 FLAGLER BEACH CLUB BUILDING# 3 ? TOWER (15 STORY)&
 PARKING STRUCTURES
  
 BUILDING PLAN REVIEW
 PERMIT: 07030460
 ADD: 5818 N FLAGLER DR(HIGH RISE BUILDING# 3) CONT:
 SCOTT GROUP
 TEL: (561)###-####
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) ADDRESS ISSUES TO BE ADDRESSED PLEASE SEE LILI URSA
 AT 822-1239.
 THE CITY?S LIST THIS ADDRESS AS 5818 WHERE AS THE PLANS
 INDICATE 5810 N FLAGLER.
 PLEASE CORRECT.
  
 3)DAVID LAWRENCE ARCHITECTURE IS MISSING THEIR
 CERTIFICATE OF AUTHORIZATION.
 481.219 F .S. CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 4) MISSING ARCHITECTURAL SEAL SHEETS A01.02- A809 IN
 ONE ROLL.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) PROJECT IS LOCATED IN AN A-5 FLOOD ZONE. PROVIDE
 FLOOD ZONE ELEVATION CERTIFICATE FOR NEW CONSTRUCTION
 WITH THE BASE FLOOD ELEVATION PLUS AN ADDITIONAL SIX
 INCHES A CITY FLOOD PLAIN REQUIREMENT. THE MINIMUM
 FINISH SLAB ELEVATION OF 7?-6?.
  
 6)FBC 1802.2.1 QUESTIONABLE SOILS,
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 7)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 8)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 9)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 10)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING
 ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS. 105.13.1 THE
 ENFORCING AGENCY SHALLREQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURALINSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 11) 109.3.10*IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PREFORMED IN A
 MANNERSO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
  
 12 ) 109.3.10.1 HURRICANE PROTECTION.IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 13)SHEETS A01.02- A809 ARE SIGNED BUT NOT SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 14) SHEET A01.01:
 14A) NOTES INDICATE PLANS ARE DESIGNED TO THE 2004 FBC,
 PLEASE UPDATE TO THE 2006 FBC AMENDMENTS.
  
 14B) CODE COMPLIANCE NOTES: INDICATE THE BUILDING TYPE
 TO BE : TYPE 1A SPRINKLED
 ( UNPROTECTED), PLEASE CORRECT,SEE TABLE 601 FOR A
 TYPE 1-A BUILDING ALL STRUCTURAL MEMBERS DO HAVE FIRE-
 RESISTANCE RATINGS SEE FOOTNOTES FOR FIRE SPRINKLED
 BUILDING.
  
 15) SHEETA01.1:
 15A) PLANS INDICATE 5 HANDICAPPED PARKING SPACES UNDER
 THE COVERED PARKING IN THE LOT, THE 15 STORY BUILDING
 ALSO INDICATES 4 PARKING SPACES BUT NONE OF THESE ARE
 DESIGNED AS ACCESSIBLE PARKING SPACES. THE DESIGNER
 HADN?T CONSIDERED :
 11-2.2 EQUIVALENT FACILITATION.
 DEPARTURES FROM PARTICULAR TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE BY THE USE OF OTHER DESIGNS
 AND TECHNOLOGIES ARE PERMITTED WHERE THE ALTERNATIVE
 DESIGNS AND TECHNOLOGIES USED WILL PROVIDE
 SUBSTANTIALLY EQUIVALENT OR GREATER ACCESS TO AND
 USABILITY OF THE FACILITY.
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
  
 15B) PLANS INDICATE POOL, DECKS, FENCES, GATES AND
 OTHER SITE AMENITIES THAT WOULD BE COVERED UNDER
 SEPARATE PERMITS ALTHOUGH THERE ARE FEATURES IN THESE
 PLANS, OTHER TRADES MAY NOT COMMENT ON THESE ISSUES
 SINCE THERE ARE NO PERMITS APPLIED FOR AT THIS TIME FOR
 THESE ITEMS.
  
 15C) PLANS INDICATE OPEN PARKING GARAGE WITH A SECOND
 STORY CREATING A PUTTING GREEN,
 THIS CREATES A MIXED OCCUPANCY REQUIRING OCCUPANCY
 SEPARATION. THE DETAILS OF THE ROOF AND OR AREA DRAINS
 FOUND IN DETAIL ?B? SHEET A803 DO NOT INDICATE ANY FIRE
 STOP FOR HORIZONTAL SEPARATION.712.4.1.1
 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 712.4.1.2 THROUGH-PENETRATION FIRE STOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING
 AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
  
 SHEET A)1.1:
 15D)DETAIL ON THE EAST SIDE OF THE BUILDING INDICATE
 A POOL DECK STAIRS AND A LOWER DECK OR SIDEWALK WHICH
 LEADS TO THE BEACH AND BOAT DOCKS. PLANS FAIL TO
 PROVIDE VERTICAL ACCESSIBILITY TO THE LOWER WALKWAY
 ELEMENTS NO RAMP IS PROVIDED ONLY STAIRS.
  
 REQUIREMENT2. ACCESSIBLE AND USABLE PUBLIC AND COMMON
 USE AREAS.
  
 SECTION 100.205(C)(1) PROVIDES THAT COVERED MULTIFAMILY
 DWELLINGS WITH A BUILDING ENTRANCE ON AN ACCESSIBLE
 ROUTE SHALL BE DESIGNED IN SUCH A MANNER THAT THE
 PUBLIC AND COMMON USE AREAS ARE READILY ACCESSIBLE TO
 AND USABLE BY HANDICAPPED PERSONS.
  
 GUIDELINE
  
 THE FOLLOWING CHART IDENTIFIES THE PUBLIC AND COMMON
 USE AREAS THAT SHOULD BE MADE ACCESSIBLE, CITES THE
 APPROPRIATE SECTION OF THE ANSI STANDARD, AND DESCRIBES
 THE APPROPRIATE APPLICATION OF THE SPECIFICATIONS,
 INCLUDING MODIFICATIONS TO THE REFERENCED STANDARD.
 FAIR HOUSING 4.3(D).
  
 15E) THE DETAIL A,B & C / A02.0ALL INDICATE A CHANGE
 IN GRADE LESS THAN 21? WHICH WILL REQUIRE 13? TREADS ON
 ALL STAIRS. 1003.5.1. WHERE A CHANGE IN LEVEL MEANS OF
 EGRESS NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY
 A STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT.
  
 16) SHEET A01.2
 16A) SHEET A01.2- A01.3THE HANDICAPPED LIFT SHOWN ON
 THE PLANS MUST MEET THE
 REQUIREMENTS OF: 11-4.11.2. IF PLATFORM LIFTS
 (WHEELCHAIR LIFTS) ARE USED, THEY SHALL COMPLY WITH
 SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27 , AND ASME A17.1,
 SAFETY CODE FOR ELEVATORS AND ESCALATORS , SECTION XX,
 1990.
 11-4.2.4 CLEAR FLOOR OR GROUND SPACE FOR WHEELCHAIRS.
 11-4.5 GROUND AND FLOOR SURFACES.
 11-4.27 CONTROLS AND OPERATING MECHANISMS.
  
 16B) A01.2 PLANS IDENTIFY THE CHAIRLIFT AS A
 WHEEL-O-VATOR MODEL BC SHROUD OR EQUAL, PLANS ARE TO
 IDENTIFY SPECIFIC MODELS.104.2.1 W.P.B.
 ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL
 BE SPECIFIC AND THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THETERM "LEGAL" OR ITS
 RQUIVALENT BE USEDAS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 17)SHEET A101
 17A) THE DOORS LOCATED ON EACH SIDE OF THE DRIVE
 THROUGH (SF3 & SF10) DO NOT INDICATE ANY DETECTABLE
 WARNING ON THE SIDEWALK SURFACES.
 11-4.29.5 DETECTABLE WARNINGS AT HAZARDOUS VEHICULAR
 AREAS.
 IF A WALK CROSSES OR ADJOINS A VEHICULAR WAY, AND THE
 WALKING SURFACES ARE NOT SEPARATED BY CURBS, RAILINGS,
 OR OTHER ELEMENTS BETWEEN THE PEDESTRIAN AREAS AND
 VEHICULAR AREAS, THE BOUNDARY BETWEEN THE AREAS SHALL
 BE DEFINED BY A CONTINUOUS DETECTABLE WARNING WHICH IS
 36 INCHES (915 MM) WIDE, COMPLYING WITH SECTION
 11-4.29.2 .
  
 17B) THE GYM DOOR IS MISSING A IDENTIFICATION MARKER.
 ADDITIONAL INFORMATION REQUIRED.
 106.1.2.*
  
 17C) THE TRASH ROOM DOORIS INDICATE AS A ROLL UP DOOR
 PLEASE PROVIDE THE LISTING REPORT PROVIDING THE 1 ? HR
 FIRE RATING AS LISTED IN THE DOOR SCHEDULE.
  
 17D) THE SAUNA ROOM DOOR (6) IS IDENTIFIED WITH A 2?-8?
 DOOR, THIS WILL ONLY PROVIDE A 30?
 OPENING FAIR HOUSING WILL REQUIRE A MINIMUM OF 32?
 CLEAR WIDTH. ANSIA117.1- 404.2.3.
  
 17E) WHEN REFERRING TO THE STOREFRONT DOORS FOUND ON
 SHEET A-101 AND THE DOOR SCHEDULE ON A404, THE DOORS
 ARE NOT REFERENCED IN THE DOOR SCHEDULE? 106.1.2.
 ADDITIONAL INFORMATION REQUIRED.
  
 17F)DOORS SF 7A ARE HORIZONTAL SLIDING DOORS, PLEASE
 PROVIDE PRODUCT APPROVALS CONFORMING TO THE FOLLOWING:
  
 1008.1.3.3 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1. THE
 DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE OF
 BEING OPERATED MANUALLY IN THE EVENT OF POWER FAILURE.
 2.THE DOORS SHALL BE OPERABLE BY A SIMPLE METHOD
 FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3.
 THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPERABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE
 APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE
 DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 80 AND SHALL COMPLY WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED
 STANDBY POWER SUPPLY.
  
 SHEET A101 (17F)
  
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE
 ELECTRICALLY SUPERVISED.
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED
 WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE
 OPERATING DEVICE.
 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 18) SHEET A101A) REFLECTED CEILING PLAN:
 18A)SKYLIGHT DRIVE THROUGH PROVIDE PRODUCT APPROVAL
 FOR WIND AND PROVIDE WHAT TYPE OF SAFETY GLAZING WILL
 BE USED. 2405.2 ALLOWABLE GLAZING MATERIALS AND
 LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
 1.FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING
 MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE
 LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM)
 POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED
 GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE
 REQUIREMENTS OF SECTION 2607 , HEAT-STRENGTHENED GLASS
 OR FULLY TEMPERED GLASS.
 2.FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT
 OR LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3 .
 FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE
 SECTION 2610 . GLASS-BLOCK CONSTRUCTION SHALL CONFORM
 TO THE REQUIREMENTS OF SECTION 2101.2.5 .
  
 18B)LOBBY SKYLIGHT IS IN ACTUALITY AN ATRIUM PLEASE
 SEE ALL REQUIREMENTS IN 404 FOR : ATRIUM. AN OPENING
 CONNECTING TWO OR MORE STORIES OTHER THAN ENCLOSED
 STAIRWAYS, ELEVATORS, HOIST WAY, ESCALATORS, PLUMBING,
 ELECTRICAL, AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH
 IS CLOSED AT THE TOP AND NOT DEFINED AS A MALL.
 STORIES, AS USED IN THIS DEFINITION, DO NOT INCLUDE
 BALCONIES WITHIN ASSEMBLY GROUPS OR MEZZANINES THAT
 COMPLY WITH SECTION 505.
  
 404.2 USE.
 THE ATRIUM FLOOR AREA IS PERMITTED TO BE USED FOR LOW
 AND ORDINARY FIRE HAZARD USES WHERE THE INDIVIDUAL
 SPACE IS PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM
 IN ACCORDANCE WITH SECTION 903.3.1.1 .
  
 404.3 AUTOMATIC SPRINKLER PROTECTION.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED THROUGHOUT THE ENTIRE BUILDING.
  
 404.4 SMOKE CONTROL.
 A SMOKE CONTROL SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 909.
  
 404.5 ENCLOSURE OF ATRIUMS.
 ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES
 BY A 1-HOUR FIRE BARRIER WALL.
 EXCEPTIONS:
 1.A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A
 GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS
 WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER SYSTEM OPERATES.
 2.A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A ?-HOUR FIRE PROTECTION
 RATING.
 3.THE ADJACENT SPACES OF ANY THREE FLOORS OF THE
 ATRIUM SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE
 ATRIUM WHERE SUCH SPACES ARE INCLUDED IN COMPUTING THE
 ATRIUM VOLUME FOR THE DESIGN OF THE SMOKE CONTROL
 SYSTEM.
  
 404.6 STANDBY POWER.
 EQUIPMENT REQUIRED TO PROVIDE SMOKE CONTROL SHALL BE
 CONNECTED TO A STANDBY POWER SYSTEM IN ACCORDANCE WITH
 SECTION 909.11.
  
 404.7 INTERIOR FINISH.
 THE INTERIOR FINISH OF WALLS AND CEILINGS OF THE ATRIUM
 SHALL NOT BE LESS THAN CLASS B WITH NO REDUCTION IN
 CLASS FOR SPRINKLER PROTECTION.
  
 404.8 TRAVEL DISTANCE.
 IN OTHER THAN THE LOWEST LEVEL OF THE ATRIUM, WHERE THE
 REQUIRED MEANS OF EGRESS IS THROUGH THE ATRIUM SPACE,
 THE PORTION OF EXIT ACCESS TRAVEL DISTANCE WITHIN THE
 ATRIUM SPACE SHALL NOT EXCEED 200 FEET (60 960 MM).
  
 18C)PLANS IDENTIFY THE USE OF 5/8? WALLBOARD FOR USE
 IN CONSTRUCTING OF EXTERIOR SOFFIT IN GARAGE AREAS.
 2508.2
 GYPSUM WALLBOARD SHALL NOT BE USED WHERE THERE WILL BE
 DIRECT EXPOSURE TO WATER OR CONTINUOUS HIGH HUMIDITY
 CONDITIONS. GYPSUM SHEATHING SHALL BE INSTALLED ON
 EXTERIOR SURFACES IN ACCORDANCE WITH ASTM C 1280.
  
 18D) THE DESIGN OF THE PARKING AREA WITHIN THE TOWER IS
 S-2 ENCLOSED PARKING GARAGE,
 THE PLANS INDICATE ALL BLOCK WALLS AS 2HR WALLS, AS
 REQUIRED BY TABLE 302.3.2.
 18D) (1) PLEASE HAVE THE BLOCK MANUFACTURER PROVIDE THE
 EQUIVALENT THICKNESS OF ALL
 RATED BLOCK SEE TABLE 721.3.2.
 18D) (2) PLEASE INDICATE ON ALL THE STOREFRONT DOORS
 AND WINDOWS THE FIRE RATING; ALSO INDICATE ALL OPENINGS
 IN THE DOOR AND WINDOW SCHEDULE. TABLE 715.3.
  
 18E)DOOR # 12 IS MISSING A FIRE RATING FROM THE DOOR
 SCHEDULE. TABLE 715.3
  
 18F)PLANS QUOTE FIRE RATED CORRIDOR NOTE NFPA 101 BUT
 DO NOT MENTION THE MORE RESTRICTIVE OCCUPANCY
 SEPARATION BETWEEN THE ENCLOSED PARKING S-2 OCCUPANCY
 AND ADJACENT SPACES. THE MOST RESTRICTIVE CODE IS USED
 IN THIS CASE. 102.4*.
  
 19) SHEET A102
 19A)(1) SEE DETAIL B-3 SHEET A-402, THE SLIDING GLASS
 DOOR TRACK ASSEMBLY AS SHOWN DOES NOT MEET FAIR HOUSING
 GUIDELINES,FOR SECONDARY DOORS (SLIDING GLASS DOORS)
 THE GUIDELINE SPECIFY THAT THE THRESHOLDS AT THESE
 DOORS SHALL BE NO HIGHER THAN ? ?.THE GUIDELINES
 FURTHER STATE THAT CHANGES IN LEVEL AT THESE LOCATIONS
 MUST BE BEVELED WITH A SLOPE NO GREATER THAN 1:2.
 19A)(2) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE
 MAXIMUM ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING
 GLASS DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO
 WILL BE 4 INCHES TO THE FINISH DECK.
 NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK
 INTO THE DESIGN CRITERIA.
 19A)(3) THE STRUCTURAL PLANS WILL ALSO NEED TO
 CORRELATE THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS
 STATED ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS
 DOORS.
 19A)(4) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK
 IS TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS
 WILL REQUIRE MECHANICAL FASTENING OF TRACK.
  
 19B)THIS COMMENT WILL BE COMMON TO ALL FLOORS PLANS
 INDICATE A ? HR FIRE RATING PER NFPA 101 WHEREAS THE
 FBC TABLE 1016.1 FOR FIRE SPRINKLED BUILDINGS REQUIRES
 A 1 HR RATING. IF THERE IS A CONFLICT BETWEEN THE TWO
 CODES THE MOST RESTRICTIVE RULES. 1 HOUR FIRE RATED
 CORRIDORS WILL BE REQUIRED WITH 20MINUTE OPENING
 PROTECTIVE.
  
 19C) THERE ARE 3 DOORS THAT ARE NOT LABELED NOR SHOW UP
 ON THE DOOR SCHEDULE AS FOLLOWS:
 1) TRASH ROOM DOOR
 2) ANY DOOR THAT LEADS TO ANY INDIVIDUAL UNIT
 3) ELEVATOR LOBBY DOORS
  
 19D) PLANS FAIL TO IDENTIFY THE WALL TYPES THAT
 SURROUND THE REFUSE SHOOT.
 707.13.3 REFUSE AND LAUNDRY CHUTE ACCESS ROOMS. ACCESS
 OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE LOCATED
 IN ROOMS OR COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR AND OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN ? HOUR AND SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 19E)GLASS WALL (SF14) AT ATRIUM TO BE 1 HR RATED, SEE
 404.5 EXCEPTION# 1 BELOW:
 #1) A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A
 GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS
 WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER SYSTEM OPERATES.
  
 19F) STAIR TOWER 1 & 2 IN BOTH CASES THE DOORS SWING
 INTO THE STAIR LANDING MORE THAN 7? SEE 1009.1.4
 EXCEPTION 2. WHEN FULLY OPEN, THE DOOR SHALL NOT
 PROJECT MORE THAN 7 INCHES (178 MM) INTO A LANDING.
  
 19G)DOOR S1 IS INDICATED TO BE A 1 ? HR FIRE RATED
 DOOR WITH A 6? WIRE GLASS VIEW PANEL
 PLEASE PROVIDE WHAT TYPE FRAME THIS ASSEMBLY WILL BE
 SECURED TO?
  
  
 19H) PLANS INDICATE BETWEEN UNITS 2 SEPARATE WALLS ONE
 WITH SOUND PROOFING THE OTHER IS A TWO HR RATED WALL.
 PLEASE PROVIDE AN ASSEMBLY HOW THE TWO WALLS WILL BE
 BUILT?
  
 19I) PROVIDE COMPLIANCE WITH:1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 19J) PROVIDE COMPLIANCE WITH: 1207.3 STRUCTURE-BORNE
 SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20) SHEET A102A)
 20A) DETAIL D SHEET A 802 SHOULD BE INTO THE ATRIUM BUT
 IS INDICATED AS PRIVACY WALL AND PARAPET @ COVERED
 TERRACES, PLEASE CORRECT.
  
 21) SHEET A103A)
 21A)THIS SHEET INDICATES VARIOUS SOFFIT DETAILS
 PROVIDE ATTACHMENT INFORMATION, NOT SUSPENDED FROM THE
 DECK ABOVE. 106.1.2* ADD INFO.
  
 21B) THIS SHEET DETAILS THE THIRD STORY CEILINGS, JUST
 BEHIND THE 3 STORY ATRIUM THERE IS A DIMENSION OF 1?-0?
 IN DETAIL ?B? WHAT DOES THIS DIMENSION REFLECT?
 106.1.2* ADD INFO.
  
 21C) THIS SHEET REFLECTS THE CEILING MATERIAL SCHEDULE,
 APPARENTLY ONLY THE SERVICE ELEVATOR AND ELEVATOR# 1
 LOBBIES ARE GOING TO HAVE DROPPED DRYWALL CEILINGS,
 NONE IN ANY PART OF THIS FLOOR. IN THE UNITS MOST
 KITCHENS AND BATHROOMS ARE DROPPED FOR A/C DUCT WORK?
  
 22)SHEET A104:
 22A)INDICATES THE SKYLIGHT IS TO BE UNDER A SEPARATE
 PERMIT, THIS BUILDING IS DESIGNED AS AN ENCLOSED
 STRUCTURE, REQUIRING ALL PARTS OF THE ENVELOPE TO BE
 PERMITTED AS A SINGLE UNIT. THE SKYLIGHT PRODUCT
 APPROVAL INFORMATION WILL BE REQUIRED TO BE PART OF THE
 BASE BUILDING DATA SUBMITTED BEFORE A PERMIT WILL BE
 ISSUED.
  
 22B) ON THE SOUTH SIDE OF THE SKYLIGHT THERE IS A PAIR
 OF DOORS, NOT LABELED, NOT RATED?PLEASE PROVIDE WHAT
 PROPOSED USAGE THIS ROOM WILL BE USED FOR?
  
 22C)TO THE EAST & WEST SIDES OF THE SKYLIGHT THE
 PLANS INDICATE A ROOF DRAIN BUT IT DOESN?T APPEAR TO
 HAVE EMERGENCY OVERFLOW SYSTEM LOCATED ON THE EAST END
 OF THE SKYLIGHT? 1503.4.3WHEN OTHER MEANS OF DRAINAGE
 OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2
 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) ABOVE
 THE FINISHED ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 23) SHEET A106:
 23A) PLANS INDICATE SPIRAL STAIRS, PLEASE SUBMIT
 INFORMATION ON STAIRS: SEE 1009.9
 (1-3) SPIRAL STAIRWAYS.
  
 24) SHEET A107:
 24A) PLEASE PROVIDE ADDITIONAL INFORMATION ON WHAT
 APPEARS TO BE A WHIRLPOOL?
  
 24B) PLANS ALSO INDICATE A GRILL ON THE EXTERIOR OF
 EACH UNIT; PROVIDE MANUFACTURERS SPECS ON THESE UNITS.
 DO THESE UNITS ALSO NEED VENTS?
  
 24C) PLANS INDICATE AN ALUMINUM CATWALK SYSTEM TO BE
 COORDINATED WITH THE MECHANICAL EQUIPMENT, ADDITIONAL
 INFORMATION WILL BE NEEDED ON BOTH?
  
 24D) MACHINE ROOM# 3 THE PLANS MAY HAVE A TYPO, THERE
 ARE STAIRS INDICATED AND A DOOR DESIGNATION R-3 BUT NO
 DOOR, DOOR IS AROUND THE CORNER.106.1.2* ADD INFO
 REQUIRED.
  
 24E) IN THE CENTER OF THE BUILDING THE PLANS INDICATE
 VARIOUS ROOF DRAINS BUT NO SECONDARY
 OVERFLOW DRAINS.1503.4.3WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 24F) THE ELEVATOR MACHINE ROOM DOORS ARE LABELED (R1)
 DOORS WITH 45 MIN DOORS PLEASE CORRECT TO 1 ? HR RATED
 DOORS (SHAFTS)/ ELEVATOR MACHINE ROOMS.
  
 24G) PLANS INDICATE BETWEEN PENTHOUSE UNITS TERRACE A
 DOOR THIS WILL CROSS UNIT LINES REQUIRING A UNITY OF
 TITLE BETWEEN UNITS.
  
 24H) STAIRWELL# 1 INDICATES THAT A 6? DIA. FIRE RATED
 VIEW PANEL WILL BE IN THIS DOOR, WILL NEED TO BE TESTED
 FOR WIND PRESSURES ALSO.
  
  
 25) SHEET A108:
 25A)PLANS INDICATE ON PENTHOUSE B AND THE REVERSE
 PENTHOUSE BTHE ROOF SCUPPERS ARE DIRECTLY OVER THE
 DOORWAY!!!!!
  
 25B) ALL ROOF SCUPPERS ARE INSTALLED LEVEL WITH THE
 ROOF DECK, PLANS DO NOT INDICATE ANY EMERGENCY OVERFLOW
 SCUPPERS. 1503.4.3WHEN OTHER MEANS OF DRAINAGE OF
 OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS SHALL
 BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES
 (51 MM) NOR MORE THAN 4 INCHES (102 MM) ABOVE THE
 FINISHED ROOF COVERING AND SHALL BE LOCATED AS CLOSE AS
 PRACTICAL TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR
 WALL AND PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE
 SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 PLUMBING.
  
 26) SHEET A201: NOTES 26A-26C COMMON TO ALL 200 SERIES
 SHEETS.
 26A) GENERAL NOTE# 9 INDICATES APPROVAL FROM THE
 ARCHITECT AND BUILDING DEPARTMENT. PLEASE CORRECT THE
 DESIGNER OF RECORD APPROVES, THE CITY REVIEWS FOR CODE
 COMPLIANCE ONLY!!
  
 26B) FINISH NOTES COMMENT ONLY ON NFPA 101, THE 2006
 FBC803.1/ TABLE 803.5 ARE THE CODE SECTIONS THE
 BUILDING DEPARTMENT WILL REVIEW TOO.
  
 26C) EGRESS WINDOWS THE MINIMUM HEIGHT IS 24? NOT 22?
 AND THE MINIMUM OPEN VENT SIZE IS 5.7? SECOND FLORR AND
 5.0? FIRST FLOOR NOT 4.)?. SEE FBC 1025.2 BUILDING.
  
 26D) UNIT DOOR SCHEDULE INDICATES WOOD DOORS (8-9) BOTH
 INDICATE WOOD DOORS AND FRAMES FIRE RATED 60 MINUTE
 DOORS. PLEASE PROVIDE APPROVAL REPORTS FOR 1 HR FIRE
 RATING.
  
 27) SHEET A201:
 27A) PLANS INDICATE 3?-0? ENTRY BETWEEN CABINET ENTRY
 INTO THE KITCHEN, PLEASE SEE A700.
 THE TITLE INDICATES PALM BEACH COUNTY ACCESSIBILITY
 CODE PLEASE CORRECT TO THE 2004
 /2006 FBC CHAPTER 11 PARTB FAIR HOUSING ACCESSIBILITY
 GUIDELINES.
 SEE NOTE# 5 INDICATES A MINIMUM OF 40? FOR KITCHENS NOT
 THE 3?-0? DIMENSIONED IN THE PLAN. USABLE KITCHENS
 (1)(B)
  
 27B) PLANS DO NOT INDICATE THE SIZE OF THE SHOWER
 DOOR?
  
  
 27C) IMPORTANT NOTE!!!!! PLANS DO NOT INDICATE
 INFORMATION AS TO EXTERIOR SLIDERS,SEE COMMENT
 19A)(1-3), AGAIN IT IS CRITICAL THAT THE SLIDING DOOR
 TRACK BE RECESSED ENOUGH TO ALLOW NO MORE THAN ?? ABOVE
 FINISH FLOOR AND FROM THE INTERIOR FINISH FLOOR TO THE
 TOP OF THE BALCONY DECK NO MORE THAN A 4? DROP. THIS IS
 TYPICAL OF ALL EXTERIOR SLIDING GLASS DOOR UNITS!!!!
 LEGEND-CURBS TYPICAL FOR ALL UNITS, THIS COMMENT WILL
 NOT BE RESTATED!!!!!!!!!!!!!!!!
  
 28) SHEET A203:
 28A) THE PRIMARY ENTRANCE DOORS ARE A PAIR OF 30?
 DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN DOOR IS 32?
 WHEN OPEN 90DEGREES TO THE OPENING. ANSI 4.13./
 1008.1.1.
  
 28B) USABLE DOOR #14 DOES NOT MEET THE GUIDELINES, THE
 BIFOLD DOOR IS LISTED AS 1 ??
 OR 3 ?? SUBTRACTED FROM 2?-10? LEAVES A 2?-61/2?
 OPENING. THE MINIMUM CLEAR OPENING IS 2?-8? FOR USABLE
 DOORS.
  
 29) SHEET A205:
 29A) THE PRIMARY ENTRY DOOR #8 WOULD REQUIRE A CLEAR
 32? THIS WILL NOT BE POSSIBLE WITH A 30? DOOR.
 1008.1.1.
  
 30) SHEET A207: DOOR # 7 IS INDICATED AS A TYPE ?D?
 POCKET WHERE IT IS SHOWN AS A SWING DOOR.
  
 31) SHEET A209) DOOR 3 & 4 BOTH ARE BI-FOLD DOORS
 2?-10? BIFOLD ? 31/2? = 2?-61/2? THIS DOES NOT MEET THE
 32? FOR USABLE DOORS.
  
 32) SHEET A212:
 32A) ENTRY DOOR# 10, ) THE PRIMARY ENTRANCE DOORS ARE A
 PAIR OF 30? DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN
 DOOR IS 32? WHEN OPEN 90DEGREES TO THE OPENING. ANSI
 4.13./ 1008.1.1.
  
 32B)KITCHEN MISSING THE DIMENSION BETWEEN CABINETS.
 MINIMUM 40? CLEAR.
  
 32C) BIFOLD DOORS ARE BI-FOLD DOORS 2?-10? BIFOLD ?
 31/2? = 2?-61/2? THIS DOES NOT MEET THE 32? FOR USABLE
 DOORS.
  
 33) SHEET A215:
 33A)DOOR # 8 ) THE PRIMARY ENTRANCE DOORS ARE A PAIR
 OF 30? DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN DOOR
 IS 32? WHEN OPEN 90DEGREES TO THE OPENING. ANSI 4.13./
 1008.1.1.
  
 33B) DOOR# 17 IS A 2?-8? DOOR IS REQUIRED TO BE 32? AS
 BEING A USABLE DOOR AND IN CLOSETS DEEPER THAN 2?-0?.
  
 34) SHEET A402 HAS VARIOUS DETAILS INDICATING THE USE
 OF STEEL TO CREATE STRUCTURAL MULLIONS.1707.4.5.1
 MULLIONS OCCURRING BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE REQUIRED BY AN
 APPROVED TESTING LABORATORY OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE
 DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 35) SHEET A-501 INDICATES IN DETAIL# 2 A 3? GAP BETWEEN
 THE HANDRAIL AND WALL. FAIR HOUSING ANSI A117.1, 505.5
 CLEARANCE BETWEEN THE CLEAR SPACE BETWEEN THE WALL AND
 THE HANDRAIL SHALL BE 1 ??.
  
 36) SHEET A-503:
 36A) PLANS DO NOT PROVIDE COMPLIANCE FOR THE ELEVATOR
 CARS TO ACCOMMODATE AMBULANCE STRETCHER REQUIREMENTS
 3002.4.
  
 36B) PLEASE NOTE SIGNAGE REQUIREMENT: 3002.3 EMERGENCY
 SIGNS.
 AN APPROVED PICTORIAL SIGN OF A STANDARDIZED DESIGN
 SHALL BE POSTED ADJACENT TO EACH ELEVATOR CALL STATION
 ON ALL FLOORS INSTRUCTING OCCUPANTS TO USE THE EXIT
 STAIRWAYS AND NOT TO USE THE ELEVATORS IN CASE OF FIRE.
 THE SIGN SHALL READ: IN FIRE EMERGENCY, DO NOT USE
 ELEVATOR. USE EXIT STAIRS. THE EMERGENCY SIGN SHALL NOT
 BE REQUIRED FOR ELEVATORS THAT ARE PART OF AN
 ACCESSIBLE MEANS OF EGRESS COMPLYING WITH SECTION 1007
 .
  
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR OR FLOORS AT THE
 TOP OF THE HOISTWAY, AND SHALL OPEN EITHER DIRECTLY TO
 THE OUTER AIR OR THROUGH NONCOMBUSTIBLE DUCTS TO THE
 OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO
 PASS THROUGH THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR
 MACHINE ROOM ARE
  
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE FIRE
 PROTECTION RATING REQUIRED FOR THE HOISTWAY. HOLES IN
 THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED SO AS NOT TO PROVIDE GREATER THAN 2 INCHES (51
 MM) OF CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION 3004.3.1 , THE AREA
 OF THE VENTS SHALL NOT BE LESS THAN 3? PERCENT OF THE
 AREA OF THE HOISTWAY NOR LESS THAN 3 SQUARE FEET (0.28
 M 2 ) FOR EACH ELEVATOR CAR, AND NOT LESS THAN 3?
 PERCENT NOR LESS THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY, WHICHEVER IS
 GREATER. OF THE TOTAL REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY OPEN TYPE UNLESS
 ALL VENTS ACTIVATE UPON DETECTION OF SMOKE FROM ANY OF
 THE ELEVATOR LOBBY SMOKE DETECTORS.
  
 37) SHEET A600 AND ALL 600 SHEETS:
 37A) FIRE RATING LEGEND WALLS, PLEASE SEE TABLE 601 FOR
 FIRE RATINGS OF STRUCTURAL MEMBERS AND NON RATED
 WALLS.
  
 38)SHEET A700:
 38A) PLANS INDICATE PALM BEACH COUNTY ACCESSIBILITY
 PLEASE CORRECT TO 2004/2006 FLORIDA BUILDING CODE
 CHAPTER 11 FLORIDA ACCESSIBILITY CODE.
  
 38B) NOTE 16 -01 IS ILLEGIBLE DOUBLE TYPED.
  
 38C) NOTE 16-04 PLEASE SEE FAIR HOUSING ACCESSIBILITY
 GUIDELINES UNDER PURPOSE:
 THE DESIGN TEAM IS RESPONSIBLE FOR FAIR HOUSING .!!!
 PURPOSE: THE PURPOSE OF THESE GUIDELINES IS TO PROVIDE
 TECHNICAL GUIDANCE ON DESIGNING DWELLING UNITS AS
 REQUIRED BY THE FAIR HOUSING AMENDMENTS ACT OF 1988
 (FAIR HOUSING ACT). THESE GUIDELINES ARE NOT MANDATORY,
 NOR DO THEY PRESCRIBE SPECIFIC REQUIREMENTS WHICH MUST
 BE MET, AND WHICH, IF NOT MET, WOULD CONSTITUTE
 UNLAWFUL DISCRIMINATION UNDER THE FAIR HOUSING ACT.
 BUILDERS AND DEVELOPERS MAY CHOOSE TO DEPART FROM THESE
 GUIDELINES AND SEEK ALTERNATE WAYS TO DEMONSTRATE THAT
 THEY HAVE MET THE REQUIREMENTS OF THE FAIR HOUSING ACT.
 THESE GUIDELINES ARE INTENDED TO PROVIDE A SAFE HARBOR
 FOR COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF
 THE FAIR HOUSING ACT.
  
 39) SHEET A802 DETAIL ?G? IS DOESN?T INDICATE HOW THIS
 SUPPORT IS TO BE TIED DOWN TO THE ROOF DECK PLEASE
 PROVIDE A CONTINUOUS PATH OF RESISTANCE.
  
 40) SHEET A803 PLEASE PROVIDE RATING BETWEEN THE
 ASSEMBLY OCCUPANCY AND THE S-2 OCCUPANCY BELOW.
  
 41) SHEET A804:
 41A)DETAIL H PLANS INDICATE A POOL COPING DETAIL,
 WHEREAS IT IS ACTUALLY AN EXHAUST FAN DETAIL, PLEASE
 CORRECT.
  
 41B) PLANS ALSO DO NOT INDICATE ANY STRAPPING IN THIS
 DETAIL SECURING THE CURB TO THE ROOF DECK?
  
 41C) PLANS MAKEREFERENCE TO THE SFBC, CORRECT
  
 42) SHEET S703 CORRECT THE REFERENCED STANDARDS :
 REINFORCED MASONRY NOTES
 42A) ACI 530.1-99
 42B) ASCE 5-99
 42C) ASCE 6-99
 42D) TMS 402-99
  
 SHEARWALL NOTES
 42E) ACI 318-99
 42F) ACI 318R-92
  
 42G)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 43 ) S-103 PLANS INDICATE THERE WILL BE PILING BUT NO
 INFORMATION HAS BEEN SUBMITTED
 THAT THIS WILL BE PART OF THIS PERMIT. PLEASE PROVIDE
 WHAT TYPE OF PILING, DIAMETER,
 LENGTH OF PILE, REINFORCING REQUIREMENTS, ETC.
  
 44) S-901 IT APPEARS THAT RWDI HAS COMPLETED A WIND
 TUNNEL TEST. PLEASE SUBMIT 3 ORIGINAL SIGNED& SEAL
 REPORTS .
  
