Plan Review Notes
Plan Review Notes For Permit 07030460
Permit Number 07030460
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-20 14:04:35 
 FLAGLER BEACH CLUB BUILDING# 3TOWER (15 STORY)&
 PARKING STRUCTURES
  
 BUILDING PLAN REVIEW
  
 PERMIT: 07030460
 ADD: 5818 N FLAGLER DR(HIGH RISE BUILDING# 3) CONT:
 SCOTT GROUP
 TEL: (561)346-9888
 CONTACT NAT HEALY635-6935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: DAVID LAWRENCE
 T: (561)805-5793
 F: (561)805-5795
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2-4) COMPLIED.
  
 5) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED. MINIMUM BASE FLOOD
 ELEVATION IS 7'-6".
  
 6) COMPLIED.
  
 7) 2ND REQUEST, .FL S S 713.13NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT.NOTE:
 713.24(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 8) 2ND REQUEST,THRESHOLD INSPECTOR:WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT
 MAY BE ISSUED.
  
 9-15A) COMPLIED.
  
 15B) INFORMATIONALONLY, NO COMMENT REQUIRED. 15B)
 PLANS INDICATE POOL, DECKS, FENCES, GATES AND OTHER
 SITE AMENITIES THAT WOULD BE COVERED UNDER SEPARATE
 PERMITS ALTHOUGH THERE ARE FEATURES IN THESE PLANS,
 OTHER TRADES MAY NOT COMMENT ON THESE ISSUES SINCE
 THERE ARE NO PERMITS APPLIED FOR AT THIS TIME FOR THESE
 ITEMS.
  
 16-17) COMPLIED.
  
 18A) SHEET A101A, THE SKYLIGHT DRIVE THROUGH PROVIDE
 PRODUCT APPROVAL FOR WIND AND PROVIDE WHAT TYPE SAFETY
 GLAZING WILL BE USED. 2405.2 ALLOWABLE GLAZING
 MATERIALS AND LIMITATIONS. THE RESPONCE INDICATED THIS
 WAS DELETED BUT ON SHEET A101 IS STILL INDICATED ON
 PLANS, PLEASE ADVISE, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 18B-D) COMPLIED.
  
 18E) SEMI-COMPLIED, RESPONCE INDICATED THAT IN THE DOOR
 SCHEDULE FOUND ON A400 DOOR NUMBERS 9, 13,16,17,18 & 19
 WERE 90 MINUTE DOORS AND FRAMES, THE DOOR SCHEDULE ALSO
 INDICATES THESE DOOR FRAMES ARE TO BE ALUMINUM, PLEASE
 PROVIDE UL OR OTHER RECONIZED AGENCY REPORT. 715.3.1
 NFPA 252 OR UL 10C.
  
 19) SHEET A102
  
 19A)(1) 2ND REQUEST, SEE DETAIL B-3 SHEET A-402, THE
 SLIDING GLASS DOOR TRACK ASSEMBLY AS SHOWN DOES NOT
 MEET FAIR HOUSING GUIDELINES,FOR SECONDARY DOORS
 (SLIDING GLASS DOORS) THE GUIDELINE SPECIFY THAT THE
 THRESHOLDS AT THESE DOORS SHALL BE NO HIGHER THAN ? ?.
 THE GUIDELINES FURTHER STATE THAT CHANGES IN LEVEL AT
 THESE LOCATIONS MUST BE BEVELED WITH A SLOPE NO GREATER
 THAN 1:2.
 19A)(2) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE
 MAXIMUM ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING
 GLASS DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO
 WILL BE 4 INCHES TO THE FINISH DECK.
 NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK
 INTO THE DESIGN CRITERIA.
 19A)(3) THE STRUCTURAL PLANS WILL ALSO NEED TO
 CORRELATE THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS
 STATED ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS
 DOORS.
 19A)(4) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK
 IS TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS
 WILL REQUIRE MECHANICAL FASTENING OF TRACK.
 THE RESPONCE INDICATED HOW THEY WOULD MEET THE
 ALTERNATIVE METHODS UNDER THE FAIR HOUSING GUIDELINES,
 WHICH WILL NEED TO BE FILED WITH THE CLERK OF THE COURT
 BEFORE ISSUANCE OF THIS PERMIT.
  
 19B-19C) COMPLIED.
  
 19D) 2ND REQUEST, PLANS FAIL TO IDENTIFY THE WALL TYPES
 THAT SURROUND THE REFUSE SHOOT.707.13.3 REFUSE AND
 LAUNDRY CHUTE ACCESS ROOMS. ACCESS OPENINGS FOR REFUSE
 AND LAUNDRY CHUTES SHALL BE LOCATED IN ROOMS OR
 COMPARTMENTS COMPLETELY ENCLOSED BY CONSTRUCTION THAT
 HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR
 AND OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE.
  
 A506.2 THE GROUND FLOOR DETAIL (A) WALL TYPE 9/ 800
 PLEASE REVISE TYPO TO 9/801.
  
 19E-19G) COMPLIED.
  
  
 19H) 2ND REQUEST, PLANS INDICATE BETWEEN UNITS 2
 SEPARATE WALLS ONE WITH SOUND PROOFING THE OTHER IS A
 TWO HR RATED WALL. PLEASE PROVIDE AN ASSEMBLY HOW THE
 TWO WALLS WILL BE BUILT?
 A203 & A206 BOTH INDICATE A WALL TYPE 8 BUT THERE IS NO
 WALL DISIGNATION FOR THE SECOND WALL INDICATED ON THE
 PLAN. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
  
 19I) PROVIDE COMPLIANCE WITH:1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 19J) NO, 2ND REQUEST, PROVIDE COMPLIANCE WITH: 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. NO STC RATING PROVIDED FOR DETAIL 9/A.801.
 THE COMMON AREAS WILL NEED TO SHOW COMPLIANCE, THE
 INDIVIDUAL UNITS WILL BE REVIEWED UNDER THE TENANT
 BUILDOUT, PERMITS WILL BE REQUIRED FOR FLOOR FINISHES
 OF UNITS.
  
 20-24A) COMPLIED.
  
 24B) SEMI-COMPLIED, PLANS STILL INDICATE GRILLS TO BE
 INSTALLED SEE A108, PROVIDE MANUFACTURERS SPEC. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 24C) PROVISO; SHOP DRAWINGS FOR CATWALKS TO BE REVIEWED
 BY DESIGN PROFESSIONAL BEFORE SUBMITION TO THE BUILDING
 DEPARTMENT.
  
 24D-24F) COMPLIED.
  
 24G) A107 THE PENTHOUSE UNITS DO HAVE THEIR OWN MEANS
 OF EGRESS USING THE SPIRAL STAIRS (1009.9.3) THEY ARE
 NOT ALLOWED TO USE THE DOORS BETWEEN UNITS FOR MEANS OF
 EGRESS, 1013.2 EGRESS THROUGH INTERVENING ROOMS.
  
 24H-26B)COMPLIED.
  
 26C) SEMI-COMPLIED) SHEET A201 EGRESS WINDOWS THE
 MINIMUM HEIGHT IS 24 INCHES, THE WORDING IS STILL
 TWENTY-TWO INCHES PLEASE MAKE CORRECTION, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 26D) COMPLIED.
  
 27) SHEET A201;
  
 27A) 2ND REQUEST , PLANS INDICATE A 3'-4" MINIMUM ENTRY
 BETWWEN THE CABINETRY INTO THE KITCHEN, BUT THE FAIR
 HOUSING NOTES ON SHEET A700 NOTE 5 USABLE KITCHENS
 INDICATES THE MEASUREMENT IS TAKEN FROM THE EDGE OF
 COUNTER TOPSTO THE HANDLES OF APPLIANCES,
 REFRIGARATORS DEPHT MINIMUM IS 30 1/2 INCHES, RANGES 27
 INCHES. PLEASE ADJUST THE PLANS TO HAVE A CLEAR NET
 OPENING OF
 3'-4".
 27B) COMPLIED.
  
 27C) SEMI-COMPLIED, SEE 19A.
  
 28-32A) COMPLIED.
  
