Plan Review Notes For Permit 07030460
Permit Number 07030460
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-30 15:45:32****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME
 INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF
 SUBMITTED PLANS COULD BE DONE.
  
 *** FLAGLER BEACH CLUB ***
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 PLEASE SEE SHEETS WHICH CONTAIN REFERENCES TO THE 2001
 FBC AND 2002 NEC.
 PLEASE SEE MANY LOCATIONS ON ELECTRICAL PLANS WHICH
 REFLECT CODES WHICH ARE FROM THE 2002 NEC ALSO. 2005
 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 ** SOME OP THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE SEE PLANS FOR ELECTRICAL AS THERE ARE SEVERAL
 CODE SECTIONS WHICH ARE REFLECTED ON PLANS FROM THE
 PREVIOUS CODES AND ANY NEW CODE SECTIONS SHOULD BE
 REFLECTED.
  
 2) NOTE: PLEASE SEE THAT ALL SHEETS MUST CONTAIN TITLE
 BLOCKS FOR DESIGNERS OR RECORD WITH ALL INFORMATION AS
 REQUIRED PER FAC 61G15-23.002 AND 61G1-16.004. PLEASE
 SEE SHEET 358-9
  
 3) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR
 LANDSCAPE ARCHITECT TITLE BLOCKS. FS 481.219 AND FAC
 61G1-16.004
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER, MISSING
 PRINTED NAME.
  
 4) NOTE: PLEASE SEE THE SEAL FOR THE LANDSCAPE
 ARCHITECT DOES NOT MEET THE FAC 61G1-16.002
 THE SEAL IS OF SIZE REQUIRED. 2 INCHES MINIMUM.
  
 5) NOTE: PLEASE KNOW THAT ALL PLANS SHALL CONTAIN
 ORIGINAL SIGNATURES, DATES AND RAISED SEALS FROM ALL
 DESIGN PROFESSIONALS. PLEASE SEE FS 471.025 AND
 481.221
  
  
 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA
 ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING.
 PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING
 CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE
 AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF
 FOR CONTROL METHODS.
 PLEASE SEE THE ELECTRICAL LIGHTING FIXTURES ON PLANS,
 LEGEND AND ENERGY CALCULATIONS DO NOT CORRELATE. PLEASE
 SEE 13-415.2 FOR PERFORMANCE OF INTERIOR LIGHTING.
 PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS.
  
 PLEASE SEE THE ENTIRE REVISED CHAPTER 13 WITH THE 2006
 REVISIONS TO THE 2004 FBC ALONG WITH THE EXISTING IN
 THE 2004.
  
 7) NOTE: PLEASE CLARIFY ELEVATOR PIT/ROOM FOR GARAGE
 ELEVATOR.
 PLEASE SEE NEC 620 AS THIS COULD NOT BE FULLY LOCATED
 ON PLANS.
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURE?S SPECS/CUT
 SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP
 CONTROLLER, GENERATOR, ATS, FUEL TANK(S).
 PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED
 FROM OTHER TRADES.
 110.3, 90.7.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL
 CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
  
 GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE
 COMMAND ROOM, MAIN ELECTRICAL ROOM,ELEVATOR EQUIPMENT
 ROOM(S).
 PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70
 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3,
 AND .4, NFPA-72 CHAPTER 2 FOR FCRM.
  
 10) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 STAIRS FOR BOTH UNDER NORMAL AND UNDER EMERGENCY
 CONDITIONS.
 PLEASE SEE THE HALLWAY EGRESS AREAS WHICH DO NOT
 INDICATE ANY BATTERY BACK UP FIXTURES.
 PLEASE KNOW AS THIS BUILDING MAY BE OCCUPIED AFTER
 POWER FAILURE DUE TO A STORM, THE SINGLE FAILURE OF A
 SINGLE OCP DEVICE WILL PLACE EGRESS HALLS IN TOTAL
 DARKNESS OR DURING AN EMERGENCY THE LIGHTING FOR COMMON
 AREAS HALLS AND FAILURE OF THESE WILL PLACE AREA IN
 DARKNESS. THIS ONLY REQUIRES MINIMUM LOCATIONS FOR
 MINIMUM LEVELS. (HALLS ARE 1FC UNDER EMERGENCY
 CONDITIONS.
 PLEASE SEE NFPA-101, 7.8., 7.9
  
 11 NOTE: PLEASE PROVIDE NOTES FOR FAIL SAFE OPERATION
 OF GATES/DOORS WHICH MAY NOT INTERFERE WITH EGRESS IN
 THE EVENT OF POWER FAILURE.
 PLEASE SEE NFPA-101 CHAPTER 7, 7.1.9,7.2.1.5.
  
 12) NOTE: PLEASE SEE DOORS ON WEST WALL WHICH SEEM TO
 SWING IN PATH OF EGRESS. PLEASE ALSO VERIFY THE MAKE UP
 AIR, AND/OR EXHAUST ALONG THIS SAME AREA OF EGRESS.
 PLEASE SEE THAT THIS MAY ALSO BE IN THE COMMENTS FROM
 OTHER TRADES.
 PLEASE VERIFY WITH ALL TRADES AND REVIEWER(S).
 FBC 106.1.2
  
 13) NOTE: PLEASE PLACE A SCHEDULE/ LIST FOR ALL
 COMPONENTS IN THE FIRE COMMAND ROOM AS REQUIRED PER
 NFPA-101 11.8.5
  
 14) NOTE: PLEASE COMPLETE ALL FIXTURE LEGENDS AS THE
 LIGHTING NEEDS TO BE DETERMINED AT THIS TIME AND TO
 CORRELATE AS NOTED IN NOTE FOR FBC CHAPTER 13. THE
 LEGEND MENTIONS TBD BY OWNER; HOWEVER THIS INFORMATION
 IS NEED TO FOR REVIEW.
 PLEASE ALSO SEE THE EXTERIOR LIGHTING IS ALSO TO BE
 DETERMINED AND COORDINATED WITH ENERGY CALCULATIONS AND
 PLANS.
 FBC CHAPTER 13-415.1.ABC.1.4, 13-415.1.ABC.2,
 13-415.2.ABC.1.3 ETC
  
 15) NOTE: PLEASE BE SURE ALL DEVICE AND LEVELS FOR
 HORNS AND STROBES MEET FBC ADA 11-4.28, .1, .2 AND
 .3(4).
 PLEASE STATE ALL LEVELS PER FBC ADA AS THE PLANS
 CURRENTLY SHOW AND NOTE SEVERAL ITEMS TO NFPA- 72 AND
 OTHER STANDARDS.
 PLEASE KNOW THAT THE MINIMUM LEVELS REQUIRED IN THE FBC
 CHAPTER 11 FOR ADA ARE SUBSTANTIALLY HIGHER.
  
 16) NOTE: PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM
 WHICH MUST MEET THE ELEVATIONS AS SET-FORTH ON THE
 100YEAR STORM SURGE CHARTS OR *SLOSH* CHARTS PER
 CHAPTER 7, 7.3.1 NFPA-110.
 PLEASE SEE THE ELEVATIONS FOR THE EQUIPMENT WHICH IS
 BEING SHOWN AT THE GARAGE SEEMS TO BE OK, HOWEVER THE
 LEVELS OF EPSS EQUIPMENT, FIRE PUMP, FIRE PUMP
 CONTROLLER, AND ALL EMERGENCY EQUIPMENT AT THE MAIN
 BUILDING NEEDS TO BE SHOWN AT 6 INCHES ABOVE.
  
 17) NOTE: PLEASE PROVIDE INFORMATION ON FUEL
 CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP
 AND ALL EMERGENCY SYSTEMS PER 700 AND 701.
 PLEASE SEE NFPA-110, NFPA-20 9.6.2.2
 * THIS WILL ALSO BE IN ADDITION AND ALONG WITH
 INFORMATION FOR THE NEXT COMMENT.
  
 18) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES
 WITH RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS
 SIGNED INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 * PLEASE SEE THE ADDITIONAL STATUTES WHICH REQUIRED
 ON-SITE FUEL FOR A SPECIFIED AMOUNT OF TIME FOR THE
 EMERGENCY LOADS AS REQUIRED.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
  
 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS
 PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE
 SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE
 LIFE SAFETY PLANS.
 * TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633, FLORIDA STATUTES*
  
 20) NOTE: PLEASE PLACE AN EMERGENCY BATTERY BACK UP
 FIXTURE OF SOME KIND IN THE LARGER BATHROOMS NEAR GYM
 ON PLANS. THESE REQUIRED PER LS 101 7.8, 7.9 PLEASE BE
 SURE TO SEE CHAPTER 13 AND 700.12E FOR CIRCUITING OF
 THESE.
  
 21) NOTE: PLEASE PROVIDE THE NORMAL AND EMERGENCY
 PHOTO-METRICS FOR ALL EGRESS PATHS. PLEASE KNOW THIS
 WOULD ALSO INCLUDE POOL DECK AREAS. ETC WHICH LEAD TO
 THE PUBLIC RIGHT OF WAY.
 LS 101 7.8, 7.9
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA LIGHTS:
 LIGHTING SHALL BE INSTALLED A MINIMUM OF 5FT FROM
 WATERS EDGE FOR 120V W/GFI PROTECTION AND A MINIMUM OF
 10FT FOR LOW VOLTAGE TYPE FIXTURES. (WORDS TO THIS
 AFFECT)
 680.22, 411.4B
  
 23) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA AND THE
 EQUAL-POTENTIAL BONDING GRID WHICH IS REQUIRED PER
 680.26. PLEASE KNOW THE POOL PERMIT WILL BE UNDER A
 SEPARATE PERMIT, HOWEVER AS THE STRUCTURAL ELEMENTS
 MOST LIKELY WILL BE IN PLACE BEFORE PERMITTING OF POOL,
 PLEASE INCLUDE NOTE AT THIS TIME.
  
 24) NOTE: PLEASE INCLUDE NOTE FOR ANY LIGHTNING
 PROTECTION SYSTEMS SHALL MEET NFPA-780. (EVEN WHEN
 PERMITTED SEPARATELY).
  
 25) NOTE: PLEASE PROVIDE WIND LOADS AND INFORMATION FOR
 SITE/ROOF TOP POLES WHICH ARE REQUIRED TO MEET FBC
 140MPH.
 THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 26) NOTE: PLEASE PROVIDE NOTE FOR NO NIGHT-TIME OR DUSK
 TO DAWN SWIMMING PERMITTED UNLESS THE INTENT IS THAT
 NIGHT-TIME SWIMMING WILL BE ALLOWED. IF THIS IS THE
 CASE PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR POOL AREA
 WHICH WILL BE REQUIRED TO BE STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPARTMENT.
 FBC 106.1.2
  
 27) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA
 DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW
 FOR CIRCUITING CODE COMPLIANCE AND USE. (DINING AREAS
 ETC)
 FBC 106.1.2
  
 28) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ELEVATOR
 ROOMS AND THE DEDICATED CIRCUITS REQUIRED PER 620.22,
 23 AND 24. SOME OF THESE ARE SHOWN ON PLANS, HOWEVER
 NOT ALL.
 PLEASE SEE COMMENT #9 ABOVE WITH RESPECT TO LIGHTING
 REQUIRED.
 FBC 106.1.2
  
 29) NOTE: PLEASE SEE AREA OUTSIDE ELEVATOR #1, AS THE
 PRINT SEEMS TO HAVE MISSED IN PRINT.
  
 30) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR THE SAME
 FEEDERS AND BRANCH CIRCUITS. WORST CASE FOR EACH AS
 LONGEST RUNS.
 PLEASE SEE FBC 13-413.ABC.1
  
 31) NOTE: PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS
 OF SMOKE DEVICES. PLEASE DETERMINE IF THESE ARE INDEED
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND.
 IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO
 HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE
 DETECTORS.
 IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS
 WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE
 CONSIDERED SA/ SMOKE ALARMS.
 PLEASE ADJUST PLANS.
 NFPA-72 11.5.1.1, 11.8.3
  
 32) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING GFI
 RECEPTACLES ON SOME PENINSULAS AND KITCHEN COUNTER
 SPACES IN KITCHENS PER 210.52C1-5. PLEASE SEE LOCATION
 OF SOME DO NOT SEEM TO MEET THE DISTANCE AS REQUIRED.
 PLEASE SEE SOME AREAS WHICH SHOWS WHAT APPEARS TO BE A
 WALL SPACE AND A COUNTER SPACE, HOWEVER AREA AND USE IS
 NOT CLEAR. SEE REDLINED PLANS FOR SOME OF THESE
 LOCATIONS.
  
 33) NOTE: PLEASE SEE SOME UNITS WHICH DO NOT APPEAR TO
 SHOW ANY LIGHTING FIXTURES IN SOME AREAS WHERE ARE
 LIGHT FIXTURE OF SOME KIND WILL BE REQUIRED. PLEASE ANY
 BEDROOM OR LIVING ROOM AREAS. SOME UNITS INDICATE
 KEYLESS FIXTURES. PLEASE SEE 210.70, LS 7.8 WHICH WILL
 REQUIRE A LIGHT FIXTURE IF SOME SORT INSTALLED FOR
 FINAL.
 PLEASE SEE SOME OF THESE AREAS ARE REDLINED ON PLANS.
  
 34) NOTE:PLEASE PROVIDE THE FLOOR CURB DETAIL FOR
 BUS-DUCT PENETRATIONS. PLEASE SEE THE RISER SHOWS THIS
 4? CURB, HOWEVER THIS IS REQUIRED IN A DETAIL WHICH
 GOES ALL THE WAY AROUND THE DUCT. (MAY NOT BE UP
 AGAINST A WALL WITH ONLY THREE SIDES WITH CURB. 368.10
 (C) 2 B.
  
 35) NOTE: PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF
 SA/SD DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3 PLEASE
 SEE SOME OF THE UNITS SHOW A CEILING LEVEL WHICH IS
 HIGHER THAN THE SMOKE DEVICES WHICH ARE ON A LOWER
 LEVEL. IF THE CEILINGS ARE 12INCHES OR GREATER IN
 HEIGHT, THEN THESE DEVICES MUST BE MOVED TO BE LOCATED
 WITHIN 12INCHES OF THE HIGHEST POINT OF A FLAT
 CEILING.
  
 36) NOTE: PLEASE SEE ANY BUILDING REVIEW COMMENTS WITH
 RESPECT TO ANY DOOR SWINGS IN HALLWAYS WHICH MAY AFFECT
 THE BACKGROUNDS OR LAYOUTS ON ELECTRICAL PLANS. THIS
 NOTE IS ONLY MADE FOR INFORMATIONAL PURPOSE ONLY AS
 SOME DOOR SWINGS MAY CONTAIN SOME DIRECTIONAL CHANGES.
  
 37) NOTE: PLEASE SEE AREAS AT PENTHOUSE LEVELS WHICH DO
 NOT INDICATE ANY LIGHTING OR STAIRS FOR ACCESS AND
 EGRESS FROM THESE AREAS WHICH DO NOT SHOW LIGHTING OR
 CONTROL FOR LIGHTING.
 210.70 NEC.
 NFPA 101 7.8
  
 38) NOTE: PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL
 OUTLETS INCLUDINGRECEPTACLES, LIGHTS, FANS AND SMOKE
 ALARMS. PLEASE SEE ALL CIRCUITING. IT APPEARS MOST ARE
 SHOWN.
 PLEASE SEE 210.12.
  
