2007-04-12 14:26:47-------------------DENIED-------------------
  
 FBC 2004 CODE FAMITY W/2006 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH NFPA
 90A-02
 NFPA 110-02
  
 1. AC-01: AC-6, BOTH ROOMS ARE MARKED AS 'STORAGE'
 ROOMS BUT ALSO SERVE AS PLENUMS. PLENUMS SHALL NOT BE
 USED FOR OCCUPANCY OR STORAGE PER NFPA 90A-4.3.10.1.1.
  
 2. AC-01: AC-6 CLOSETS: CAVITIES DESIGNED FOR AIR
 TRANSPORT SUCH AS MECHANICAL CLOSETS SHALL BE LINED
 WITH AN AIR BARRIER (NON-POUROUS, NO EXPOSED BLOCK) AND
 SEALED IN ACCORDANCE WITH FBC,M 603.9 AND SHALL BE
 INSULATED IN ACCORDANCE WITH FBC TABLE
 13-410.1.ABC.2.2.
  
 3. AC-01: ELECTRICAL ROOM A133, MECHANICAL PLAN CALLS
 FOR LOUVERED DOOR FOR MAKE-UP AIR, DOOR SCHEDULE IN
 ARCHITECTURAL PLAN DOES NOT CALL FOR A LOUVERED DOOR IN
 THAT LOCATION. PLEASE COORDINATE DRAWING AND SCHEDULE.
 FBC 106.1.1.
  
 4. ALL A/C CLOSETS: SEVERAL CLOSETS CALL FOR WOOD DOORS
 ON SCHEDULE (A400 AND UNIT DOOR SCHEDULES). MATERIALS
 EXPOSED IN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
 HAVE A FLAME SPREAD/SMOKE DEVELOPMENT INDEX OF NOT MORE
 THAN 25/50 PER FBC,M 602.2..1.
  
 5. AC-04: PLAN STATES "TYPICAL FLOOR PLAN (4-14)"BUT
 FLOORS 5 THRU 14 DO NOT HAVE AN AC-1 OR RELATED
 DUCTWORK. PLEASE CLARIFY PER FBC 106.1.1.
  
 6. AC-04: RISER DIAGRAM SHOWS 8" ROUND O/A DUCT TO
 FIRST FLOOR, BUT PG AC-01 SHOWS A 6" ROUND DUCT. PLEASE
 CLARIFY. FBC 106.1.1.
  
 7. AC-04 RISER DIAGRAM: AC-1 DUCTS ON 2ND THRU 4TH
 FLOORS AND O/A DUCT FOR AC-6 ON FIRST FLOOR ARE
 PENETRATING A SHEFT ENCLOSURE. PENETRATIONS OF SHAFT
 ENCLOSURES SHALL BE PROTECTED WITH APPROVED FIRE AND
 SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING PER FBC,M 607.5.5.1.
  
 8. AC-01 GARAGE VENTILATION: AUTOMATIC OPERATION OF THE
 GARAGE VENTILATION SYSTEM (BY C.O. SENSORS) SHALL NOT
 REDUCE THE VENTILATION RATE BELOW 0.05 CFM PER SQ FT OF
 FLOOR AREA PER FBC,M 404.2. PLEASE SHOW HOW THIS
 CONTINUOUS VENTILATION WILL BE PROVIDED.
  
 9. AC-01: OCCUPIED SPACES ACCESSORY TO A PUBLIC GARAGE
 (VALET OFFICE) SHALL BE MAINTAIONED AT A POSITIVE
 PRESSURE AND SHALL BE PROVIDED WITH VENTILATION IN
 ACCORDANCE WITH FBC,M 403.3 AND 404.3
  
 10. AC-01 C.O. SENSORS DRAWING NOTES: NOTE #2 AND
 SEQUENCE OF OPERATION CONDITIONS DO NOT RELATE TO
 CONDITIONS IN THIS BUILDING. PLEASE CORRECT.
  
 11. AC-13 HVAC DESIGN REQUIREMENTS SCHEDULE INDICATES
 THAT SMOKE CONTROL IS NOT REQUIRED. IN HIGH-RISE
 BUILDINGS, SMOKE CONTROLS SHALL BE PROVIDED IN
 ACCORDANCE WITH FBC SEC909 PER FBC 403.15. THIS SECTION
 WAS REVISED AS OF DEC 8, 2006.
  
 12. AC-01: MATERIALS NOTE 1 ON AC-13 LIMITS LENGTH OF
 FLEX DUCT TO 8 FEET. PLEASE VERIFY THIS WITH FLEX DUCTS
 IN THE SAUNA/GYM AREA.
  
 13. AC-01: APPLIANCES (CIRCULATION FANS) LOCATED IN
 PUBLIC GARAGES OR OTHER AREAS FREQUENTED BY MOTOR
 VEHICLES SHALL BE INSTALLED A MINIMUM OF 8 FEET ABOVE
 THE FLOOR UNLESS PROTECTED FROM VEHICLE IMPACT PER
 FBC,M 304.5.
  
 14. AC-06: STAIR 2 PRESSURIZATION FAN DOES NOT SHOW A
 DUCT SMOKE DETECTOR. PLEASE SHOW COMPLIANCE WITH FBC,M
 606.2.1.
  
 15. AC-07 UNIT A: FLEX DUCT FEEDING PDR IS MISSING
 SIZE. PLEASE CORRECT. FBC 106.1.1.
  
 16. AC-07 THRU AC-11: PLAN SHOWS 5" ROUND FLEX FEEDING
 SIDEWALL GRILL IN ELEVATOR LOBBY. HOW WILL THIS BE
 ACCOMPLISHED IF BOTH SIDES OF WALL HAVE THE SAME
 CEILING HEIGHT? ALSO, PLEASE SHOW MEANS OF ACCESS TO
 THE FIRE DAMPER. FBC 106.1.1.
  
 17. AC-07 UNIT A AND A REVERSED: PLAN APPEARS TO SHOW
 DRYER EXHAUST OUTLET TO BE IN CLOSE PROXIMITY TO THE
 O.A. INTAKES FOR AC-1 AND AC-6. PLEASE SHOW COMPLIANCE
 WITH FBC,M 401.5 AND 501.2.
  
 18. AC-07 UNIT A AND A REVERSED: A/C FLOOR PLAN CALLS
 FOR 1500 AND 1550 CFM RESPECTIVELY. HEAT PUMP SCHEDULE
 ON AC-14 SHOWS AC-3.5 AS PRODUCING 1370 CFM. PLEASE
 CLARIFY AND CORRECT AS NEEDED.
  
 19. AC-08 UNIT D AND D REVERSED: A/C FLOOR PLAN CALLS
 FOR 1450 AND 1500 CFM RESPECTIVELY. HEAT PUMP SCHEDULE
 ON AC-14 SHOWS AC-3.5 PRODUCING 1370 CFM. PLEASE
 CLARIFY AND CORRECT AS NEEDED.
  
 20. AC-08 UNIT C AND D: RETURN AIR TRANSFERS DUCT FROM
 MASTER BEDROOM IS NOT DESIGNED TO MEET THE BALANCED
 RETURN EXCEPTIONS OF FBC,M 601.4 (1 1/2 TIMES THE SIZE
 OF SUPPLY). A FIELD TEST WILL BE REQUIRED TO VERIFY
 COMPLIANCE WITH 0.01" WC MAXIMUM ALLOWABME PRESSURE
 DIFFERENTIAL UNLESS RETURNS ARE DESIGNED TO MEET THE
 EXCEPTIONS OF THIS SECTION.
  
 21. AC-09 BEDRROOM 2 W.I.C DROP IS MISSING GRILL SIZE
 AND CFM. PLEASE CORRECT.
  
 22. AC-09: PLEASE SEE COMMENT #20 REGARDING BALANCED
 RETURN,
  
 23. AC-10: WILL THERE BE PROVISIONS FOR AN AIR-TIGHT
 DOOR ON AC CLOSET IN LAUNDRY ROOM AS THERE IS IN UNIT
 C?
  
 24. AC-10: AC-5.0 AS STATED ON AC-14 IS RATED FOR 2060
 CFM. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED PER
 FBC,M 606.2..
  
 25. AC-11: TWO DROPS IN BEDROOM 2 MISSING CFM AND GRILL
 SIZES.
  
 26. AC-11: SEE COMMENT #20 REGARDING BALANCED RETURN -
 MASTER SUITE.
  
 27. AC-12: PLAN SHOWS GENERATOR EXHAUST DISCHARGING
 NORTH. PG P-1C SHOWS EXHAUST DISCHARGING EAST. PLEASE
 COORDINATE DRAWINGS.
  