 32B) 2ND REQUEST, THE KITCHEN INDICATES A MINIMUM OF
 40" CLEAR BUT THE MEASUREMENT IS TO BE TAKEN FROM THE
 EDGE OF THE COUNTER TOP TO THE HANDLE OF THE 27" DEEP
 RANGE, SEE FAAIR HOUSING NOTE 5 LOCATED ON SHEET A700.
  
 33-41A) COMPLIED.
  
 41B) SEMI-COMPLIED, ATACHMENT DETAIL OF CURBING AS
 SHOWN ON S7.2 INDICATES THE USE OF RFB, PLANS DO NOT
 INDICATE WHO MAKES THIS ITEM? 106.1.2 ADDITIONAL
 INFORMATION.
  
 41C) 2ND REQUESTSHEET A804 PLANS MAKE REFERENCE TO
 THE SFBC, PLEASE MAKE CORRECTION.
  
 41-42) COMPLIED.
  
 43A) SEMI-COMPLIED. PILING, SHEET S-3.02 NOTE 4
 REFERENCES THE 2001 FBC
 43B) S-3.02 NOTE# 10 INDICATES THE USE OF 16 INCH PILE
 WHEREAS S-3.01 & S-3.02 BOTH INDICATE THE USE OF 18
 INCH PILE PLEASE CORRELATE PLANS, 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 44) COMPLIED.
  
 45) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 ROOFING REPORT SUBMITTED IS FOR A WOOD DECK SEE A-306
  
 46) COMPLIED.
  
 47) COMPLIED.
  
 8) PLANS ARE TO SHOWCOMPLIANCE WITH:
 403.8 FIRE COMMAND .
 A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL
 BE PROVIDED IN A LOCATION APPROVED BY THE FIRE
 DEPARTMENT.
  
  
  
 403.10 STANDBY POWER.
 A STANDBY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN
 SECTION 403.10.2 .
  
 403.10.1 SPECIAL REQUIREMENTS FOR STANDBY POWER
 SYSTEMS.
 IF THE STANDBY SYSTEM IS A GENERATOR SET INSIDE A
 BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE
 ROOM ENCLOSED WITH 2-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIER ASSEMBLIES. SYSTEM SUPERVISION WITH MANUAL
 START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE
 FIRE COMMAND CENTER.
  
 403.10.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 1.
 POWER AND LIGHTING FOR THE FIRE COMMAND CENTER REQUIRED
 BY SECTION 403.8 ;
 2.ELECTRICALLY POWERED FIRE PUMPS;
 3.VENTILATION AND AUTOMATIC FIRE DETECTION
 EQUIPMENT FOR SMOKEPROOF ENCLOSURES.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTION 3003 .
  
 403.11 EMERGENCY POWER SYSTEMS.
 AN EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED
 IN SECTION 403.11.1 .
  
 403.11.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
  
 1.EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION
 REQUIRED BY CHAPTER 10 ;
 2.ELEVATOR CAR LIGHTING;
 3.EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; 4.
 AUTOMATIC FIRE DETECTION SYSTEMS; AND
 5.FIRE ALARM SYSTEMS.
  
 403.12 STAIRWAY DOOR OPERATION.
 STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS
 SHALL BE PERMITTED TO BE LOCKED FROM
 STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED FROM THE
 STAIRWAY SIDE SHALL BE CAPABLE OF BEING UNLOCKED
 SIMULTANEOUSLY WITHOUT UNLATCHING UPON A SIGNAL FROM
 THE FIRE COMMAND CENTER.
  
 403.12.1 STAIRWAY COMMUNICATIONS SYSTEM.
 A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH REQUIRED STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 403.13 SMOKEPROOF EXIT ENCLOSURES.
 EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS
 909.20 AND 1019.1.8 .
  
 403.14 RESERVED.
  
 **403.15 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 909.**
 909.16 FIRE-FIGHTER?S SMOKE CONTROL PANEL.
 A FIRE-FIGHTER?S SMOKE CONTROL PANEL FOR FIRE
 DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE
 PROVIDED AND SHALL INCLUDE MANUAL CONTROL OR OVERRIDE
 OF AUTOMATIC CONTROL FOR MECHANICAL SMOKE CONTROL
 SYSTEMS. THE PANEL SHALL BE LOCATED IN A FIRE COMMAND
 CENTER COMPLYING WITH SECTION 911 IN HIGH-RISE
 BUILDINGS OR BUILDINGS WITH SMOKE PROTECTED ASSEMBLY
 SEATING. IN OTHER BUILDINGS, THE FIRE-FIGHTER?S SMOKE
 CONTROL PANEL SHALL BE INSTALLED IN AN APPROVED
 LOCATION ADJACENT TO THE FIRE ALARM CONTROL PANEL. THE
 FIRE-FIGHTER?S SMOKE CONTROL PANEL SHALL COMPLY WITH
 SECTIONS 909.16.1 THROUGH 909.16.3 .
  
 909.16.1 SMOKE CONTROL SYSTEMS.
 FANS WITHIN THE BUILDING SHALL BE SHOWN ON THE
 FIRE-FIGHTER?S CONTROL PANEL. A CLEAR INDICATION OF THE
 DIRECTION OF AIRFLOW AND THE RELATIONSHIP OF COMPONENTS
 SHALL BE DISPLAYED. STATUS INDICATORS SHALL BE PROVIDED
 FOR ALL SMOKE CONTROL EQUIPMENT, ANNUNCIATED BY FAN AND
 ZONE, AND BY PILOT-LAMP-TYPE INDICATORS AS FOLLOWS:
 1.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN
 THEIR NORMAL STATUS?WHITE.
 2.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN
 THEIR OFF OR CLOSED STATUS?RED.
 3.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN
 THEIR ON OR OPEN STATUS?GREEN.
 4.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN A
 FAULT STATUS?YELLOW/AMBER.
  
 909.16.2 SMOKE CONTROL PANEL.
 THE FIRE-FIGHTER?S CONTROL PANEL SHALL PROVIDE CONTROL
 CAPABILITY OVER THE COMPLETE SMOKE-CONTROL SYSTEM
 EQUIPMENT WITHIN THE BUILDING AS FOLLOWS:
 1.ON-AUTO-OFF CONTROL OVER EACH INDIVIDUAL PIECE
 OF OPERATING SMOKE CONTROL EQUIPMENT THAT CAN ALSO BE
 CONTROLLED FROM OTHER SOURCES WITHIN THE BUILDING. THIS
 INCLUDES STAIRWAY PRESSURIZATION FANS; SMOKE EXHAUST
 FANS; SUPPLY, RETURN AND EXHAUST FANS; ELEVATOR SHAFT
 FANS AND OTHER OPERATING EQUIPMENT USED OR INTENDED FOR
 SMOKE CONTROL PURPOSES.
 2.OPEN-AUTO-CLOSE CONTROL OVER INDIVIDUAL DAMPERS
 RELATING TO SMOKE CONTROL AND THAT ARE ALSO CONTROLLED
 FROM OTHER SOURCES WITHIN THE BUILDING.
 3.ON-OFF OR OPEN-CLOSE CONTROL OVER SMOKE CONTROL
 AND OTHER CRITICAL EQUIPMENT ASSOCIATED WITH A FIRE OR
 SMOKE EMERGENCY AND THAT CAN ONLY BE CONTROLLED FROM
 THE FIRE-FIGHTER?S CONTROL PANEL.
  
  
 49)COMPLIED.
  
 50) NEW,PROVIDE INFORMATION ON THE VENTILATION OF THE
 ENCLOSED PARKING GARAGE. 406.4.2 VENTILATION. A
 MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL .
 NOTEFLORIDA ADMINISTRATIVE CODE RULE 9B-3.0472 EVERY
 BUILDING WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED
 ON OR AFTER 7-1-08 AND HAVING A FOSSIL -FUEL- BURNING
 HEATER OR APPLIANCE OR AN ATTACHED GARAGE SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. IN
 CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER
 FROM
 THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FROM THE
 LOCAL POWER UTUILIY SUCH ALARMS SHALL HAVE BATTERY BACK
 UP. BOMBINATION SMOKE/ CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 51)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 THIS REVIEW IS MAY HAVE ADDITIONAL COMMENTS AS A RESULT
 OF THE DESIGNERS ANSWERS TO THE PLAN REVIEW OR NEW
 INFORMATION BEING ADDED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 FLAGLER BEACH CLUB TOWER 1ST REVIEW.DOC
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  