Date |
Text |
2007-05-08 17:03:15 | 1. SITE PLAN DOES NOT ILLUSTRATE ANY FIRE HYDRANTS. |
| |
| 2. BUILDING 1 AND BUILDING 2 SHALL BE BE FIRE SPRINKLER |
| PROTECTED IN ACCORDANCE WITH FS 553.895 (2). |
| |
| 3. THE DEPICTED ENTRY CONFIGURATION SHALL BE DESIGNED |
| SO AS TO BE UTILIZED BY FIRE RESCUE. |
| |
| 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. |
| |
| 5. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| |
| 6. SUITABLE ROADS THAT CAN SUPPORT FIRE APPARATUS SHALL |
| BE PROVIDED DURING CONSTRUCTION ACTIVITIES. |
| |
| 7. TEMPORARY STANDPIPE SYSTEMS ARE REQUIRED WHEN THE |
| BUILDING REACHES THREE STORIES OR THIRTY FEET IN |
| HEIGHT. |
| |
| 8. STANDPIPE SYSTEM FOR FUTURE DOCK MUST BE PERMITTED. |
| |
| 9. DEBRIS SHALL BE REMOVED FROM THE SITE AND BUILDING |
| DAILY. |
| |
| 10. PLEASE INDICATE WHAT SAFETY PRACTICES WILL BE |
| EMPLOYED WHEN THE TORCH APPLIED ROOFING MATERIALS ARE |
| INSTALLED. |
| |
| 11. PLEASE EXPLAIN STAIRS THAT ARE ABSENT OF DOORS. |
| |
| 12. PLEASE INDICATE ON THE PLANS THAT VOID SPACES WILL |
| NOT BE USED FOR ANY PURPOSE. |
| |
| 13. ANY SECURITY FEATURES PLANNED SHALL NOT INTERFERE |
| WITH ANY EXITING FROM THE BUILDING. |
| |
| 14. PLEASE ILLUSTRATE ON THE PLANS THAT ALL EXTERIOR |
| STAIRS AND RAMPS WILL BE SLIP RESISTANT. |
| |
| 15. PLEASE EXPLAIN WHY THE PARKING AREA ON THE GROUND |
| FLOOR OF BUILDING THREE ONLY HAS A ONE HOUR FIRE |
| RATING. |
| |
| 16. ELEVATOR WARNING SIGNS ARE REQUIRED. |
| |
| 17. KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING. |
| |
| 18. ARCHITECTURAL FEATURES SUCH AS SOFFITS SHALL NOT |
| INTERFERE WITH WITH THE OPERATION OF ANY FIRE SPRINKLER |
| HEADS. |
| |
| 19. SINCE BUILDING THREE WILL BE CONSIDERED A HIGH-RISE |
| BUILDING, ALL OF THE REQUIREMENTS SHALL BE MET OF THE |
| FLORIDA FIRE AND BUILDING CODE. |
| |
| 20. THE LOBBY APPEARS TO BE AN ATRIUM AND THE REQUIRED |
| PROTECTION FOR AN ATRIUM SHALL BE PROVIDED. |
| |
| 21. THE NOTE FOR EGRESS WINDOWS ON PAGE A201 DOES NOT |
| INDICATE A MAXIMUM SILL HEIGHT. |
| |
| 22. ELEVATION DRAWING DOES NOT DISPLAY BUILDING |
| ADDRESS. A MINIMUM OF AT LEAST 6" HIGH NUMBERS WITH 1" |
| IN WIDTH SHALL BE PROVIDED. |
| |
| 23. SERVICE ELEVATOR DOORS LOCATED NEAR STAIR # 2 SHALL |
| BE MARKED "NO EXIT" SINCE IT IS IN CLOSE PROXIMITY TO |
| THE STAIR # 2 EXIT DOOR. |
| |
| 24. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR |
| LOCATIONS. |
| |
| 25. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE |
| SIGNS SHALL IDENTIFY THE STAIR IDENTITY, FLOOR LEVEL, |
| AND TERMINUS TOP AND BOTTOM. |
| |
| 26. ALL FIRE AND SMOKE DAMPERS SHALL BE DROP TESTED |
| AFTER INSTALLATION TO ENSURE PROPER OPERATION. |
| |
| 27. THE CARBON MONOXIDE DETECTORS SHOWN ON PAGE AC-01 |
| SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS |
| INSTRUCTIONS. SPACING AND AREA TO BE COVERED SHALL NOT |
| EXCEED THESE REQUIREMENTS. |
| |
| 28. MORE DETAILS NEEDED ON THE RECIRCULATION |
| RESIDENTIAL EXHAUST HOOD DISPLAYED ON PAGE AC-07. |
| |
| 29. PLEASE PROVIDE AN ELEVATION DRAWING OF THE |
| GENERATOR EXHAUST AND STAIR DISPLAYED ON PAGE AC-12. |
| |
| 30. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| COMPLETE INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER |
| SYSTEMS. |
| |
| 31. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| INSTALLATION OF THE FIRE ALARM SYSTEM. |
| |
| 32. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL |
| LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION |
| SERVICE. |
| |
| 33. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE |
| WILL SAY WHEN THE REQUIRED FIRE ALARM SYSTEM IS |
| ACTIVATED. |
| |
| 34. PLEASE INDICATE ON THE PLANS WHAT UL LISTINGS THAT |
| THE 500 GALLON FUEL TANK WILL HAVE. |
| |
| 35. PLEASE DECLARE ON PAGE P-15 THAT THE GAS |
| INSTALLATION WILL COMPLY WITH NFPA 54. |
| |
| 36. THE FDC SHOWN ON PAGE SP-1.1 SHOULD BE ROTATED TO |
| FACE SOUTH. HOSE MAY KINK THE WAY IS IS POSITIONED. |
| |
| 37. WHY ARE BUILDINGS 1 & 2 SHARING A FD CONNECTION. |
| |
| 38. FIRE SPRINKLER HEADS THAT ARE LOCATED OUTSIDE SHALL |
| BE WAX OR CORROSION RESISTANT. |
| |
| 39. SOME DRAWINGS ILLUSTRATE THAT CLOSETS ARE FIRE |
| SPRINKLER PROTECTED AND SOME ARE NOT. PLEASE PROVIDE |
| DETAILS ON THE PLANS. |
| |
| 40. PLEASE PROVIDE MORE DETAILS ON THE PRESSURE |
| RESTRICTING AND PRESSURE REGULATING DEVICES PLANNED FOR |
| USE. WILL THESE DEVICES BE FACTORYOR FIELD ADJUSTED. |
| |
| 41. THE BACKFLOW DEVICE SHOWN ON PAGE SP-14 SHALL BE |
| EQUIPPED WITH A CHAIN AND LOCK. |
| |
| 42. PLEASE VERIFY ALL DOORS THAT NEED TO BE RATED AS TO |
| THE RATING AND TYPES THAT CAN BE USED. |
| |
| 43. ELECTRIC POWERED SMOKE DETECTORS SHALL BE PROVIDED |
| ON EVERY LEVEL OF THE RESIDENTIAL UNITS. |
| |
| 44. WET FIRE HYDRANTS ARE REQUIRED PRIOR, TO DURING, |
| AND AFTER CONSTRUCTION. |
| |
| 45. THE FLORIDA FIRE PREVENTION CODE REQUIRES THAT |
| EMERGENCY INSTRUCTIONS BE PROVIDED TO THE RESIDENTS. |
| PLEASE ADVISE HOW THIS WILL BE ACCOMPLISHED AND ENSURE |
| THAT THIS REQUIREMENT IS PLACED ON THE PLANS. |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| 804-4709 PHONE |
| 804-4774 FAX |