 28. AC-12 GENERATOR ROOM: PLEASE SHOW HOW THE
 REQUIREMENTS OF NFPA 110-7.7.1 THROUGH 7.7.8 ARE BEING
 MET IN CONJUNCTION WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 29. AC-13 MECHANICAL EQUIPMENT NOTES #20: PROVIDE DRYER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS SHOWING
 MAXIMUM ALLOWABLE DUCT LENGTH PER FBC,M 504.6.1. IF
 DRYER BOOSTER FAN IS TO BE USED, PROVIDE DOCUMENTATION
 FROM THE DRYER MANUFACTURER DEMONSTRATING COMPATIBILITY
 WITH BOOSTER FAN. WILL MANUFACTURER HONOR WARRANTY IF
 DRYER IS USED WITH A BOOSTER FAN? FBC 106.1.2.
  
 30. AC-13 GENERAL A/C NOTES #26: PLEASE SEE COMMENT #13
 REGARDING APPLIANCES LOCATED IN GARAGES.
  
 31. AC-13 MATERIALS NOTE #1: FLEX DUCT LIMITITED TO
 MAXIMUM 8'0" BY THIS NOTE. PLAN CALLLS FOR LONGER FLEX
 DUCT IN SEVERAL AREAS. PLEASE CORRELATE NOTES AND FLOOR
 PLANS PER FBC 106.1.1.
  
 32. AC-13 MATERIALS NOTE K: THE OPERATING TEMPERATURE
 OF A FUSIBLE LINK SHALL BE APPROXIMATELY 50 DEGREES (F)
 ABOVE THE NORMAL TEMPERATURE WITHIN THE DUCT SYSTEM BUT
 NOT LESS THAN 160 DEGREES PER FBC,M 607.3.1.1. WHAT IS
 THE NORMAL TEMPERATURE WITHIN THE DUCT SYSTEM TO
 REQUIRE A 265 DEGREE FUSIBLE LINK?
  
 33. AC-13 MATERIALS NOTE T: SEE COMMENT # 29 REGARDING
 BOOSTER FANS.
  
 34. AC-13 HVAC DESIGN REQUIREMENTS: SEE COMMENT #11
 REGARDING SMOKE CONTROL.
  
 35. AC-14 HEAT PUMP SCHEDULE: UNIT B IS LISTED UNDER
 BOTH AC-3.5 AND AC-4.0. UNIT D IS MISSING FROM THE
 SCHEDULE. PLEASE CORRECT.
  
 36. AC-14 HEAT PUMP SCHEDULE: AC-5.0 IN PH-B REQUIRES
 FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC,M 606.2.1.
  
 37. AC-14 SPLIT SYSTEM SCHEDULE SHOWS AHU 2 AND CU 2
 SERVING STORAGE ROOMS. PG AC-01 SHOWS IT SERVING MAIN
 TELEPHONE ROOM. PLEASE CORRECT.
  
 38. AC-14 FAN SSCHEDULE: EF 1,2,3,4 CALL FOR WALL CAPS
 ON SOME FLOOR PLANS BUT WALL CAPS ARE NOT CALLED FOR ON
 SCHEDULE AS AN ACCESSORY. PLEASE PROVIDE DETAIL FOR
 WALL CAP EXHAUST TERMINATIONS FOR EFS AND DRYER
 EXHAUST. FBC 106.1.1.
  
 39. AC-15: CW RISER 4: PH-C IS SHOWN ON RISER AS AC-5.0
 BUT ON HP SCHEDULE AND FLOOR PLAN IT IS SHOWN AS
 AC-4.0. PLEASE CORRECT AND VERIFY ALL HEAT PUMPS AS
 CORRECTLY CORRESPONDING WITH THE AREA BEING SERVED.
  
 40. AC-15 CW1 AND CW2, PLEASE MARK ALL HPS FOR SIZE AND
 AREA BEING SERVED.
  
 41. AC-16: SHAFT ENCLOSURES THAT ARE PERMITTED TO BE
 PENETRATED BY DUCTS AND AIR TRANSFER OPENINGS SHALL BE
 PROTECTED WITH APPROVED FIRE AND SMOKE DAMPERS IN
 ACCORDANCE WITH THEIR LISTING PER FBC,M 607.5.5.1.
 PLEASE NOTE THAT THE USE OF A SUBDUCT UNDER EXCEPTION 1
 OF THIS SECTION PROVIDES AN EXCEPTION FOR THE FIRE
 DAMPER ONLY WHILE LEAVING IN PLACE THE REQUIREMENT FOR
 THE SMOKE DAMPER. IF A SHAFT IS TO BE USED FOR THE
 BATHROOM EXHAUST, A SMOKE DAMPER WILL BE REQUIRED AT
 EACH DUCT PENETRATION. AN ALTERNATE LOCATION FOR DRYER
 EXHAUST TERMINATION MAY BE NEEDED AS THE USE OF A SMOKE
 DAMPER ON DRYER EXHAUST DUCTS IS PROHIBITED PER FBC,M
 504.2.
  
