Plan Review Notes
Plan Review Notes For Permit 07030460
Permit Number 07030460
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-05-08 17:03:151. SITE PLAN DOES NOT ILLUSTRATE ANY FIRE HYDRANTS.
  
 2. BUILDING 1 AND BUILDING 2 SHALL BE BE FIRE SPRINKLER
 PROTECTED IN ACCORDANCE WITH FS 553.895 (2).
  
 3. THE DEPICTED ENTRY CONFIGURATION SHALL BE DESIGNED
 SO AS TO BE UTILIZED BY FIRE RESCUE.
  
 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 5. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 6. SUITABLE ROADS THAT CAN SUPPORT FIRE APPARATUS SHALL
 BE PROVIDED DURING CONSTRUCTION ACTIVITIES.
  
 7. TEMPORARY STANDPIPE SYSTEMS ARE REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 8. STANDPIPE SYSTEM FOR FUTURE DOCK MUST BE PERMITTED.
  
 9. DEBRIS SHALL BE REMOVED FROM THE SITE AND BUILDING
 DAILY.
  
 10. PLEASE INDICATE WHAT SAFETY PRACTICES WILL BE
 EMPLOYED WHEN THE TORCH APPLIED ROOFING MATERIALS ARE
 INSTALLED.
  
 11. PLEASE EXPLAIN STAIRS THAT ARE ABSENT OF DOORS.
  
 12. PLEASE INDICATE ON THE PLANS THAT VOID SPACES WILL
 NOT BE USED FOR ANY PURPOSE.
  
 13. ANY SECURITY FEATURES PLANNED SHALL NOT INTERFERE
 WITH ANY EXITING FROM THE BUILDING.
  
 14. PLEASE ILLUSTRATE ON THE PLANS THAT ALL EXTERIOR
 STAIRS AND RAMPS WILL BE SLIP RESISTANT.
  
 15. PLEASE EXPLAIN WHY THE PARKING AREA ON THE GROUND
 FLOOR OF BUILDING THREE ONLY HAS A ONE HOUR FIRE
 RATING.
  
 16. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 17. KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING.
  
 18. ARCHITECTURAL FEATURES SUCH AS SOFFITS SHALL NOT
 INTERFERE WITH WITH THE OPERATION OF ANY FIRE SPRINKLER
 HEADS.
  
 19. SINCE BUILDING THREE WILL BE CONSIDERED A HIGH-RISE
 BUILDING, ALL OF THE REQUIREMENTS SHALL BE MET OF THE
 FLORIDA FIRE AND BUILDING CODE.
  
 20. THE LOBBY APPEARS TO BE AN ATRIUM AND THE REQUIRED
 PROTECTION FOR AN ATRIUM SHALL BE PROVIDED.
  
 21. THE NOTE FOR EGRESS WINDOWS ON PAGE A201 DOES NOT
 INDICATE A MAXIMUM SILL HEIGHT.
  
 22. ELEVATION DRAWING DOES NOT DISPLAY BUILDING
 ADDRESS. A MINIMUM OF AT LEAST 6" HIGH NUMBERS WITH 1"
 IN WIDTH SHALL BE PROVIDED.
  
 23. SERVICE ELEVATOR DOORS LOCATED NEAR STAIR # 2 SHALL
 BE MARKED "NO EXIT" SINCE IT IS IN CLOSE PROXIMITY TO
 THE STAIR # 2 EXIT DOOR.
  
 24. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR
 LOCATIONS.
  
 25. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE
 SIGNS SHALL IDENTIFY THE STAIR IDENTITY, FLOOR LEVEL,
 AND TERMINUS TOP AND BOTTOM.
  
 26. ALL FIRE AND SMOKE DAMPERS SHALL BE DROP TESTED
 AFTER INSTALLATION TO ENSURE PROPER OPERATION.
  
 27. THE CARBON MONOXIDE DETECTORS SHOWN ON PAGE AC-01
 SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS
 INSTRUCTIONS. SPACING AND AREA TO BE COVERED SHALL NOT
 EXCEED THESE REQUIREMENTS.
  
 28. MORE DETAILS NEEDED ON THE RECIRCULATION
 RESIDENTIAL EXHAUST HOOD DISPLAYED ON PAGE AC-07.
  
 29. PLEASE PROVIDE AN ELEVATION DRAWING OF THE
 GENERATOR EXHAUST AND STAIR DISPLAYED ON PAGE AC-12.
  
 30. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 COMPLETE INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER
 SYSTEMS.
  
 31. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 32. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 33. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE
 WILL SAY WHEN THE REQUIRED FIRE ALARM SYSTEM IS
 ACTIVATED.
  
 34. PLEASE INDICATE ON THE PLANS WHAT UL LISTINGS THAT
 THE 500 GALLON FUEL TANK WILL HAVE.
  
 35. PLEASE DECLARE ON PAGE P-15 THAT THE GAS
 INSTALLATION WILL COMPLY WITH NFPA 54.
  
 36. THE FDC SHOWN ON PAGE SP-1.1 SHOULD BE ROTATED TO
 FACE SOUTH. HOSE MAY KINK THE WAY IS IS POSITIONED.
  
 37. WHY ARE BUILDINGS 1 & 2 SHARING A FD CONNECTION.
  
 38. FIRE SPRINKLER HEADS THAT ARE LOCATED OUTSIDE SHALL
 BE WAX OR CORROSION RESISTANT.
  
 39. SOME DRAWINGS ILLUSTRATE THAT CLOSETS ARE FIRE
 SPRINKLER PROTECTED AND SOME ARE NOT. PLEASE PROVIDE
 DETAILS ON THE PLANS.
  
 40. PLEASE PROVIDE MORE DETAILS ON THE PRESSURE
 RESTRICTING AND PRESSURE REGULATING DEVICES PLANNED FOR
 USE. WILL THESE DEVICES BE FACTORYOR FIELD ADJUSTED.
  
 41. THE BACKFLOW DEVICE SHOWN ON PAGE SP-14 SHALL BE
 EQUIPPED WITH A CHAIN AND LOCK.
  
 42. PLEASE VERIFY ALL DOORS THAT NEED TO BE RATED AS TO
 THE RATING AND TYPES THAT CAN BE USED.
  
 43. ELECTRIC POWERED SMOKE DETECTORS SHALL BE PROVIDED
 ON EVERY LEVEL OF THE RESIDENTIAL UNITS.
  
 44. WET FIRE HYDRANTS ARE REQUIRED PRIOR, TO DURING,
 AND AFTER CONSTRUCTION.
  
 45. THE FLORIDA FIRE PREVENTION CODE REQUIRES THAT
 EMERGENCY INSTRUCTIONS BE PROVIDED TO THE RESIDENTS.
 PLEASE ADVISE HOW THIS WILL BE ACCOMPLISHED AND ENSURE
 THAT THIS REQUIREMENT IS PLACED ON THE PLANS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX