION WITH MANUAL |
| START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE |
| FIRE COMMAND CENTER. |
| |
| 403.10.2 STANDBY POWER LOADS. |
| THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 1. |
| POWER AND LIGHTING FOR THE FIRE COMMAND CENTER REQUIRED |
| BY SECTION 403.8 ; |
| 2.ELECTRICALLY POWERED FIRE PUMPS; |
| 3.VENTILATION AND AUTOMATIC FIRE DETECTION |
| EQUIPMENT FOR SMOKEPROOF ENCLOSURES. |
| STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN |
| ACCORDANCE WITH SECTION 3003 . |
| |
| 403.11 EMERGENCY POWER SYSTEMS. |
| AN EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702 |
| SHALL BE PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED |
| IN SECTION 403.11.1 . |
| |
| 403.11.1 EMERGENCY POWER LOADS. |
| THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS: |
| |
| 1.EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION |
| REQUIRED BY CHAPTER 10 ; |
| 2.ELEVATOR CAR LIGHTING; |
| 3.EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; 4. |
| AUTOMATIC FIRE DETECTION SYSTEMS; AND |
| 5.FIRE ALARM SYSTEMS. |
| |
| 403.12 STAIRWAY DOOR OPERATION. |
| STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS |
| SHALL BE PERMITTED TO BE LOCKED FROM |
| STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED FROM THE |
| STAIRWAY SIDE SHALL BE CAPABLE OF BEING UNLOCKED |
| SIMULTANEOUSLY WITHOUT UNLATCHING UPON A SIGNAL FROM |
| THE FIRE COMMAND CENTER. |
| |
| 403.12.1 STAIRWAY COMMUNICATIONS SYSTEM. |
| A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM |
| CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION |
| SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN |
| EACH REQUIRED STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| ARE LOCKED. |
| |
| 403.13 SMOKEPROOF EXIT ENCLOSURES. |
| EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75 |
| FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE |
| DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS |
| 909.20 AND 1019.1.8 . |
| |
| 403.14 RESERVED. |
| |
| **403.15 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE |
| WITH SECTION 909.** |
| 909.16 FIRE-FIGHTER?S SMOKE CONTROL PANEL. |
| A FIRE-FIGHTER?S SMOKE CONTROL PANEL FOR FIRE |
| DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE |
| PROVIDED AND SHALL INCLUDE MANUAL CONTROL OR OVERRIDE |
| OF AUTOMATIC CONTROL FOR MECHANICAL SMOKE CONTROL |
| SYSTEMS. THE PANEL SHALL BE LOCATED IN A FIRE COMMAND |
| CENTER COMPLYING WITH SECTION 911 IN HIGH-RISE |
| BUILDINGS OR BUILDINGS WITH SMOKE PROTECTED ASSEMBLY |
| SEATING. IN OTHER BUILDINGS, THE FIRE-FIGHTER?S SMOKE |
| CONTROL PANEL SHALL BE INSTALLED IN AN APPROVED |
| LOCATION ADJACENT TO THE FIRE ALARM CONTROL PANEL. THE |
| FIRE-FIGHTER?S SMOKE CONTROL PANEL SHALL COMPLY WITH |
| SECTIONS 909.16.1 THROUGH 909.16.3 . |
| |
| 909.16.1 SMOKE CONTROL SYSTEMS. |
| FANS WITHIN THE BUILDING SHALL BE SHOWN ON THE |
| FIRE-FIGHTER?S CONTROL PANEL. A CLEAR INDICATION OF THE |
| DIRECTION OF AIRFLOW AND THE RELATIONSHIP OF COMPONENTS |
| SHALL BE DISPLAYED. STATUS INDICATORS SHALL BE PROVIDED |
| FOR ALL SMOKE CONTROL EQUIPMENT, ANNUNCIATED BY FAN AND |
| ZONE, AND BY PILOT-LAMP-TYPE INDICATORS AS FOLLOWS: |
| 1.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN |
| THEIR NORMAL STATUS?WHITE. |
| 2.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN |
| THEIR OFF OR CLOSED STATUS?RED. |
| 3.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN |
| THEIR ON OR OPEN STATUS?GREEN. |
| 4.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN A |
| FAULT STATUS?YELLOW/AMBER. |
| |
| 909.16.2 SMOKE CONTROL PANEL. |
| THE FIRE-FIGHTER?S CONTROL PANEL SHALL PROVIDE CONTROL |
| CAPABILITY OVER THE COMPLETE SMOKE-CONTROL SYSTEM |
| EQUIPMENT WITHIN THE BUILDING AS FOLLOWS: |
| 1.ON-AUTO-OFF CONTROL OVER EACH INDIVIDUAL PIECE |
| OF OPERATING SMOKE CONTROL EQUIPMENT THAT CAN ALSO BE |
| CONTROLLED FROM OTHER SOURCES WITHIN THE BUILDING. THIS |
| INCLUDES STAIRWAY PRESSURIZATION FANS; SMOKE EXHAUST |
| FANS; SUPPLY, RETURN AND EXHAUST FANS; ELEVATOR SHAFT |
| FANS AND OTHER OPERATING EQUIPMENT USED OR INTENDED FOR |
| SMOKE CONTROL PURPOSES. |
| 2.OPEN-AUTO-CLOSE CONTROL OVER INDIVIDUAL DAMPERS |
| RELATING TO SMOKE CONTROL AND THAT ARE ALSO CONTROLLED |
| FROM OTHER SOURCES WITHIN THE BUILDING. |
| 3.ON-OFF OR OPEN-CLOSE CONTROL OVER SMOKE CONTROL |
| AND OTHER CRITICAL EQUIPMENT ASSOCIATED WITH A FIRE OR |
| SMOKE EMERGENCY AND THAT CAN ONLY BE CONTROLLED FROM |
| THE FIRE-FIGHTER?S CONTROL PANEL. |
| |
| |
| 49)COMPLIED. |
| |
| 50) NEW,PROVIDE INFORMATION ON THE VENTILATION OF THE |
| ENCLOSED PARKING GARAGE. 406.4.2 VENTILATION. A |
| MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL . |
| NOTEFLORIDA ADMINISTRATIVE CODE RULE 9B-3.0472 EVERY |
| BUILDING WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED |
| ON OR AFTER 7-1-08 AND HAVING A FOSSIL -FUEL- BURNING |
| HEATER OR APPLIANCE OR AN ATTACHED GARAGE SHALL HAVE AN |
| OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 |
| FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. IN |
| CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER |
| FROM |
| THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FROM THE |
| LOCAL POWER UTUILIY SUCH ALARMS SHALL HAVE BATTERY BACK |
| UP. BOMBINATION SMOKE/ CARBON MONOXIDE ALARMS SHALL BE |
| LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| LABORATORY. |
| |
| 51)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST |
| BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| THIS REVIEW IS MAY HAVE ADDITIONAL COMMENTS AS A RESULT |
| OF THE DESIGNERS ANSWERS TO THE PLAN REVIEW OR NEW |
| INFORMATION BEING ADDED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| FLAGLER BEACH CLUB TOWER 1ST REVIEW.DOC |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |