Date |
Text |
2007-03-30 15:45:32 | ****** UNSAT ***** |
| |
| ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| THE CITY OF WEST PALM BEACH. |
| |
| ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME |
| INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF |
| SUBMITTED PLANS COULD BE DONE. |
| |
| *** FLAGLER BEACH CLUB *** |
| |
| ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN |
| SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE NEXT REVIEW. |
| |
| ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| THE CITY OF WEST PALM BEACH. |
| |
| |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS. |
| PLEASE SEE SHEETS WHICH CONTAIN REFERENCES TO THE 2001 |
| FBC AND 2002 NEC. |
| PLEASE SEE MANY LOCATIONS ON ELECTRICAL PLANS WHICH |
| REFLECT CODES WHICH ARE FROM THE 2002 NEC ALSO. 2005 |
| NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| 2003 NFPA-20 |
| 2002 NFPA-110 |
| ** SOME OP THESE CODES MAY BE PRESENT ON PLANS HOWEVER |
| PLEASE SEE PLANS FOR ELECTRICAL AS THERE ARE SEVERAL |
| CODE SECTIONS WHICH ARE REFLECTED ON PLANS FROM THE |
| PREVIOUS CODES AND ANY NEW CODE SECTIONS SHOULD BE |
| REFLECTED. |
| |
| 2) NOTE: PLEASE SEE THAT ALL SHEETS MUST CONTAIN TITLE |
| BLOCKS FOR DESIGNERS OR RECORD WITH ALL INFORMATION AS |
| REQUIRED PER FAC 61G15-23.002 AND 61G1-16.004. PLEASE |
| SEE SHEET 358-9 |
| |
| 3) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR |
| LANDSCAPE ARCHITECT TITLE BLOCKS. FS 481.219 AND FAC |
| 61G1-16.004 |
| MISSING CERTIFICATE OF AUTHORIZATION NUMBER, MISSING |
| PRINTED NAME. |
| |
| 4) NOTE: PLEASE SEE THE SEAL FOR THE LANDSCAPE |
| ARCHITECT DOES NOT MEET THE FAC 61G1-16.002 |
| THE SEAL IS OF SIZE REQUIRED. 2 INCHES MINIMUM. |
| |
| 5) NOTE: PLEASE KNOW THAT ALL PLANS SHALL CONTAIN |
| ORIGINAL SIGNATURES, DATES AND RAISED SEALS FROM ALL |
| DESIGN PROFESSIONALS. PLEASE SEE FS 471.025 AND |
| 481.221 |
| |
| |
| 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA |
| ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING. |
| PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING |
| CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND |
| .1.3. |
| PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE |
| AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF |
| FOR CONTROL METHODS. |
| PLEASE SEE THE ELECTRICAL LIGHTING FIXTURES ON PLANS, |
| LEGEND AND ENERGY CALCULATIONS DO NOT CORRELATE. PLEASE |
| SEE 13-415.2 FOR PERFORMANCE OF INTERIOR LIGHTING. |
| PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS. |
| |
| PLEASE SEE THE ENTIRE REVISED CHAPTER 13 WITH THE 2006 |
| REVISIONS TO THE 2004 FBC ALONG WITH THE EXISTING IN |
| THE 2004. |
| |
| 7) NOTE: PLEASE CLARIFY ELEVATOR PIT/ROOM FOR GARAGE |
| ELEVATOR. |
| PLEASE SEE NEC 620 AS THIS COULD NOT BE FULLY LOCATED |
| ON PLANS. |
| |
| 8) NOTE: PLEASE SUBMIT THE MANUFACTURE?S SPECS/CUT |
| SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP |
| CONTROLLER, GENERATOR, ATS, FUEL TANK(S). |
| PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED |
| FROM OTHER TRADES. |
| 110.3, 90.7. |
| FBC 106.1.2 |
| |
| 9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL |
| CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND. |
| |
| GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE |
| COMMAND ROOM, MAIN ELECTRICAL ROOM,ELEVATOR EQUIPMENT |
| ROOM(S). |
| PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70 |
| 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3, |
| AND .4, NFPA-72 CHAPTER 2 FOR FCRM. |
| |
| 10) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR |
| STAIRS FOR BOTH UNDER NORMAL AND UNDER EMERGENCY |
| CONDITIONS. |
| PLEASE SEE THE HALLWAY EGRESS AREAS WHICH DO NOT |
| INDICATE ANY BATTERY BACK UP FIXTURES. |
| PLEASE KNOW AS THIS BUILDING MAY BE OCCUPIED AFTER |
| POWER FAILURE DUE TO A STORM, THE SINGLE FAILURE OF A |
| SINGLE OCP DEVICE WILL PLACE EGRESS HALLS IN TOTAL |
| DARKNESS OR DURING AN EMERGENCY THE LIGHTING FOR COMMON |
| AREAS HALLS AND FAILURE OF THESE WILL PLACE AREA IN |
| DARKNESS. THIS ONLY REQUIRES MINIMUM LOCATIONS FOR |
| MINIMUM LEVELS. (HALLS ARE 1FC UNDER EMERGENCY |
| CONDITIONS. |
| PLEASE SEE NFPA-101, 7.8., 7.9 |
| |
| 11 NOTE: PLEASE PROVIDE NOTES FOR FAIL SAFE OPERATION |
| OF GATES/DOORS WHICH MAY NOT INTERFERE WITH EGRESS IN |
| THE EVENT OF POWER FAILURE. |
| PLEASE SEE NFPA-101 CHAPTER 7, 7.1.9,7.2.1.5. |
| |
| 12) NOTE: PLEASE SEE DOORS ON WEST WALL WHICH SEEM TO |
| SWING IN PATH OF EGRESS. PLEASE ALSO VERIFY THE MAKE UP |
| AIR, AND/OR EXHAUST ALONG THIS SAME AREA OF EGRESS. |
| PLEASE SEE THAT THIS MAY ALSO BE IN THE COMMENTS FROM |
| OTHER TRADES. |
| PLEASE VERIFY WITH ALL TRADES AND REVIEWER(S). |
| FBC 106.1.2 |
| |
| 13) NOTE: PLEASE PLACE A SCHEDULE/ LIST FOR ALL |
| COMPONENTS IN THE FIRE COMMAND ROOM AS REQUIRED PER |
| NFPA-101 11.8.5 |
| |
| 14) NOTE: PLEASE COMPLETE ALL FIXTURE LEGENDS AS THE |
| LIGHTING NEEDS TO BE DETERMINED AT THIS TIME AND TO |
| CORRELATE AS NOTED IN NOTE FOR FBC CHAPTER 13. THE |
| LEGEND MENTIONS TBD BY OWNER; HOWEVER THIS INFORMATION |
| IS NEED TO FOR REVIEW. |
| PLEASE ALSO SEE THE EXTERIOR LIGHTING IS ALSO TO BE |
| DETERMINED AND COORDINATED WITH ENERGY CALCULATIONS AND |
| PLANS. |
| FBC CHAPTER 13-415.1.ABC.1.4, 13-415.1.ABC.2, |
| 13-415.2.ABC.1.3 ETC |
| |
| 15) NOTE: PLEASE BE SURE ALL DEVICE AND LEVELS FOR |
| HORNS AND STROBES MEET FBC ADA 11-4.28, .1, .2 AND |
| .3(4). |
| PLEASE STATE ALL LEVELS PER FBC ADA AS THE PLANS |
| CURRENTLY SHOW AND NOTE SEVERAL ITEMS TO NFPA- 72 AND |
| OTHER STANDARDS. |
| PLEASE KNOW THAT THE MINIMUM LEVELS REQUIRED IN THE FBC |
| CHAPTER 11 FOR ADA ARE SUBSTANTIALLY HIGHER. |
| |
| 16) NOTE: PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM |
| WHICH MUST MEET THE ELEVATIONS AS SET-FORTH ON THE |
| 100YEAR STORM SURGE CHARTS OR *SLOSH* CHARTS PER |
| CHAPTER 7, 7.3.1 NFPA-110. |
| PLEASE SEE THE ELEVATIONS FOR THE EQUIPMENT WHICH IS |
| BEING SHOWN AT THE GARAGE SEEMS TO BE OK, HOWEVER THE |
| LEVELS OF EPSS EQUIPMENT, FIRE PUMP, FIRE PUMP |
| CONTROLLER, AND ALL EMERGENCY EQUIPMENT AT THE MAIN |
| BUILDING NEEDS TO BE SHOWN AT 6 INCHES ABOVE. |
| |
| 17) NOTE: PLEASE PROVIDE INFORMATION ON FUEL |
| CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP |
| AND ALL EMERGENCY SYSTEMS PER 700 AND 701. |