 42. AC-16 EXHAUST FAN ON STAND ROOFTOP DETAIL:
 1) PLEASE REFERENCE FBC 2004, NOT 2001
 2) PRE-ENGINEERED ROOF STANDS ARE STRUCTURAL ELEMENTS
 AS DEFINED BY FAC 9B-72. AS SUCH, PRODUCT APPROVAL IS
 REQUIRED UNDER FS 553.842.
 3) BOTTOM NOTE ON DETAIL POINTS TO WHAT APPEARS TO BE A
 PITCH PAN, BUT STATES THAT STEEL PLATES ARE TO BE
 WELDED TO THE LEGS OF THE ALUMINUM STAND(?). PLEASE
 CLARIFY THIS DETAIL.
 4) PRE-ENGINEERED ROOF STANDS ARE TO BE INSTALLED PER
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 43. SOME DETAILS ON THIS PAGE DIFFER FROM STRUCTURAL
 DETAILS PROVIDED WHICH ARE RELATED TO ROOFTOP
 INSTALLATION OF DUCTS, PIPES AND EQUIPMENT. PLEASE
 COORDINATE DRAWINGS/DETAILS SO AS TO NOT BE IN CONFLICT
 WITH STRUCTURAL PLANS. THE STRUCTURAL DETAILS FOR
 OUTDOOR EQUIPMENT SHOULD PREVAIL PER FBC,M 301.13 AND
 FBC CH 15 & 16.
  
 44. AC-17 SUPPLY FAN ROOF DETAIL: SMOKE DETECTOR IS TO
 BE INSTALLED IN THE SUPPLY AIR DUCT PER FBC,M 606.2.1.
  
 45. AC-17: HEAT PUMP UNIT DETAIL:
 1) PLEASE REFERENCE FBC,M 2004, NOT 2001.
 2) PLEASE INDICATE MEANS OF SECONDARY/AUXILIARY DRAIN
 PROTECTION TO BE USED PER FBC,M 307.2.3. MOST HEAT
 PUMPS DO NOT HAVE A SECONDARY DRAIN OUTLET AND AS SUCH,
 THE METHOD SHOWN MAY NOT BE AN AVAILABLE OPTION FOR
 COMPLIANCE WITH THIS SECTION.
 3) PLEASE SPECIFY TYPE OF PIPE MATERIAL TO BE USED FOR
 CONDENSATE DISPOSAL, SHOWING COMPLIANCE WITH FBC,M
 606.2.2.1 (MATERIALS EXPOSED IN PLENUM) AND FBC,M
 307.2.2 (MIN. 3/4" I.D.).
  
 46. AC-19: PLEASE SEE COMMENT #43 REGARDING ROOFTOP
 EQUIPMENT DETAILS.
  
 47. PLEASE CORRECT ADDRESS ON ENERGY CALCULATIONS AND
 PLAN TO MATCH THAT ON PERMIT APPLICATION.
  
 48. PLEASE VERIFY MAX. TONNAGE AS STATED ON ENERGY
 CALCULATIONS. PLANS INDICATE >350 TONS.
  
 49. STAIR AND ELEVATOR SHAFT VENTS SHALL BE EQUIPPED
 WITH MOTORIZED DAMPERS THAT ARE CAPABLE OF BEING
 AUTOMATICALLY CLOSED DURING NORMAL BUILDING OPERIATION
 AND ARE INTERLOCKED TO OPEN AS REQUIRED BY FIRE AND
 SMOKE DETECTION SYSTEMS PER FBC 13-409.1.ABC.3.1.
  
 PLEASE NOTE: WHILE EVERY EFORT WAS MADE TO PERFORM A
 COMPLETE REVIEW, ADDITIONAL COMMENTS ARE POSSIBLE AFTER
 RESUBMITTAL, ESPECIALLY RELATED TO ANY CHANGES/NEW
 PAGES WHICH MAY BE SUBMITTED IN RESPONSE TO REVIEW
 COMMENTS FROM ALL TRADES.
  
  