 39) NOTE:PLEASE SEE 2005 NEC 422.13 FOR WATER HEATERS
 AND LOADS TO BE SHOWN AT 125%.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS BEING TAKEN FROM
 THE CODE.
 *THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.*
  
 40) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL INDICATE
 THE SPECIFIC ROOMS AND AREAS IN WHICH THEY FEED. THE
 USE OF GENERAL LIGHTS, OR RECEPTACLES WAS REVISED IN
 408.4 OF THE 2005 NEC FOR WHICH AREAS ETC ARE TO BE
 SPECIFIC.
 PLEASE SEE THE FOLLOWING TEXT TAKEN FROM THE NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
  
 41) NOTE: PLEASE SEE ANOTHER REVISION TO THE 2005 NEC
 WAS TO REQUIRE ALL 15/20 AMP RECEPTACLES 120V WITHIN
 6FT OF A SINK IN A LAUNDRY ROOM ARE REQUIRED TO BE GFI
 OR GFI PROTECTED. 210.8A7.
 THIS DOES NOT CHANGE EVEN IF THE RECEPTACLE IS A
 DEDICATED POINT OF USE SINGLE RECEPTACLES.
  
 42) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES AND OTHER CIRCUITS
 ON PLANS.
 PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER
 SOME SEEM TO MISSING.
 PLEASE SEE SOME AREAS WHICH ARE BEING SHOWN AS COMMON
 AREAS YET THEY ARE BEING SHOWN BEING FED FROM THE
 UNITS. PLEASE ALSO SEE THESE SAME COMMON AREAS ARE
 BEING SHOWN BEING FED FROM THE HOUSE POWER.
 PLEASE SEE 210.25 AS COMMON AREAS ARE NOT TO BE FED
 FROM THE TENANT PANELS OR ELECTRICAL. SOME AREAS ARE
 REDLINED ON PLANS.
 408.4, 310.16, 240.4.
 FBC 106.1.2
  
 43) NOTE: PLEASE PROVIDE NOTES ON ELECTRICAL ROOMS/FIRE
 COMMAND ROOMS SHEETS ALONG WITH THE RISER SHEETS FOR
 REQUIREMENTS FOR SIGNAGE FOR ALL SERVICES, MAINS,
 LOCATIONS.
 230.2E, 700.8, 701.9 ETC
  
 44) NOTE: PLEASE VERIFY THE SIZE OF THE OPC ON THE
 JACUZZI AS THE LOAD IS BEING SHOWN AT 12KW AND THE
 CIRCUIT SHOWS 80AMP OCP.
  
 45) NOTE: PLEASE KNOW THAT ALL *LOCK-OFF/ON* DEVICES
 SHALL BE APPROVED BY THIS AHJ. THE DEVICE SHALL BE AN
 INTEGRAL PART OF THE BREAKER SO AS NOT TO BE REMOVED.
 PLEASE KNOW THAT SNAP-ON, CLIPS ETC WHICH READILY FALL
 OFF WHEN PANEL COVER IS REMOVED SHALL NOT BE USED.
 PLEASE PLACE NOT ON PLANS FOR THE TYPE REQUIRED. 110.3,
 90.7
  
 46) NOTE: PLEASE CORRELATE ALL FEEDERS ON RISER
 DIAGRAM.
 PLEASE SEE MAIN 1 TO MAIN OF BUILDING AS SHOWN IS RATED
 AT 1520AMPS,AND THIS IS A 2000AMP DEVICE.
 PLEASE SEE 240.4
 * PLEASE SEE SOME OF THE FEEDERS ONLY APPEARED TO BE
 MIS-LABLED. PLEASE SEE THERE ARE TWO SEPARATE FEEDERS
 INDICATED ON THE SAME CONDUIT.
  