| PLEASE SEE NFPA-110, NFPA-20 9.6.2.2 |
| * THIS WILL ALSO BE IN ADDITION AND ALONG WITH |
| INFORMATION FOR THE NEXT COMMENT. |
| |
| 18) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES |
| WITH RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS |
| SIGNED INTO LAW JULY OF 07. |
| PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE |
| AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING |
| PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL |
| INFORMATION. |
| * PLEASE SEE THE ADDITIONAL STATUTES WHICH REQUIRED |
| ON-SITE FUEL FOR A SPECIFIED AMOUNT OF TIME FOR THE |
| EMERGENCY LOADS AS REQUIRED. |
| *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED, |
| PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND |
| DOCUMENTATION FOR REVIEW. |
| PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE |
| NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS |
| ETC. |
| |
| 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS |
| PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE |
| SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE |
| LIFE SAFETY PLANS. |
| * TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE BUILDING CODES AND THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| 633, FLORIDA STATUTES* |
| |
| 20) NOTE: PLEASE PLACE AN EMERGENCY BATTERY BACK UP |
| FIXTURE OF SOME KIND IN THE LARGER BATHROOMS NEAR GYM |
| ON PLANS. THESE REQUIRED PER LS 101 7.8, 7.9 PLEASE BE |
| SURE TO SEE CHAPTER 13 AND 700.12E FOR CIRCUITING OF |
| THESE. |
| |
| 21) NOTE: PLEASE PROVIDE THE NORMAL AND EMERGENCY |
| PHOTO-METRICS FOR ALL EGRESS PATHS. PLEASE KNOW THIS |
| WOULD ALSO INCLUDE POOL DECK AREAS. ETC WHICH LEAD TO |
| THE PUBLIC RIGHT OF WAY. |
| LS 101 7.8, 7.9 |
| FBC 106.1.2 |
| |
| 22) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA LIGHTS: |
| LIGHTING SHALL BE INSTALLED A MINIMUM OF 5FT FROM |
| WATERS EDGE FOR 120V W/GFI PROTECTION AND A MINIMUM OF |
| 10FT FOR LOW VOLTAGE TYPE FIXTURES. (WORDS TO THIS |
| AFFECT) |
| 680.22, 411.4B |
| |
| 23) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA AND THE |
| EQUAL-POTENTIAL BONDING GRID WHICH IS REQUIRED PER |
| 680.26. PLEASE KNOW THE POOL PERMIT WILL BE UNDER A |
| SEPARATE PERMIT, HOWEVER AS THE STRUCTURAL ELEMENTS |
| MOST LIKELY WILL BE IN PLACE BEFORE PERMITTING OF POOL, |
| PLEASE INCLUDE NOTE AT THIS TIME. |
| |
| 24) NOTE: PLEASE INCLUDE NOTE FOR ANY LIGHTNING |
| PROTECTION SYSTEMS SHALL MEET NFPA-780. (EVEN WHEN |
| PERMITTED SEPARATELY). |
| |
| 25) NOTE: PLEASE PROVIDE WIND LOADS AND INFORMATION FOR |
| SITE/ROOF TOP POLES WHICH ARE REQUIRED TO MEET FBC |
| 140MPH. |
| THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL |
| REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA |
| (EFA) OF FIXTURE. |
| FBC 106.1.2 |
| |
| 26) NOTE: PLEASE PROVIDE NOTE FOR NO NIGHT-TIME OR DUSK |
| TO DAWN SWIMMING PERMITTED UNLESS THE INTENT IS THAT |
| NIGHT-TIME SWIMMING WILL BE ALLOWED. IF THIS IS THE |
| CASE PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR POOL AREA |
| WHICH WILL BE REQUIRED TO BE STAMPED BY THE PALM BEACH |
| COUNTY HEALTH DEPARTMENT. |
| FBC 106.1.2 |
| |
