2007-03-27 10:04:19 | FAILED |
| |
| 1) INDICATE THE LIMITS OF WORK, TO INCLUDE DRIVE AISLES |
| AND LANDSCAPE, INCLUDED AS PART OF THIS PERMIT. |
| |
| 2) ORDINANCE NO. 3856-05 REQUIRES THE SUBMITTAL OF A |
| PHOTOMETRIC PLAN PRIOR TO BUILDING PERMIT APPROVAL. |
| |
| 3) A UNITY OF TITLE IS REQUIRED. |
| |
| 4) PLEASE NOTE THAT ORDINANCE NO. 3856-05 PROHIBITS THE |
| USE OF REFLECTIVE GLASS AND REQUIRES THE USE OF AUGER |
| CAST PILINGS. |
| |
| 5) THE PARALLEL PARKING SPACES LOCATED IN THE MIDDLE OF |
| THE SITE DO NOT CONFORM TO CITY PARKING STANDARDS. |
| |
| A. PARALLEL SPACES ARE REQUIRED TO BE 8 FEET 6 INCHES |
| WIDE. |
| B. PARALLEL SPACES ARE REQUIRED TO BE 22 FEET LONG. |
| THE SUPPORT COLUMNS LOCATED AT THE OUTSIDE EDGE OF THE |
| PARKING SPACES ENCROACH INTO EACH PARKING SPACE, |
| CREATING AN OPENING OF 21 FEET, WHICH IS INSUFFICIENT |
| FOR A STANDARD PARKING SPACE. |
| |
| 6) THE PARKING SPACE DETAIL ON SHEET A01.1 SHALL SHOW |
| THE STANDARD PARKING SPACE AS A MINIMUM OF 18 FEET IN |
| DEPTH.THE STANDARD PARKING STALL DETAIL ON SCHORAH |
| SHEET 5 IS LISTED AT 19 FEET DEEP BY 9 FEET WIDE, BUT |
| NONE OF THE PARKING STALLS ARE THIS SIZE ON THE PLANS |
| AND THE PARALLEL PARKING STALL DETAIL DOES NOT REFLECT |
| CONDITIONS ON THE SITE. |
| |
| 7) THE SOUTHERN ROW OF PARKING SPACES IS DEPICTED WITH |
| A DEPTH OF 15 FEET 10 INCHES WITH A 2 FOOT OVERHANG. |
| THIS IS LESS THAN THE REQUIRED 18 FOOT STANDARD PARKING |
| STALL DEPTH. |
| |
| 8)THE NORTHERN LANDSCAPE BUFFER IS LISTED ON THE |
| PLANS AS BEING 5 FEET WIDE ?OPEN TO ABOVE,? YET IS |
| MEASURES AS 4 FEET WIDE TO THE GARAGE ROOF LINE. |
| |
| 9) THE NORTH AND SOUTH CARPORT ROOF DETAILS SHOWN ON |
| SHEET A01.5 DO NOT MATCH THE CARPORTS SHOWN ON THE |
| CIVIL, ARCHITECTURAL SITE PLANS AND LANDSCAPE PLANS. |
| |
| 10) THE PLANTERS SHOWN ON THE CARPORT ROOFS ARE NOT |
| REFLECTED ON THE LANDSCAPE PLANS. |
| |
| 11) NO ADA WALKWAY IS PROVIDED ACROSS THE PARKING AISLE |
| FOR THE NORTHERNMOST HANDICAP PARKING SPACE. |
| |
| 12) FENCES AND COLUMNS MAY NOT EXCEED 6 FEET IN THE |
| REQUIRED SIDE AND REAR SETBACKS.THIS IS EXCEEDED ON |
| THE NORTH SIDE OF BUILDING 2 AND THE SOUTH SIDE OF |
| BUILDING 1.THE RETAINING WALL PLUS PICKET FENCE ON |
| THE NORTH PROPERTY LINE MAY NOT EXCEED 6 FEET IN HEIGHT |
| WHEN MEASURED FROM THE OUTSIDE OF THE PROPERTY (NOT 11 |
| FEET AS SHOWN).THE CMU PRIVACY WALL SHOWN ADJACENT TO |
| THE SOUTH PROPERTY LINE MAY ONLY BE 6 FEET IN HEIGHT, |
| NOT THE 8 FOOT HIGH AS SHOWN.SPECIFIC DETAILS OF THIS |
| WALL WERE NOT PROVIDED. |
| |
| 13) THE LANDSCAPE PLANS DO NOT MATCH THOSE APPROVED BY |
| ORDINANCE NO. 3856-05.MINOR AMENDMENT IS REQUIRED. |
| |
| 14) THE ROOF CANOPY (OVER CENTRAL PARKING) NEEDS |
| APPROVAL FOR A MINOR AMENDMENT FOR LANDSCAPE AND |
| DESIGN. |
| |
| 15) REMOVE THE BOAT SLIPS FROM THE PROJECT FACT SHEET. |
| |
| 16) THE PROJECT FACT SHEET SHALL BE UPDATED TO REFLECT |
| THE SETBACKS APPROVED BY THE ORDINANCE NO. 3856-05 SITE |
| PLAN. |
| |
| 17) THE FOOTPRINT AND ELEVATIONS FOR BUILDING 3 IS |
| DIFFERENT FROM THE ONE APPROVED BY ORDINANCE NO. |
| 3856-05.A MINOR AMENDMENT IS REQUIRED. |
| |
| 18) ORDINANCE NO. 3856-05 APPROVED A MAXIMUM BUILDING |
| HEIGHT OF 150 FEET.THE PLANS SHOW AIR CONDITIONED |
| SPACE (AN EXTRA FLOOR) ABOVE 150 FEET - STAIRS AND |
| LANDING - AND JACUZZIS, WHICH ARE NOT COVERED UNDER THE |
| HEIGHT EXEMPTIONS. |
| |
| 19) THE USE OF THE PRIVATE GARBAGE PICK-UP REQUIRES |
| SIGN-OFF FROM THE CITY?S ENGINEERING SERVICES |
| DEPARTMENT. |
| |
| 20) AN ABSTRACTED SURVEY, SHOWING ALL EASEMENTS, IS |
| REQUIRED. |
| |
| 21) AN APPROVED TREE RELOCATION PERMIT IS REQUIRED. |
| NOTE THAT THE TREE MITIGATION PLAN APPEARS TO CALL OUT |
| TREES INCORRECTLY AS TO SPECIES AND SHOWS TREES |
| REMAINING IN PLACE IN PAVED AREAS.ADDITIONALLY, THE |
| RELOCATED AND PRESERVED TREES DO NOT MATCH THE |
| LANDSCAPE PLAN. |
| |
| 22) PROVIDE RESPONSES TO COMMENTS IN WRITTING WITH |
| PERMIT RESUBMIT. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1435. |