2007-04-19 13:38:19 | |
| FLAGLER BEACH CLUB BUILDING# 3 ? TOWER (15 STORY)& |
| PARKING STRUCTURES |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07030460 |
| ADD: 5818 N FLAGLER DR(HIGH RISE BUILDING# 3) CONT: |
| SCOTT GROUP |
| TEL: (561)###-#### |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) ADDRESS ISSUES TO BE ADDRESSED PLEASE SEE LILI URSA |
| AT 822-1239. |
| THE CITY?S LIST THIS ADDRESS AS 5818 WHERE AS THE PLANS |
| INDICATE 5810 N FLAGLER. |
| PLEASE CORRECT. |
| |
| 3)DAVID LAWRENCE ARCHITECTURE IS MISSING THEIR |
| CERTIFICATE OF AUTHORIZATION. |
| 481.219 F .S. CERTIFICATE OF AUTHORIZATION.THE TITLE |
| BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT |
| PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL |
| INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD |
| THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND. |
| |
| 4) MISSING ARCHITECTURAL SEAL SHEETS A01.02- A809 IN |
| ONE ROLL. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| |
| 5) PROJECT IS LOCATED IN AN A-5 FLOOD ZONE. PROVIDE |
| FLOOD ZONE ELEVATION CERTIFICATE FOR NEW CONSTRUCTION |
| WITH THE BASE FLOOD ELEVATION PLUS AN ADDITIONAL SIX |
| INCHES A CITY FLOOD PLAIN REQUIREMENT. THE MINIMUM |
| FINISH SLAB ELEVATION OF 7?-6?. |
| |
| 6)FBC 1802.2.1 QUESTIONABLE SOILS, |
| WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 7)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 8)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION |
| SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT |
| HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM |
| AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE |
| PERMIT MAY BE ISSUED. |
| |
| 9)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE |
| BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 10)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING |
| ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT |
| IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. 105.13.1 THE |
| ENFORCING AGENCY SHALLREQUIRE A SPECIAL INSPECTOR TO |
| PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| PURSUANT TO A STRUCTURALINSPECTION PLAN PREPARED BY |
| THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| ISSUANCE |
| OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| 11) 109.3.10*IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PREFORMED IN A |
| MANNERSO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED |
| TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE |
| FINAL INSPECTION. |
| |
| |
| 12 ) 109.3.10.1 HURRICANE PROTECTION.IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE |
| CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION |
| TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| SECTION 113 OF THIS CHAPTER. |
| |
| |
| 13)SHEETS A01.02- A809 ARE SIGNED BUT NOT SEALED. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| |
| 14) SHEET A01.01: |
| 14A) NOTES INDICATE PLANS ARE DESIGNED TO THE 2004 FBC, |
| PLEASE UPDATE TO THE 2006 FBC AMENDMENTS. |
| |
| 14B) CODE COMPLIANCE NOTES: INDICATE THE BUILDING TYPE |
| TO BE : TYPE 1A SPRINKLED |
| ( UNPROTECTED), PLEASE CORRECT,SEE TABLE 601 FOR A |
| TYPE 1-A BUILDING ALL STRUCTURAL MEMBERS DO HAVE FIRE- |
| RESISTANCE RATINGS SEE FOOTNOTES FOR FIRE SPRINKLED |
| BUILDING. |
| |
| 15) SHEETA01.1: |
| 15A) PLANS INDICATE 5 HANDICAPPED PARKING SPACES UNDER |
| THE COVERED PARKING IN THE LOT, THE 15 STORY BUILDING |
| ALSO INDICATES 4 PARKING SPACES BUT NONE OF THESE ARE |
| DESIGNED AS ACCESSIBLE PARKING SPACES. THE DESIGNER |
| HADN?T CONSIDERED : |
| 11-2.2 EQUIVALENT FACILITATION. |
| DEPARTURES FROM PARTICULAR TECHNICAL AND SCOPING |
| REQUIREMENTS OF THIS CODE BY THE USE OF OTHER DESIGNS |
| AND TECHNOLOGIES ARE PERMITTED WHERE THE ALTERNATIVE |
| DESIGNS AND TECHNOLOGIES USED WILL PROVIDE |
| SUBSTANTIALLY EQUIVALENT OR GREATER ACCESS TO AND |
| USABILITY OF THE FACILITY. |
| DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING |
| REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY |
| OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE |
| THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN |
| ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS |
| OF THE ADA. |
| |
| 15B) PLANS INDICATE POOL, DECKS, FENCES, GATES AND |
| OTHER SITE AMENITIES THAT WOULD BE COVERED UNDER |
| SEPARATE PERMITS ALTHOUGH THERE ARE FEATURES IN THESE |
| PLANS, OTHER TRADES MAY NOT COMMENT ON THESE ISSUES |
| SINCE THERE ARE NO PERMITS APPLIED FOR AT THIS TIME FOR |
| THESE ITEMS. |
| |
| 15C) PLANS INDICATE OPEN PARKING GARAGE WITH A SECOND |
| STORY CREATING A PUTTING GREEN, |
| THIS CREATES A MIXED OCCUPANCY REQUIRING OCCUPANCY |
| SEPARATION. THE DETAILS OF THE ROOF AND OR AREA DRAINS |
| FOUND IN DETAIL ?B? SHEET A803 DO NOT INDICATE ANY FIRE |
| STOP FOR HORIZONTAL SEPARATION.712.4.1.1 |
| FIRE-RESISTANCE-RATED ASSEMBLIES. |
| PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| |
| 712.4.1.2 THROUGH-PENETRATION FIRE STOP SYSTEM. THROUGH |
| PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED AND |
| TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A |
| MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH |
| (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING |
| AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS |
| THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. |
| |
| SHEET A)1.1: |
| 15D)DETAIL ON THE EAST SIDE OF THE BUILDING INDICATE |
| A POOL DECK STAIRS AND A LOWER DECK OR SIDEWALK WHICH |
| LEADS TO THE BEACH AND BOAT DOCKS. PLANS FAIL TO |
| PROVIDE VERTICAL ACCESSIBILITY TO THE LOWER WALKWAY |
| ELEMENTS NO RAMP IS PROVIDED ONLY STAIRS. |
| |
| REQUIREMENT2. ACCESSIBLE AND USABLE PUBLIC AND COMMON |
| USE AREAS. |
| |
| SECTION 100.205(C)(1) PROVIDES THAT COVERED MULTIFAMILY |
| DWELLINGS WITH A BUILDING ENTRANCE ON AN ACCESSIBLE |
| ROUTE SHALL BE DESIGNED IN SUCH A MANNER THAT THE |
| PUBLIC AND COMMON USE AREAS ARE READILY ACCESSIBLE TO |
| AND USABLE BY HANDICAPPED PERSONS. |
| |
| GUIDELINE |
| |
| THE FOLLOWING CHART IDENTIFIES THE PUBLIC AND COMMON |
| USE AREAS THAT SHOULD BE MADE ACCESSIBLE, CITES THE |
| APPROPRIATE SECTION OF THE ANSI STANDARD, AND DESCRIBES |
| THE APPROPRIATE APPLICATION OF THE SPECIFICATIONS, |
| INCLUDING MODIFICATIONS TO THE REFERENCED STANDARD. |
| FAIR HOUSING 4.3(D). |
| |
| 15E) THE DETAIL A,B & C / A02.0ALL INDICATE A CHANGE |
| IN GRADE LESS THAN 21? WHICH WILL REQUIRE 13? TREADS ON |
| ALL STAIRS. 1003.5.1. WHERE A CHANGE IN LEVEL MEANS OF |
| EGRESS NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY |
| A STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE |
| 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF |
| EACH STEP SHALL BE READILY APPARENT. |
| |
| 16) SHEET A01.2 |
| 16A) SHEET A01.2- A01.3THE HANDICAPPED LIFT SHOWN ON |
| THE PLANS MUST MEET THE |
| REQUIREMENTS OF: 11-4.11.2. IF PLATFORM LIFTS |
| (WHEELCHAIR LIFTS) ARE USED, THEY SHALL COMPLY WITH |
| SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27 , AND ASME A17.1, |
| SAFETY CODE FOR ELEVATORS AND ESCALATORS , SECTION XX, |
| 1990. |
| 11-4.2.4 CLEAR FLOOR OR GROUND SPACE FOR WHEELCHAIRS. |
| 11-4.5 GROUND AND FLOOR SURFACES. |
| 11-4.27 CONTROLS AND OPERATING MECHANISMS. |
| |
| 16B) A01.2 PLANS IDENTIFY THE CHAIRLIFT AS A |
| WHEEL-O-VATOR MODEL BC SHROUD OR EQUAL, PLANS ARE TO |
| IDENTIFY SPECIFIC MODELS.104.2.1 W.P.B. |
| ADMINISTRATIVE CODE |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL |
| BE SPECIFIC AND THE TECHNICAL CODES "SHALL NOT BE CITED |
| AS A WHOLE OR IN PART, NOR THETERM "LEGAL" OR ITS |
| RQUIVALENT BE USEDAS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". |
| |
| 17)SHEET A101 |
| 17A) THE DOORS LOCATED ON EACH SIDE OF THE DRIVE |
| THROUGH (SF3 & SF10) DO NOT INDICATE ANY DETECTABLE |
| WARNING ON THE SIDEWALK SURFACES. |
| 11-4.29.5 DETECTABLE WARNINGS AT HAZARDOUS VEHICULAR |
| AREAS. |
| IF A WALK CROSSES OR ADJOINS A VEHICULAR WAY, AND THE |
| WALKING SURFACES ARE NOT SEPARATED BY CURBS, RAILINGS, |
| OR OTHER ELEMENTS BETWEEN THE PEDESTRIAN AREAS AND |
| VEHICULAR AREAS, THE BOUNDARY BETWEEN THE AREAS SHALL |
| BE DEFINED BY A CONTINUOUS DETECTABLE WARNING WHICH IS |
| 36 INCHES (915 MM) WIDE, COMPLYING WITH SECTION |
| 11-4.29.2 . |
| |
| 17B) THE GYM DOOR IS MISSING A IDENTIFICATION MARKER. |
| ADDITIONAL INFORMATION REQUIRED. |
| 106.1.2.* |
| |
| 17C) THE TRASH ROOM DOORIS INDICATE AS A ROLL UP DOOR |
| PLEASE PROVIDE THE LISTING REPORT PROVIDING THE 1 ? HR |
| FIRE RATING AS LISTED IN THE DOOR SCHEDULE. |
| |
| 17D) THE SAUNA ROOM DOOR (6) IS IDENTIFIED WITH A 2?-8? |
| DOOR, THIS WILL ONLY PROVIDE A 30? |
| OPENING FAIR HOUSING WILL REQUIRE A MINIMUM OF 32? |
| CLEAR WIDTH. ANSIA117.1- 404.2.3. |
| |
| 17E) WHEN REFERRING TO THE STOREFRONT DOORS FOUND ON |
| SHEET A-101 AND THE DOOR SCHEDULE ON A404, THE DOORS |
| ARE NOT REFERENCED IN THE DOOR SCHEDULE? 106.1.2. |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 17F)DOORS SF 7A ARE HORIZONTAL SLIDING DOORS, PLEASE |
| PROVIDE PRODUCT APPROVALS CONFORMING TO THE FOLLOWING: |
| |
| 1008.1.3.3 HORIZONTAL SLIDING DOORS. |
| IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING |
| DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS |
| IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 |
| SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1. THE |
| DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE OF |
| BEING OPERATED MANUALLY IN THE EVENT OF POWER FAILURE. |
| 2.THE DOORS SHALL BE OPERABLE BY A SIMPLE METHOD |
| FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3. |
| THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT |
| EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND |
| 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE |
| MINIMUM REQUIRED WIDTH. |
| 4.THE DOOR SHALL BE OPERABLE WITH A FORCE NOT TO |
| EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS |
| (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT |
| TO THE OPERATING DEVICE. |
| 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE |
| APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED, |
| SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE |
| DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA |
| 80 AND SHALL COMPLY WITH SECTION 715 . |
| 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED |
| STANDBY POWER SUPPLY. |
| |
| SHEET A101 (17F) |
| |
| 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE |
| ELECTRICALLY SUPERVISED. |
| 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED |
| WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE |
| OPERATING DEVICE. |
| 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES, |
| HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS |
| CORRIDORS. |
| |
| 18) SHEET A101A) REFLECTED CEILING PLAN: |
| 18A)SKYLIGHT DRIVE THROUGH PROVIDE PRODUCT APPROVAL |
| FOR WIND AND PROVIDE WHAT TYPE OF SAFETY GLAZING WILL |
| BE USED. 2405.2 ALLOWABLE GLAZING MATERIALS AND |
| LIMITATIONS. |
| SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS, |
| SUBJECT TO THE LISTED LIMITATIONS. |
| 1.FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING |
| MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE |
| LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM) |
| POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED |
| GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE |
| REQUIREMENTS OF SECTION 2607 , HEAT-STRENGTHENED GLASS |
| OR FULLY TEMPERED GLASS. |
| 2.FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT |
| OR LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS |
| SPECIFIED IN ITEM 1 ABOVE. |
| ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED |
| WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3 . |
| FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE |
| SECTION 2610 . GLASS-BLOCK CONSTRUCTION SHALL CONFORM |
| TO THE REQUIREMENTS OF SECTION 2101.2.5 . |
| |
| 18B)LOBBY SKYLIGHT IS IN ACTUALITY AN ATRIUM PLEASE |
| SEE ALL REQUIREMENTS IN 404 FOR : ATRIUM. AN OPENING |
| CONNECTING TWO OR MORE STORIES OTHER THAN ENCLOSED |
| STAIRWAYS, ELEVATORS, HOIST WAY, ESCALATORS, PLUMBING, |
| ELECTRICAL, AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH |
| IS CLOSED AT THE TOP AND NOT DEFINED AS A MALL. |
| STORIES, AS USED IN THIS DEFINITION, DO NOT INCLUDE |
| BALCONIES WITHIN ASSEMBLY GROUPS OR MEZZANINES THAT |
| COMPLY WITH SECTION 505. |
| |
| 404.2 USE. |
| THE ATRIUM FLOOR AREA IS PERMITTED TO BE USED FOR LOW |
| AND ORDINARY FIRE HAZARD USES WHERE THE INDIVIDUAL |
| SPACE IS PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM |
| IN ACCORDANCE WITH SECTION 903.3.1.1 . |
| |
| 404.3 AUTOMATIC SPRINKLER PROTECTION. |
| AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| INSTALLED THROUGHOUT THE ENTIRE BUILDING. |
| |
| 404.4 SMOKE CONTROL. |
| A SMOKE CONTROL SYSTEM SHALL BE INSTALLED IN ACCORDANCE |
| WITH SECTION 909. |
| |
| 404.5 ENCLOSURE OF ATRIUMS. |
| ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES |
| BY A 1-HOUR FIRE BARRIER WALL. |
| EXCEPTIONS: |
| 1.A GLASS WALL FORMING A SMOKE PARTITION WHERE |
| AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR |
| LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE |
| ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM |
| SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND |
| 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE |
| ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF |
| THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A |
| GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS |
| WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE |
| SPRINKLER SYSTEM OPERATES. |
| 2.A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH |
| SECTION 2110 AND HAVING A ?-HOUR FIRE PROTECTION |
| RATING. |
| 3.THE ADJACENT SPACES OF ANY THREE FLOORS OF THE |
| ATRIUM SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE |
| ATRIUM WHERE SUCH SPACES ARE INCLUDED IN COMPUTING THE |
| ATRIUM VOLUME FOR THE DESIGN OF THE SMOKE CONTROL |
| SYSTEM. |
| |
| 404.6 STANDBY POWER. |
| EQUIPMENT REQUIRED TO PROVIDE SMOKE CONTROL SHALL BE |
| CONNECTED TO A STANDBY POWER SYSTEM IN ACCORDANCE WITH |
| SECTION 909.11. |
| |
| 404.7 INTERIOR FINISH. |
| THE INTERIOR FINISH OF WALLS AND CEILINGS OF THE ATRIUM |
| SHALL NOT BE LESS THAN CLASS B WITH NO REDUCTION IN |
| CLASS FOR SPRINKLER PROTECTION. |
| |
| 404.8 TRAVEL DISTANCE. |
| IN OTHER THAN THE LOWEST LEVEL OF THE ATRIUM, WHERE THE |
| REQUIRED MEANS OF EGRESS IS THROUGH THE ATRIUM SPACE, |
| THE PORTION OF EXIT ACCESS TRAVEL DISTANCE WITHIN THE |
| ATRIUM SPACE SHALL NOT EXCEED 200 FEET (60 960 MM). |
| |
| 18C)PLANS IDENTIFY THE USE OF 5/8? WALLBOARD FOR USE |
| IN CONSTRUCTING OF EXTERIOR SOFFIT IN GARAGE AREAS. |
| 2508.2 |
| GYPSUM WALLBOARD SHALL NOT BE USED WHERE THERE WILL BE |
| DIRECT EXPOSURE TO WATER OR CONTINUOUS HIGH HUMIDITY |
| CONDITIONS. GYPSUM SHEATHING SHALL BE INSTALLED ON |
| EXTERIOR SURFACES IN ACCORDANCE WITH ASTM C 1280. |
| |
| 18D) THE DESIGN OF THE PARKING AREA WITHIN THE TOWER IS |
| S-2 ENCLOSED PARKING GARAGE, |
| THE PLANS INDICATE ALL BLOCK WALLS AS 2HR WALLS, AS |
| REQUIRED BY TABLE 302.3.2. |
| 18D) (1) PLEASE HAVE THE BLOCK MANUFACTURER PROVIDE THE |
| EQUIVALENT THICKNESS OF ALL |
| RATED BLOCK SEE TABLE 721.3.2. |
| 18D) (2) PLEASE INDICATE ON ALL THE STOREFRONT DOORS |
| AND WINDOWS THE FIRE RATING; ALSO INDICATE ALL OPENINGS |
| IN THE DOOR AND WINDOW SCHEDULE. TABLE 715.3. |
| |
| 18E)DOOR # 12 IS MISSING A FIRE RATING FROM THE DOOR |
| SCHEDULE. TABLE 715.3 |
| |
| 18F)PLANS QUOTE FIRE RATED CORRIDOR NOTE NFPA 101 BUT |
| DO NOT MENTION THE MORE RESTRICTIVE OCCUPANCY |
| SEPARATION BETWEEN THE ENCLOSED PARKING S-2 OCCUPANCY |
| AND ADJACENT SPACES. THE MOST RESTRICTIVE CODE IS USED |
| IN THIS CASE. 102.4*. |
| |
| 19) SHEET A102 |
| 19A)(1) SEE DETAIL B-3 SHEET A-402, THE SLIDING GLASS |
| DOOR TRACK ASSEMBLY AS SHOWN DOES NOT MEET FAIR HOUSING |
| GUIDELINES,FOR SECONDARY DOORS (SLIDING GLASS DOORS) |
| THE GUIDELINE SPECIFY THAT THE THRESHOLDS AT THESE |
| DOORS SHALL BE NO HIGHER THAN ? ?.THE GUIDELINES |
| FURTHER STATE THAT CHANGES IN LEVEL AT THESE LOCATIONS |
| MUST BE BEVELED WITH A SLOPE NO GREATER THAN 1:2. |
| 19A)(2) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE |
| MAXIMUM ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING |
| GLASS DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO |
| WILL BE 4 INCHES TO THE FINISH DECK. |
| NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK |
| INTO THE DESIGN CRITERIA. |
| 19A)(3) THE STRUCTURAL PLANS WILL ALSO NEED TO |
| CORRELATE THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS |
| STATED ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS |
| DOORS. |
| 19A)(4) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK |
| IS TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS |
| WILL REQUIRE MECHANICAL FASTENING OF TRACK. |
| |
| 19B)THIS COMMENT WILL BE COMMON TO ALL FLOORS PLANS |
| INDICATE A ? HR FIRE RATING PER NFPA 101 WHEREAS THE |
| FBC TABLE 1016.1 FOR FIRE SPRINKLED BUILDINGS REQUIRES |
| A 1 HR RATING. IF THERE IS A CONFLICT BETWEEN THE TWO |
| CODES THE MOST RESTRICTIVE RULES. 1 HOUR FIRE RATED |
| CORRIDORS WILL BE REQUIRED WITH 20MINUTE OPENING |
| PROTECTIVE. |
| |
| 19C) THERE ARE 3 DOORS THAT ARE NOT LABELED NOR SHOW UP |
| ON THE DOOR SCHEDULE AS FOLLOWS: |
| 1) TRASH ROOM DOOR |
| 2) ANY DOOR THAT LEADS TO ANY INDIVIDUAL UNIT |
| 3) ELEVATOR LOBBY DOORS |
| |
| 19D) PLANS FAIL TO IDENTIFY THE WALL TYPES THAT |
| SURROUND THE REFUSE SHOOT. |
| 707.13.3 REFUSE AND LAUNDRY CHUTE ACCESS ROOMS. ACCESS |
| OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE LOCATED |
| IN ROOMS OR COMPARTMENTS COMPLETELY ENCLOSED BY |
| CONSTRUCTION THAT HAS A FIRE-RESISTANCE RATING OF NOT |
| LESS THAN 1 HOUR AND OPENINGS INTO THE ACCESS ROOMS |
| SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| PROTECTION RATING OF NOT LESS THAN ? HOUR AND SHALL BE |
| SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF |
| SMOKE. |
| |
| 19E)GLASS WALL (SF14) AT ATRIUM TO BE 1 HR RATED, SEE |
| 404.5 EXCEPTION# 1 BELOW: |
| #1) A GLASS WALL FORMING A SMOKE PARTITION WHERE |
| AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR |
| LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE |
| ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM |
| SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND |
| 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE |
| ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF |
| THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A |
| GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS |
| WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE |
| SPRINKLER SYSTEM OPERATES. |
| |
| 19F) STAIR TOWER 1 & 2 IN BOTH CASES THE DOORS SWING |
| INTO THE STAIR LANDING MORE THAN 7? SEE 1009.1.4 |
| EXCEPTION 2. WHEN FULLY OPEN, THE DOOR SHALL NOT |
| PROJECT MORE THAN 7 INCHES (178 MM) INTO A LANDING. |
| |
| 19G)DOOR S1 IS INDICATED TO BE A 1 ? HR FIRE RATED |
| DOOR WITH A 6? WIRE GLASS VIEW PANEL |
| PLEASE PROVIDE WHAT TYPE FRAME THIS ASSEMBLY WILL BE |
| SECURED TO? |
| |
| |
| 19H) PLANS INDICATE BETWEEN UNITS 2 SEPARATE WALLS ONE |
| WITH SOUND PROOFING THE OTHER IS A TWO HR RATED WALL. |
| PLEASE PROVIDE AN ASSEMBLY HOW THE TWO WALLS WILL BE |
| BUILT? |
| |
| 19I) PROVIDE COMPLIANCE WITH:1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 19J) PROVIDE COMPLIANCE WITH: 1207.3 STRUCTURE-BORNE |
| SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 20) SHEET A102A) |
| 20A) DETAIL D SHEET A 802 SHOULD BE INTO THE ATRIUM BUT |
| IS INDICATED AS PRIVACY WALL AND PARAPET @ COVERED |
| TERRACES, PLEASE CORRECT. |
| |
| 21) SHEET A103A) |
| 21A)THIS SHEET INDICATES VARIOUS SOFFIT DETAILS |
| PROVIDE ATTACHMENT INFORMATION, NOT SUSPENDED FROM THE |
| DECK ABOVE. 106.1.2* ADD INFO. |
| |
| 21B) THIS SHEET DETAILS THE THIRD STORY CEILINGS, JUST |
| BEHIND THE 3 STORY ATRIUM THERE IS A DIMENSION OF 1?-0? |
| IN DETAIL ?B? WHAT DOES THIS DIMENSION REFLECT? |
| 106.1.2* ADD INFO. |
| |
| 21C) THIS SHEET REFLECTS THE CEILING MATERIAL SCHEDULE, |
| APPARENTLY ONLY THE SERVICE ELEVATOR AND ELEVATOR# 1 |
| LOBBIES ARE GOING TO HAVE DROPPED DRYWALL CEILINGS, |
| NONE IN ANY PART OF THIS FLOOR. IN THE UNITS MOST |
| KITCHENS AND BATHROOMS ARE DROPPED FOR A/C DUCT WORK? |
| |
| 22)SHEET A104: |
| 22A)INDICATES THE SKYLIGHT IS TO BE UNDER A SEPARATE |
| PERMIT, THIS BUILDING IS DESIGNED AS AN ENCLOSED |
| STRUCTURE, REQUIRING ALL PARTS OF THE ENVELOPE TO BE |
| PERMITTED AS A SINGLE UNIT. THE SKYLIGHT PRODUCT |
| APPROVAL INFORMATION WILL BE REQUIRED TO BE PART OF THE |
| BASE BUILDING DATA SUBMITTED BEFORE A PERMIT WILL BE |
| ISSUED. |
| |
| 22B) ON THE SOUTH SIDE OF THE SKYLIGHT THERE IS A PAIR |
| OF DOORS, NOT LABELED, NOT RATED?PLEASE PROVIDE WHAT |
| PROPOSED USAGE THIS ROOM WILL BE USED FOR? |
| |
| 22C)TO THE EAST & WEST SIDES OF THE SKYLIGHT THE |
| PLANS INDICATE A ROOF DRAIN BUT IT DOESN?T APPEAR TO |
| HAVE EMERGENCY OVERFLOW SYSTEM LOCATED ON THE EAST END |
| OF THE SKYLIGHT? 1503.4.3WHEN OTHER MEANS OF DRAINAGE |
| OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS |
| SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 |
| INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) ABOVE |
| THE FINISHED ROOF COVERING AND SHALL BE LOCATED AS |
| CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR |
| DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW |
| SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, PLUMBING. |
| |
| 23) SHEET A106: |
| 23A) PLANS INDICATE SPIRAL STAIRS, PLEASE SUBMIT |
| INFORMATION ON STAIRS: SEE 1009.9 |
| (1-3) SPIRAL STAIRWAYS. |
| |
| 24) SHEET A107: |
| 24A) PLEASE PROVIDE ADDITIONAL INFORMATION ON WHAT |
| APPEARS TO BE A WHIRLPOOL? |
| |
| 24B) PLANS ALSO INDICATE A GRILL ON THE EXTERIOR OF |
| EACH UNIT; PROVIDE MANUFACTURERS SPECS ON THESE UNITS. |
| DO THESE UNITS ALSO NEED VENTS? |
| |
| 24C) PLANS INDICATE AN ALUMINUM CATWALK SYSTEM TO BE |
| COORDINATED WITH THE MECHANICAL EQUIPMENT, ADDITIONAL |
| INFORMATION WILL BE NEEDED ON BOTH? |
| |
| 24D) MACHINE ROOM# 3 THE PLANS MAY HAVE A TYPO, THERE |
| ARE STAIRS INDICATED AND A DOOR DESIGNATION R-3 BUT NO |
| DOOR, DOOR IS AROUND THE CORNER.106.1.2* ADD INFO |
| REQUIRED. |
| |
| 24E) IN THE CENTER OF THE BUILDING THE PLANS INDICATE |
| VARIOUS ROOF DRAINS BUT NO SECONDARY |
| OVERFLOW DRAINS.1503.4.3WHEN OTHER MEANS OF |
| DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW |
| SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS |
| THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) |
| ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED |
| AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR |
| DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW |
| SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, PLUMBING. |
| |
| 24F) THE ELEVATOR MACHINE ROOM DOORS ARE LABELED (R1) |
| DOORS WITH 45 MIN DOORS PLEASE CORRECT TO 1 ? HR RATED |
| DOORS (SHAFTS)/ ELEVATOR MACHINE ROOMS. |
| |
| 24G) PLANS INDICATE BETWEEN PENTHOUSE UNITS TERRACE A |
| DOOR THIS WILL CROSS UNIT LINES REQUIRING A UNITY OF |
| TITLE BETWEEN UNITS. |
| |
| 24H) STAIRWELL# 1 INDICATES THAT A 6? DIA. FIRE RATED |
| VIEW PANEL WILL BE IN THIS DOOR, WILL NEED TO BE TESTED |
| FOR WIND PRESSURES ALSO. |
| |
| |
| 25) SHEET A108: |
| 25A)PLANS INDICATE ON PENTHOUSE B AND THE REVERSE |
| PENTHOUSE BTHE ROOF SCUPPERS ARE DIRECTLY OVER THE |
| DOORWAY!!!!! |
| |
| 25B) ALL ROOF SCUPPERS ARE INSTALLED LEVEL WITH THE |
| ROOF DECK, PLANS DO NOT INDICATE ANY EMERGENCY OVERFLOW |
| SCUPPERS. 1503.4.3WHEN OTHER MEANS OF DRAINAGE OF |
| OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS SHALL |
| BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES |
| (51 MM) NOR MORE THAN 4 INCHES (102 MM) ABOVE THE |
| FINISHED ROOF COVERING AND SHALL BE LOCATED AS CLOSE AS |
| PRACTICAL TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR |
| WALL AND PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE |
| SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| PLUMBING. |
| |
| 26) SHEET A201: NOTES 26A-26C COMMON TO ALL 200 SERIES |
| SHEETS. |
| 26A) GENERAL NOTE# 9 INDICATES APPROVAL FROM THE |
| ARCHITECT AND BUILDING DEPARTMENT. PLEASE CORRECT THE |
| DESIGNER OF RECORD APPROVES, THE CITY REVIEWS FOR CODE |
| COMPLIANCE ONLY!! |
| |
| 26B) FINISH NOTES COMMENT ONLY ON NFPA 101, THE 2006 |
| FBC803.1/ TABLE 803.5 ARE THE CODE SECTIONS THE |
| BUILDING DEPARTMENT WILL REVIEW TOO. |
| |
| 26C) EGRESS WINDOWS THE MINIMUM HEIGHT IS 24? NOT 22? |
| AND THE MINIMUM OPEN VENT SIZE IS 5.7? SECOND FLORR AND |
| 5.0? FIRST FLOOR NOT 4.)?. SEE FBC 1025.2 BUILDING. |
| |
| 26D) UNIT DOOR SCHEDULE INDICATES WOOD DOORS (8-9) BOTH |
| INDICATE WOOD DOORS AND FRAMES FIRE RATED 60 MINUTE |
| DOORS. PLEASE PROVIDE APPROVAL REPORTS FOR 1 HR FIRE |
| RATING. |
| |
| 27) SHEET A201: |
| 27A) PLANS INDICATE 3?-0? ENTRY BETWEEN CABINET ENTRY |
| INTO THE KITCHEN, PLEASE SEE A700. |
| THE TITLE INDICATES PALM BEACH COUNTY ACCESSIBILITY |
| CODE PLEASE CORRECT TO THE 2004 |
| /2006 FBC CHAPTER 11 PARTB FAIR HOUSING ACCESSIBILITY |
| GUIDELINES. |
| SEE NOTE# 5 INDICATES A MINIMUM OF 40? FOR KITCHENS NOT |
| THE 3?-0? DIMENSIONED IN THE PLAN. USABLE KITCHENS |
| (1)(B) |
| |
| 27B) PLANS DO NOT INDICATE THE SIZE OF THE SHOWER |
| DOOR? |
| |
| |
| 27C) IMPORTANT NOTE!!!!! PLANS DO NOT INDICATE |
| INFORMATION AS TO EXTERIOR SLIDERS,SEE COMMENT |
| 19A)(1-3), AGAIN IT IS CRITICAL THAT THE SLIDING DOOR |
| TRACK BE RECESSED ENOUGH TO ALLOW NO MORE THAN ?? ABOVE |
| FINISH FLOOR AND FROM THE INTERIOR FINISH FLOOR TO THE |
| TOP OF THE BALCONY DECK NO MORE THAN A 4? DROP. THIS IS |
| TYPICAL OF ALL EXTERIOR SLIDING GLASS DOOR UNITS!!!! |
| LEGEND-CURBS TYPICAL FOR ALL UNITS, THIS COMMENT WILL |
| NOT BE RESTATED!!!!!!!!!!!!!!!! |
| |
| 28) SHEET A203: |
| 28A) THE PRIMARY ENTRANCE DOORS ARE A PAIR OF 30? |
| DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN DOOR IS 32? |
| WHEN OPEN 90DEGREES TO THE OPENING. ANSI 4.13./ |
| 1008.1.1. |
| |
| 28B) USABLE DOOR #14 DOES NOT MEET THE GUIDELINES, THE |
| BIFOLD DOOR IS LISTED AS 1 ?? |
| OR 3 ?? SUBTRACTED FROM 2?-10? LEAVES A 2?-61/2? |
| OPENING. THE MINIMUM CLEAR OPENING IS 2?-8? FOR USABLE |
| DOORS. |
| |
| 29) SHEET A205: |
| 29A) THE PRIMARY ENTRY DOOR #8 WOULD REQUIRE A CLEAR |
| 32? THIS WILL NOT BE POSSIBLE WITH A 30? DOOR. |
| 1008.1.1. |
| |
| 30) SHEET A207: DOOR # 7 IS INDICATED AS A TYPE ?D? |
| POCKET WHERE IT IS SHOWN AS A SWING DOOR. |
| |
| 31) SHEET A209) DOOR 3 & 4 BOTH ARE BI-FOLD DOORS |
| 2?-10? BIFOLD ? 31/2? = 2?-61/2? THIS DOES NOT MEET THE |
| 32? FOR USABLE DOORS. |
| |
| 32) SHEET A212: |
| 32A) ENTRY DOOR# 10, ) THE PRIMARY ENTRANCE DOORS ARE A |
| PAIR OF 30? DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN |
| DOOR IS 32? WHEN OPEN 90DEGREES TO THE OPENING. ANSI |
| 4.13./ 1008.1.1. |
| |
| 32B)KITCHEN MISSING THE DIMENSION BETWEEN CABINETS. |
| MINIMUM 40? CLEAR. |
| |
| 32C) BIFOLD DOORS ARE BI-FOLD DOORS 2?-10? BIFOLD ? |
| 31/2? = 2?-61/2? THIS DOES NOT MEET THE 32? FOR USABLE |
| DOORS. |
| |
| 33) SHEET A215: |
| 33A)DOOR # 8 ) THE PRIMARY ENTRANCE DOORS ARE A PAIR |
| OF 30? DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN DOOR |
| IS 32? WHEN OPEN 90DEGREES TO THE OPENING. ANSI 4.13./ |
| 1008.1.1. |
| |
| 33B) DOOR# 17 IS A 2?-8? DOOR IS REQUIRED TO BE 32? AS |
| BEING A USABLE DOOR AND IN CLOSETS DEEPER THAN 2?-0?. |
| |
| 34) SHEET A402 HAS VARIOUS DETAILS INDICATING THE USE |
| OF STEEL TO CREATE STRUCTURAL MULLIONS.1707.4.5.1 |
| MULLIONS OCCURRING BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE REQUIRED BY AN |
| APPROVED TESTING LABORATORY OR BE ENGINEERED. |
| 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE |
| DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR |
| ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE. |
| |
| 35) SHEET A-501 INDICATES IN DETAIL# 2 A 3? GAP BETWEEN |
| THE HANDRAIL AND WALL. FAIR HOUSING ANSI A117.1, 505.5 |
| CLEARANCE BETWEEN THE CLEAR SPACE BETWEEN THE WALL AND |
| THE HANDRAIL SHALL BE 1 ??. |
| |
| 36) SHEET A-503: |
| 36A) PLANS DO NOT PROVIDE COMPLIANCE FOR THE ELEVATOR |
| CARS TO ACCOMMODATE AMBULANCE STRETCHER REQUIREMENTS |
| 3002.4. |
| |
| 36B) PLEASE NOTE SIGNAGE REQUIREMENT: 3002.3 EMERGENCY |
| SIGNS. |
| AN APPROVED PICTORIAL SIGN OF A STANDARDIZED DESIGN |
| SHALL BE POSTED ADJACENT TO EACH ELEVATOR CALL STATION |
| ON ALL FLOORS INSTRUCTING OCCUPANTS TO USE THE EXIT |
| STAIRWAYS AND NOT TO USE THE ELEVATORS IN CASE OF FIRE. |
| THE SIGN SHALL READ: IN FIRE EMERGENCY, DO NOT USE |
| ELEVATOR. USE EXIT STAIRS. THE EMERGENCY SIGN SHALL NOT |
| BE REQUIRED FOR ELEVATORS THAT ARE PART OF AN |
| ACCESSIBLE MEANS OF EGRESS COMPLYING WITH SECTION 1007 |
| . |
| |
| 3004.2 LOCATION OF VENTS. |
| VENTS SHALL BE LOCATED BELOW THE FLOOR OR FLOORS AT THE |
| TOP OF THE HOISTWAY, AND SHALL OPEN EITHER DIRECTLY TO |
| THE OUTER AIR OR THROUGH NONCOMBUSTIBLE DUCTS TO THE |
| OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO |
| PASS THROUGH THE ELEVATOR MACHINE ROOM PROVIDED THAT |
| PORTIONS OF THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR |
| MACHINE ROOM ARE |
| |
| ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE FIRE |
| PROTECTION RATING REQUIRED FOR THE HOISTWAY. HOLES IN |
| THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES, |
| CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE |
| LIMITED SO AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 |
| MM) OF CLEARANCE ON ALL SIDES. |
| |
| 3004.3 AREA OF VENTS. |
| EXCEPT AS PROVIDED FOR IN SECTION 3004.3.1 , THE AREA |
| OF THE VENTS SHALL NOT BE LESS THAN 3? PERCENT OF THE |
| AREA OF THE HOISTWAY NOR LESS THAN 3 SQUARE FEET (0.28 |
| M 2 ) FOR EACH ELEVATOR CAR, AND NOT LESS THAN 3? |
| PERCENT NOR LESS THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR |
| EACH DUMBWAITER CAR IN THE HOISTWAY, WHICHEVER IS |
| GREATER. OF THE TOTAL REQUIRED VENT AREA, NOT LESS THAN |
| ONE-THIRD SHALL BE OF THE PERMANENTLY OPEN TYPE UNLESS |
| ALL VENTS ACTIVATE UPON DETECTION OF SMOKE FROM ANY OF |
| THE ELEVATOR LOBBY SMOKE DETECTORS. |
| |
| 37) SHEET A600 AND ALL 600 SHEETS: |
| 37A) FIRE RATING LEGEND WALLS, PLEASE SEE TABLE 601 FOR |
| FIRE RATINGS OF STRUCTURAL MEMBERS AND NON RATED |
| WALLS. |
| |
| 38)SHEET A700: |
| 38A) PLANS INDICATE PALM BEACH COUNTY ACCESSIBILITY |
| PLEASE CORRECT TO 2004/2006 FLORIDA BUILDING CODE |
| CHAPTER 11 FLORIDA ACCESSIBILITY CODE. |
| |
| 38B) NOTE 16 -01 IS ILLEGIBLE DOUBLE TYPED. |
| |
| 38C) NOTE 16-04 PLEASE SEE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES UNDER PURPOSE: |
| THE DESIGN TEAM IS RESPONSIBLE FOR FAIR HOUSING .!!! |
| PURPOSE: THE PURPOSE OF THESE GUIDELINES IS TO PROVIDE |
| TECHNICAL GUIDANCE ON DESIGNING DWELLING UNITS AS |
| REQUIRED BY THE FAIR HOUSING AMENDMENTS ACT OF 1988 |
| (FAIR HOUSING ACT). THESE GUIDELINES ARE NOT MANDATORY, |
| NOR DO THEY PRESCRIBE SPECIFIC REQUIREMENTS WHICH MUST |
| BE MET, AND WHICH, IF NOT MET, WOULD CONSTITUTE |
| UNLAWFUL DISCRIMINATION UNDER THE FAIR HOUSING ACT. |
| BUILDERS AND DEVELOPERS MAY CHOOSE TO DEPART FROM THESE |
| GUIDELINES AND SEEK ALTERNATE WAYS TO DEMONSTRATE THAT |
| THEY HAVE MET THE REQUIREMENTS OF THE FAIR HOUSING ACT. |
| THESE GUIDELINES ARE INTENDED TO PROVIDE A SAFE HARBOR |
| FOR COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF |
| THE FAIR HOUSING ACT. |
| |
| 39) SHEET A802 DETAIL ?G? IS DOESN?T INDICATE HOW THIS |
| SUPPORT IS TO BE TIED DOWN TO THE ROOF DECK PLEASE |
| PROVIDE A CONTINUOUS PATH OF RESISTANCE. |
| |
| 40) SHEET A803 PLEASE PROVIDE RATING BETWEEN THE |
| ASSEMBLY OCCUPANCY AND THE S-2 OCCUPANCY BELOW. |
| |
| 41) SHEET A804: |
| 41A)DETAIL H PLANS INDICATE A POOL COPING DETAIL, |
| WHEREAS IT IS ACTUALLY AN EXHAUST FAN DETAIL, PLEASE |
| CORRECT. |
| |
| 41B) PLANS ALSO DO NOT INDICATE ANY STRAPPING IN THIS |
| DETAIL SECURING THE CURB TO THE ROOF DECK? |
| |
| 41C) PLANS MAKEREFERENCE TO THE SFBC, CORRECT |
| |
| 42) SHEET S703 CORRECT THE REFERENCED STANDARDS : |
| REINFORCED MASONRY NOTES |
| 42A) ACI 530.1-99 |
| 42B) ASCE 5-99 |
| 42C) ASCE 6-99 |
| 42D) TMS 402-99 |
| |
| SHEARWALL NOTES |
| 42E) ACI 318-99 |
| 42F) ACI 318R-92 |
| |
| 42G)2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 43 ) S-103 PLANS INDICATE THERE WILL BE PILING BUT NO |
| INFORMATION HAS BEEN SUBMITTED |
| THAT THIS WILL BE PART OF THIS PERMIT. PLEASE PROVIDE |
| WHAT TYPE OF PILING, DIAMETER, |
| LENGTH OF PILE, REINFORCING REQUIREMENTS, ETC. |
| |
| 44) S-901 IT APPEARS THAT RWDI HAS COMPLETED A WIND |
| TUNNEL TEST. PLEASE SUBMIT 3 ORIGINAL SIGNED& SEAL |
| REPORTS . |
| |
| 45) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF |
| PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) FIXED GLASS |
| B) STOREFRONT GLASS |
| C) OPERABLE WINDOWS |
| D) MULLIONS HORIZONTAL & VERTICAL |
| E) SKYLIGHTS |
| F) GLASS BLOCK |
| G) LOUVERS |
| H) HOLLOW METAL DOORS/ ROOF HATCHES |
| I) GLASS DOORS SWING |
| J) OVERHEAD DOORS/ COIL DOORS |
| K) SLIDING GLASS DOORS |
| L) AUTOMATIC HORIZONTAL SLIDING DOORS |
| M)PANEL WALL SYSTEM: SOFFITS, EFIS |
| N) ROOFING ASSEMBLIES |
| |
| AT THIS TIME NO APPROVALS (GLAZING) CAN BE REVIEWED! |
| FOR EXAMPLE FOR STOREFRONT PGT NOA 03-0508.03 WAS |
| SUBMITTED FOR LARGE AND SMALL MISSILE TESTING. |
| THE FIRST ISSUE IS FOR THE LARGE MISSILE |
| TEST NO ONE HAS INDICATED WHICH FASTENER TYPE WAS TO BE |
| USED, SECOND WHICH STYLE LAMINATED GLAZING WAS TO BE |
| INSTALLED. PLEASE HIGHLIGHT OR INDICATE THE DESIGN |
| TEAM?S CHOICE. |
| THE NEXT ISSUE WITH THIS PRODUCT APPROVAL |
| IS THE LIMITATION ON THE HEIGHT AND WIDTH OR MAXIMUM |
| DAYLIGHT OPENING ALLOWED BY THE NOA, SEE SHEET A400 & |
| A401. |
| |
| THE NEXT ISSUE IS WITHIN THE NOA ITSELF, |
| THIS PGTNOA INDICATES THAT IT IS TO BE USED FOR LARGE |
| AND SMALL MISSILE IMPACT WINDOW BUT THERE IS NO |
| LITERATURE FOR SMALL MISSILE IMPACT RATING INDICATED IN |
| THE PRODUCT APPROVAL? |
| THIS COMMENT WILL STAND FOR ALL PRODUCT |
| APPROVALS IN REGARDS TO THE WIND STUDY. SINCE THERE ARE |
| NUMEROUS WIND PRESSURE ZONES FOR THIS BUILDING THE |
| DESIGN TEAM WILL NEED TO PROVIDE SOME MEANS OF |
| IDENTIFYING WHICH PRODUCT APPROVALS WILL TIE TO THERE |
| ASSOCIATED GLAZING UNIT FOR BOTH LARGE AND SMALL |
| MISSILE UNITS. |
| |
| THIS NEXT ISSUE WILL DEAL WITH THE WIND |
| REPORT SUBMITTED FROM RWDI AND THE REQUIREMENTS OF |
| ASCE7-02 SECTION 6.6 METHOD 3 WIND TUNNEL TEST. UNDER |
| THE HEADING OF LIMITATIONS SEE ANALYSIS FOR WIND SPEEDS |
| CONFORMS TO THE REQUIREMENTS OF SECTION 6.5.4.2. |
| 6.5.4.2 ESTIMATION OF BASIC WIND SPEEDS FROM |
| REGIONAL CLIMATIC DATA |
| (2) THE DESIGN WIND SPEEDS RESULTING FROM THE STUDY |
| SHALL NOT BE LESS THAN THE RESULTING |
| 500-YEAR RETURN PERIOD WIND SPEED DIVIDED BY SQUARE |
| ROOT OF 1.5. |
| THE SQUARE ROOT OF 1.5 IS 1.22. 500 DIVIDED |
| BY 1.22= 154 WIND SPEED. THE RESULTING STUDY SHOULD |
| HAVE BEEN COMPOSED USING 154 MPH NOT THE 145 MPH 3 |
| SECOND GUST. |
| |
| ANOTHER ISSUE WITH THE WIND STUDY PLEASE |
| COMMENT ON WHY ON A SYMMETRIC BUILDING SEE FIGURE# 6 |
| THE WEST ELEVATION THE PRESSURES ARE SYMMETRIC BUT ON |
| THE EAST SIDE OF THE BUILDING WHICH IS ALSO SYMMETRIC |
| WHY THERE IS A DIFFERENCE IN CONFIGURATION IN PRESSURE |
| ZONES 75/ 85 FROM THE CENTERED 65 PSF? I WOULD BELIEVE |
| THE WIND WOULD BE EFFECTED THE SAME AMOUNT ON A |
| SYMMETRIC BUILDING. THE SAME CONCEPT I WOULD BELIEVE |
| HOLD TRUE ON THE NORTH AND SOUTH SIDES? |
| |
| THE SAME ISSUE WITH THE SLIDING GLASS DOOR NOA |
| SUBMITTED. THE TYPE OF GLAZING |
| (LAMINATION) WAS NOTHIGHLIGHTED . PROVIDE A DETAILED |
| ACCOUNT WHERE EACH OF THESE TYPE UNITS ARE TO LOCATED |
| ON THE BUILDING. |
| |
| MULLIONS:1707.4.5.1 MULLIONS OCCURRING BETWEEN |
| INDIVIDUAL WINDOW AND GLASS DOOR ASSEMBLIES. TESTING |
| REPORTS ARE REQUIRED BY AN APPROVED TESTING LABORATORY |
| OR BE ENGINEERED. |
| 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE |
| DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR |
| ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE. |
| |
| THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE |
| FOLLOW ITEMS: |
| ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__ |
| CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED. |
| _X__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| _2&3__ . |
| SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM |
| HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED._X__ THE |
| SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD THE |
| FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS |
| DETERMINED BY THEBUILDING OFFICIAL, A REVISED |
| FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A |
| FLORIDA REGISTEREDPROFESSIONAL ENGINEER, |
| REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT |
| MAY BE SUBMITTED. |
| _X__THE SYSTEM PROVIDED INDICATESLIMITATION# |
| 9, NO ENHANCEDFASTENING ALLOWED. |
| |
| |
| 46)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. |
| WWW.FLORIDABUILDING.ORG |
| |
| 47) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 48) PLANS ARE TO SHOWCOMPLIANCE WITH: |
| 403.8 FIRE COMMAND . |
| A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL |
| BE PROVIDED IN A LOCATION APPROVED BY THE FIRE |
| DEPARTMENT. |
| |
| 403.9 ELEVATORS. |
| ELEVATOR OPERATION AND INSTALLATION SHALL BE IN |
| ACCORDANCE WITH CHAPTER 30 . |
| |
| 403.10 STANDBY POWER. |
| A STANDBY POWER SYSTEM COMPLYING WITH SECTION 2702 |
| SHALL BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN |
| SECTION 403.10.2 . |
| |
| 403.10.1 SPECIAL REQUIREMENTS FOR STANDBY POWER |
| SYSTEMS. |
| IF THE STANDBY SYSTEM IS A GENERATOR SET INSIDE A |
| BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE |
| ROOM ENCLOSED WITH 2-HOUR FIRE-RESISTANCE-RATED FIRE |
| BARRIER ASSEMBLIES. SYSTEM SUPERVISION WITH MANUAL |
| START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE |
| FIRE COMMAND CENTER. |
| |
| 403.10.2 STANDBY POWER LOADS. |
| THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 1. |
| POWER AND LIGHTING FOR THE FIRE COMMAND CENTER REQUIRED |
| BY SECTION 403.8 ; |
| 2.ELECTRICALLY POWERED FIRE PUMPS; |
| 3.VENTILATION AND AUTOMATIC FIRE DETECTION |
| EQUIPMENT FOR SMOKEPROOF ENCLOSURES. |
| STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN |
| ACCORDANCE WITH SECTION 3003 . |
| |
| 403.11 EMERGENCY POWER SYSTEMS. |
| AN EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702 |
| SHALL BE PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED |
| IN SECTION 403.11.1 . |
| |
| 403.11.1 EMERGENCY POWER LOADS. |
| THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS: |
| |
| 1.EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION |
| REQUIRED BY CHAPTER 10 ; |
| 2.ELEVATOR CAR LIGHTING; |
| 3.EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; 4. |
| AUTOMATIC FIRE DETECTION SYSTEMS; AND |
| 5.FIRE ALARM SYSTEMS. |
| |
| 403.12 STAIRWAY DOOR OPERATION. |
| STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS |
| SHALL BE PERMITTED TO BE LOCKED FROM |
| STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED FROM THE |
| STAIRWAY SIDE SHALL BE CAPABLE OF BEING UNLOCKED |
| SIMULTANEOUSLY WITHOUT UNLATCHING UPON A SIGNAL FROM |
| THE FIRE COMMAND CENTER. |
| |
| 403.12.1 STAIRWAY COMMUNICATIONS SYSTEM. |
| A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM |
| CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION |
| SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN |
| EACH REQUIRED STAIRWAY WHERE THE DOORS TO THE STAIRWAY |
| ARE LOCKED. |
| |
| 403.13 SMOKEPROOF EXIT ENCLOSURES. |
| EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75 |
| FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE |
| DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS |
| 909.20 AND 1019.1.8 . |
| |
| 403.14 RESERVED. |
| |
| 403.15 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE |
| WITH SECTION 909. |
| |
| 49)SHEET AC-01 THE VALET OFFICE INDICATES A THROUGH |
| THE WALL A/C UNIT, IS THIS GOING TO DRAW FRESH AIR FROM |
| THE ENCLOSED PARKING GARAGE? |
| |
| 50)PROVIDE INFORMATION ON THE VENTILATION OF THE |
| ENCLOSED PARKING GARAGE. 406.4.2 VENTILATION. A |
| MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL |
| . |
| |
| |
| 51)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST |
| BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| THIS REVIEW IS MAY HAVE ADDITIONAL COMMENTS AS A RESULT |
| OF THE DESIGNERS ANSWERS TO THE PLAN REVIEW OR NEW |
| INFORMATION BEING ADDED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| FLAGLER BEACH CLUB TOWER 1ST REVIEW.DOC |
| |
| |