| 27) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA |
| DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA |
| DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW |
| FOR CIRCUITING CODE COMPLIANCE AND USE. (DINING AREAS |
| ETC) |
| FBC 106.1.2 |
| |
| 28) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ELEVATOR |
| ROOMS AND THE DEDICATED CIRCUITS REQUIRED PER 620.22, |
| 23 AND 24. SOME OF THESE ARE SHOWN ON PLANS, HOWEVER |
| NOT ALL. |
| PLEASE SEE COMMENT #9 ABOVE WITH RESPECT TO LIGHTING |
| REQUIRED. |
| FBC 106.1.2 |
| |
| 29) NOTE: PLEASE SEE AREA OUTSIDE ELEVATOR #1, AS THE |
| PRINT SEEMS TO HAVE MISSED IN PRINT. |
| |
| 30) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR THE SAME |
| FEEDERS AND BRANCH CIRCUITS. WORST CASE FOR EACH AS |
| LONGEST RUNS. |
| PLEASE SEE FBC 13-413.ABC.1 |
| |
| 31) NOTE: PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS |
| OF SMOKE DEVICES. PLEASE DETERMINE IF THESE ARE INDEED |
| DEVICES WHICH ONLY DETECT AND DO NOT SOUND. |
| IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO |
| HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE |
| DETECTORS. |
| IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS |
| WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE |
| CONSIDERED SA/ SMOKE ALARMS. |
| PLEASE ADJUST PLANS. |
| NFPA-72 11.5.1.1, 11.8.3 |
| |
| 32) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING GFI |
| RECEPTACLES ON SOME PENINSULAS AND KITCHEN COUNTER |
| SPACES IN KITCHENS PER 210.52C1-5. PLEASE SEE LOCATION |
| OF SOME DO NOT SEEM TO MEET THE DISTANCE AS REQUIRED. |
| PLEASE SEE SOME AREAS WHICH SHOWS WHAT APPEARS TO BE A |
| WALL SPACE AND A COUNTER SPACE, HOWEVER AREA AND USE IS |
| NOT CLEAR. SEE REDLINED PLANS FOR SOME OF THESE |
| LOCATIONS. |
| |
| 33) NOTE: PLEASE SEE SOME UNITS WHICH DO NOT APPEAR TO |
| SHOW ANY LIGHTING FIXTURES IN SOME AREAS WHERE ARE |
| LIGHT FIXTURE OF SOME KIND WILL BE REQUIRED. PLEASE ANY |
| BEDROOM OR LIVING ROOM AREAS. SOME UNITS INDICATE |
| KEYLESS FIXTURES. PLEASE SEE 210.70, LS 7.8 WHICH WILL |
| REQUIRE A LIGHT FIXTURE IF SOME SORT INSTALLED FOR |
| FINAL. |
| PLEASE SEE SOME OF THESE AREAS ARE REDLINED ON PLANS. |
| |
| 34) NOTE:PLEASE PROVIDE THE FLOOR CURB DETAIL FOR |
| BUS-DUCT PENETRATIONS. PLEASE SEE THE RISER SHOWS THIS |
| 4? CURB, HOWEVER THIS IS REQUIRED IN A DETAIL WHICH |
| GOES ALL THE WAY AROUND THE DUCT. (MAY NOT BE UP |
| AGAINST A WALL WITH ONLY THREE SIDES WITH CURB. 368.10 |
| (C) 2 B. |
| |
| 35) NOTE: PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF |
| SA/SD DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3 PLEASE |
| SEE SOME OF THE UNITS SHOW A CEILING LEVEL WHICH IS |
| HIGHER THAN THE SMOKE DEVICES WHICH ARE ON A LOWER |
| LEVEL. IF THE CEILINGS ARE 12INCHES OR GREATER IN |
| HEIGHT, THEN THESE DEVICES MUST BE MOVED TO BE LOCATED |
| WITHIN 12INCHES OF THE HIGHEST POINT OF A FLAT |
| CEILING. |
| |
| 36) NOTE: PLEASE SEE ANY BUILDING REVIEW COMMENTS WITH |
| RESPECT TO ANY DOOR SWINGS IN HALLWAYS WHICH MAY AFFECT |
| THE BACKGROUNDS OR LAYOUTS ON ELECTRICAL PLANS. THIS |
| NOTE IS ONLY MADE FOR INFORMATIONAL PURPOSE ONLY AS |