 47) NOTE: PLEASE CLARIFY MAINS 2 AND 3 AT GARAGE. IS 1B
 A 1600AMP RATED MCB?
 IS THIS EQUIPMENT MLO WITH TWO MAINS?
 PLEASE SEE THAT NO MORE THAN 6 SPACES ARE PERMITTED IN
 EQUIPMENT WITH OUT THE USE OF A MCB.
 PLEASE SEE 230.70, 230.71.
 IF THIS EQUIPMENT IS TWO *MAINS* LOCATED ON THE SAME
 EQUIPMENT, THE EQUIPMENT SHALL CONTAIN A FACTORY
 INSTALLED DEAD-FRONT INSTALLED AND SHALL BE NOTED ON
 PLANS ACCORDINGLY.
  
 48) NOTE: PLEASE SEE THAT NO PANEL SCHEDULE OR
 INFORMATION FOR PANEL XG WAS SUBMITTED OR SHOWN ON
 PLANS.
 PLEASE SEE NO VERIFICATION FOR TAPPED CONDUCTORS,
 CIRCUITS, MAINS, ETC ARE SHOWN.
 408.36, 240.21.
  
 48) NOTE: PLEASE INDICATE THE GROUNDING ELECTRODE
 SYSTEM FOR THE SEPARATELY DERIVED GENERATOR AS THE ATS
 IS BEING NOTED AS 4-POLE. PLEASE SEE 250.20, 250.30,
 250.50 ETC.
 AS THIS SYSTEM/SERVICE AS SHOWN DOES NOT REQUIRE GF
 PROTECTION IN SERVICE, THIS IS NOT REQUIRED TO HAVE A
 SD SYSTEM, ALTHOUGH THIS MOST CERTAINLY MAY BE DONE.
 PLEASE CLARIFY THIS.
  
 49) NOTE: PLEASE SEE THE TOTAL LOADS FOR THE GENERATOR
 CAN NOT BE CONFIRMED AT THIS TIME AS THE PANEL/LOAD FOR
 XG WAS NOT SUBMITTED.
 PLEASE ALSO CLARIFY THE LOADS AS BEING SHOWN FOR THE
 EMERGENCY LOADS AS LOAD SHEDDING IS NOT SHOWN OR
 INDICATED.
 PLEASE SEE OTHER SECTIONS OF NOTES PERTAINING TO THE
 MINIMUM LOADS NOW REQUIRED BY FLORIDA STATUTES WHICH
 WILL REQUIRE ADDITIONAL LOAD AND USE OF FUEL ETC.
 PLEASE SUBMIT AND COMPLETE INFORMATION.
 700, 701, NEC 220. ETC
 FBC 106.3.5.1.2
  
 50) NOTE: PLEASE KNOW THAT A DETAILED RESPONSE LETTER
 FOR ALL OF THE ABOVE NOTES WILL HELP TO EXPEDITE THE
 REVIEW PROCESS.
  
 51) NOTE: PLEASE KNOW THAT THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, SOME ITEMS CAN NOT BE REVIEWED AT
 THIS TIME FOR CODE COMPLIANCE.
  
 52) NOTE: PLEASE SEE LOAD CALCULATIONS AND THE SECTION
 OF THE CODES IN DIFFERENT PLACES WHICH ARE FROM THE
 PREVIOUS CODE. PLEASE SEE THE 2005 NEC AND UPDATE CODE
 SECTIONS.
 FBC 106.1.2
  
 53) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125% ON EACH PANEL AND THEN FOR
 THE SERVICE LOADS.
 230.42, 215.3 ETC.
 PLEASE SHOW IN LOAD CALCULATIONS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-27 19:35:272007-03-27 19:35:27
 TO CONTINUE ON 3/28
2007-03-26 07:02:362007-03-26 07:02:36
 REVIEW IN PROGRESS
2007-03-25 14:30:312007-03-25 14:30:31
 REVIEW TO CONTINUE AND COMMENCE ON 3/26
2007-03-24 19:55:072007-03-24 19:55:07
 ON ROLLIN ELEC FOR REVIEW.