| SOME DOOR SWINGS MAY CONTAIN SOME DIRECTIONAL CHANGES. |
| |
| 37) NOTE: PLEASE SEE AREAS AT PENTHOUSE LEVELS WHICH DO |
| NOT INDICATE ANY LIGHTING OR STAIRS FOR ACCESS AND |
| EGRESS FROM THESE AREAS WHICH DO NOT SHOW LIGHTING OR |
| CONTROL FOR LIGHTING. |
| 210.70 NEC. |
| NFPA 101 7.8 |
| |
| 38) NOTE: PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL |
| OUTLETS INCLUDINGRECEPTACLES, LIGHTS, FANS AND SMOKE |
| ALARMS. PLEASE SEE ALL CIRCUITING. IT APPEARS MOST ARE |
| SHOWN. |
| PLEASE SEE 210.12. |
| |
| 39) NOTE:PLEASE SEE 2005 NEC 422.13 FOR WATER HEATERS |
| AND LOADS TO BE SHOWN AT 125%. |
| PLEASE SEE THE FOLLOWING TEXT WHICH IS BEING TAKEN FROM |
| THE CODE. |
| *THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN |
| ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120 |
| GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION |
| REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND |
| CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE |
| WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT |
| DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED |
| TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT |
| RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY |
| WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE |
| FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A |
| CONTINUOUS LOAD.* |
| |
| 40) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL INDICATE |
| THE SPECIFIC ROOMS AND AREAS IN WHICH THEY FEED. THE |
| USE OF GENERAL LIGHTS, OR RECEPTACLES WAS REVISED IN |
| 408.4 OF THE 2005 NEC FOR WHICH AREAS ETC ARE TO BE |
| SPECIFIC. |
| PLEASE SEE THE FOLLOWING TEXT TAKEN FROM THE NEC. |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| |
| 41) NOTE: PLEASE SEE ANOTHER REVISION TO THE 2005 NEC |
| WAS TO REQUIRE ALL 15/20 AMP RECEPTACLES 120V WITHIN |
| 6FT OF A SINK IN A LAUNDRY ROOM ARE REQUIRED TO BE GFI |
| OR GFI PROTECTED. 210.8A7. |
| THIS DOES NOT CHANGE EVEN IF THE RECEPTACLE IS A |
| DEDICATED POINT OF USE SINGLE RECEPTACLES. |
| |
| 42) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULES AND OTHER CIRCUITS |
| ON PLANS. |
| PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER |
| SOME SEEM TO MISSING. |
| PLEASE SEE SOME AREAS WHICH ARE BEING SHOWN AS COMMON |
| AREAS YET THEY ARE BEING SHOWN BEING FED FROM THE |
| UNITS. PLEASE ALSO SEE THESE SAME COMMON AREAS ARE |
| BEING SHOWN BEING FED FROM THE HOUSE POWER. |
| PLEASE SEE 210.25 AS COMMON AREAS ARE NOT TO BE FED |
| FROM THE TENANT PANELS OR ELECTRICAL. SOME AREAS ARE |
| REDLINED ON PLANS. |
| 408.4, 310.16, 240.4. |
| FBC 106.1.2 |
| |
| 43) NOTE: PLEASE PROVIDE NOTES ON ELECTRICAL ROOMS/FIRE |
| COMMAND ROOMS SHEETS ALONG WITH THE RISER SHEETS FOR |
| REQUIREMENTS FOR SIGNAGE FOR ALL SERVICES, MAINS, |
| LOCATIONS. |
| 230.2E, 700.8, 701.9 ETC |
| |
| 44) NOTE: PLEASE VERIFY THE SIZE OF THE OPC ON THE |
| JACUZZI AS THE LOAD IS BEING SHOWN AT 12KW AND THE |
| CIRCUIT SHOWS 80AMP OCP. |
| |
| 45) NOTE: PLEASE KNOW THAT ALL *LOCK-OFF/ON* DEVICES |
| SHALL BE APPROVED BY THIS AHJ. THE DEVICE SHALL BE AN |
| INTEGRAL PART OF THE BREAKER SO AS NOT TO BE REMOVED. |
| PLEASE KNOW THAT SNAP-ON, CLIPS ETC WHICH READILY FALL |
| OFF WHEN PANEL COVER IS REMOVED SHALL NOT BE USED. |
| PLEASE PLACE NOT ON PLANS FOR THE TYPE REQUIRED. 110.3, |
| 90.7 |
| |
| 46) NOTE: PLEASE CORRELATE ALL FEEDERS ON RISER |
| DIAGRAM. |
| PLEASE SEE MAIN 1 TO MAIN OF BUILDING AS SHOWN IS RATED |
| AT 1520AMPS,AND THIS IS A 2000AMP DEVICE. |
| PLEASE SEE 240.4 |
| * PLEASE SEE SOME OF THE FEEDERS ONLY APPEARED TO BE |
| MIS-LABLED. PLEASE SEE THERE ARE TWO SEPARATE FEEDERS |
| INDICATED ON THE SAME CONDUIT. |
| |
| 47) NOTE: PLEASE CLARIFY MAINS 2 AND 3 AT GARAGE. IS 1B |
| A 1600AMP RATED MCB? |
| IS THIS EQUIPMENT MLO WITH TWO MAINS? |
| PLEASE SEE THAT NO MORE THAN 6 SPACES ARE PERMITTED IN |
| EQUIPMENT WITH OUT THE USE OF A MCB. |
| PLEASE SEE 230.70, 230.71. |
| IF THIS EQUIPMENT IS TWO *MAINS* LOCATED ON THE SAME |
| EQUIPMENT, THE EQUIPMENT SHALL CONTAIN A FACTORY |
| INSTALLED DEAD-FRONT INSTALLED AND SHALL BE NOTED ON |
| PLANS ACCORDINGLY. |
| |
| 48) NOTE: PLEASE SEE THAT NO PANEL SCHEDULE OR |
| INFORMATION FOR PANEL XG WAS SUBMITTED OR SHOWN ON |
| PLANS. |
| PLEASE SEE NO VERIFICATION FOR TAPPED CONDUCTORS, |
| CIRCUITS, MAINS, ETC ARE SHOWN. |
| 408.36, 240.21. |
| |
| 48) NOTE: PLEASE INDICATE THE GROUNDING ELECTRODE |
| SYSTEM FOR THE SEPARATELY DERIVED GENERATOR AS THE ATS |
| IS BEING NOTED AS 4-POLE. PLEASE SEE 250.20, 250.30, |
| 250.50 ETC. |
| AS THIS SYSTEM/SERVICE AS SHOWN DOES NOT REQUIRE GF |
| PROTECTION IN SERVICE, THIS IS NOT REQUIRED TO HAVE A |
| SD SYSTEM, ALTHOUGH THIS MOST CERTAINLY MAY BE DONE. |
| PLEASE CLARIFY THIS. |
| |
| 49) NOTE: PLEASE SEE THE TOTAL LOADS FOR THE GENERATOR |
| CAN NOT BE CONFIRMED AT THIS TIME AS THE PANEL/LOAD FOR |
| XG WAS NOT SUBMITTED. |
| PLEASE ALSO CLARIFY THE LOADS AS BEING SHOWN FOR THE |
| EMERGENCY LOADS AS LOAD SHEDDING IS NOT SHOWN OR |
| INDICATED. |
| PLEASE SEE OTHER SECTIONS OF NOTES PERTAINING TO THE |
| MINIMUM LOADS NOW REQUIRED BY FLORIDA STATUTES WHICH |
| WILL REQUIRE ADDITIONAL LOAD AND USE OF FUEL ETC. |
| PLEASE SUBMIT AND COMPLETE INFORMATION. |
| 700, 701, NEC 220. ETC |
| FBC 106.3.5.1.2 |
| |
| 50) NOTE: PLEASE KNOW THAT A DETAILED RESPONSE LETTER |
| FOR ALL OF THE ABOVE NOTES WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. |
| |
| 51) NOTE: PLEASE KNOW THAT THERE IS INFORMATION NOT YET |
| SUBMITTED FOR REVIEW, SOME ITEMS CAN NOT BE REVIEWED AT |
| THIS TIME FOR CODE COMPLIANCE. |
| |
| 52) NOTE: PLEASE SEE LOAD CALCULATIONS AND THE SECTION |
| OF THE CODES IN DIFFERENT PLACES WHICH ARE FROM THE |
| PREVIOUS CODE. PLEASE SEE THE 2005 NEC AND UPDATE CODE |
| SECTIONS. |
| FBC 106.1.2 |
| |
| 53) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND |
| LARGEST MOTOR LOADS AT 125% ON EACH PANEL AND THEN FOR |
| THE SERVICE LOADS. |
| 230.42, 215.3 ETC. |
| PLEASE SHOW IN LOAD CALCULATIONS. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-03-27 19:35:27 | 2007-03-27 19:35:27 |
| TO CONTINUE ON 3/28 |
2007-03-26 07:02:36 | 2007-03-26 07:02:36 |
| REVIEW IN PROGRESS |
2007-03-25 14:30:31 | 2007-03-25 14:30:31 |
| REVIEW TO CONTINUE AND COMMENCE ON 3/26 |
2007-03-24 19:55:07 | 2007-03-24 19:55:07 |
| ON ROLLIN ELEC FOR REVIEW. |