 45) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED GLASS
 B) STOREFRONT GLASS
 C) OPERABLE WINDOWS
 D) MULLIONS HORIZONTAL & VERTICAL
 E) SKYLIGHTS
 F) GLASS BLOCK
 G) LOUVERS
 H) HOLLOW METAL DOORS/ ROOF HATCHES
 I) GLASS DOORS SWING
 J) OVERHEAD DOORS/ COIL DOORS
 K) SLIDING GLASS DOORS
 L) AUTOMATIC HORIZONTAL SLIDING DOORS
 M)PANEL WALL SYSTEM: SOFFITS, EFIS
 N) ROOFING ASSEMBLIES
  
 AT THIS TIME NO APPROVALS (GLAZING) CAN BE REVIEWED!
 FOR EXAMPLE FOR STOREFRONT PGT NOA 03-0508.03 WAS
 SUBMITTED FOR LARGE AND SMALL MISSILE TESTING.
 THE FIRST ISSUE IS FOR THE LARGE MISSILE
 TEST NO ONE HAS INDICATED WHICH FASTENER TYPE WAS TO BE
 USED, SECOND WHICH STYLE LAMINATED GLAZING WAS TO BE
 INSTALLED. PLEASE HIGHLIGHT OR INDICATE THE DESIGN
 TEAM?S CHOICE.
 THE NEXT ISSUE WITH THIS PRODUCT APPROVAL
 IS THE LIMITATION ON THE HEIGHT AND WIDTH OR MAXIMUM
 DAYLIGHT OPENING ALLOWED BY THE NOA, SEE SHEET A400 &
 A401.
  
 THE NEXT ISSUE IS WITHIN THE NOA ITSELF,
 THIS PGTNOA INDICATES THAT IT IS TO BE USED FOR LARGE
 AND SMALL MISSILE IMPACT WINDOW BUT THERE IS NO
 LITERATURE FOR SMALL MISSILE IMPACT RATING INDICATED IN
 THE PRODUCT APPROVAL?
 THIS COMMENT WILL STAND FOR ALL PRODUCT
 APPROVALS IN REGARDS TO THE WIND STUDY. SINCE THERE ARE
 NUMEROUS WIND PRESSURE ZONES FOR THIS BUILDING THE
 DESIGN TEAM WILL NEED TO PROVIDE SOME MEANS OF
 IDENTIFYING WHICH PRODUCT APPROVALS WILL TIE TO THERE
 ASSOCIATED GLAZING UNIT FOR BOTH LARGE AND SMALL
 MISSILE UNITS.
  
 THIS NEXT ISSUE WILL DEAL WITH THE WIND
 REPORT SUBMITTED FROM RWDI AND THE REQUIREMENTS OF
 ASCE7-02 SECTION 6.6 METHOD 3 WIND TUNNEL TEST. UNDER
 THE HEADING OF LIMITATIONS SEE ANALYSIS FOR WIND SPEEDS
 CONFORMS TO THE REQUIREMENTS OF SECTION 6.5.4.2.
 6.5.4.2 ESTIMATION OF BASIC WIND SPEEDS FROM
 REGIONAL CLIMATIC DATA
 (2) THE DESIGN WIND SPEEDS RESULTING FROM THE STUDY
 SHALL NOT BE LESS THAN THE RESULTING
 500-YEAR RETURN PERIOD WIND SPEED DIVIDED BY SQUARE
 ROOT OF 1.5.
 THE SQUARE ROOT OF 1.5 IS 1.22. 500 DIVIDED
 BY 1.22= 154 WIND SPEED. THE RESULTING STUDY SHOULD
 HAVE BEEN COMPOSED USING 154 MPH NOT THE 145 MPH 3
 SECOND GUST.
  
 ANOTHER ISSUE WITH THE WIND STUDY PLEASE
 COMMENT ON WHY ON A SYMMETRIC BUILDING SEE FIGURE# 6
 THE WEST ELEVATION THE PRESSURES ARE SYMMETRIC BUT ON
 THE EAST SIDE OF THE BUILDING WHICH IS ALSO SYMMETRIC
 WHY THERE IS A DIFFERENCE IN CONFIGURATION IN PRESSURE
 ZONES 75/ 85 FROM THE CENTERED 65 PSF? I WOULD BELIEVE
 THE WIND WOULD BE EFFECTED THE SAME AMOUNT ON A
 SYMMETRIC BUILDING. THE SAME CONCEPT I WOULD BELIEVE
 HOLD TRUE ON THE NORTH AND SOUTH SIDES?
  
 THE SAME ISSUE WITH THE SLIDING GLASS DOOR NOA
 SUBMITTED. THE TYPE OF GLAZING
 (LAMINATION) WAS NOTHIGHLIGHTED . PROVIDE A DETAILED
 ACCOUNT WHERE EACH OF THESE TYPE UNITS ARE TO LOCATED
 ON THE BUILDING.
  
 MULLIONS:1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS DOOR ASSEMBLIES. TESTING
 REPORTS ARE REQUIRED BY AN APPROVED TESTING LABORATORY
 OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE
 DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 _X__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 _2&3__ .
 SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM
 HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED._X__ THE
 SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD THE
 FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTEREDPROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT
 MAY BE SUBMITTED.
 _X__THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCEDFASTENING ALLOWED.
  
  
 46)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 47) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 48) PLANS ARE TO SHOWCOMPLIANCE WITH:
 403.8 FIRE COMMAND .
 A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL
 BE PROVIDED IN A LOCATION APPROVED BY THE FIRE
 DEPARTMENT.
  
 403.9 ELEVATORS.
 ELEVATOR OPERATION AND INSTALLATION SHALL BE IN
 ACCORDANCE WITH CHAPTER 30 .
  
 403.10 STANDBY POWER.
 A STANDBY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN
 SECTION 403.10.2 .
  
 403.10.1 SPECIAL REQUIREMENTS FOR STANDBY POWER
 SYSTEMS.
 IF THE STANDBY SYSTEM IS A GENERATOR SET INSIDE A
 BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE
 ROOM ENCLOSED WITH 2-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIER ASSEMBLIES. SYSTEM SUPERVISION WITH MANUAL
 START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE
 FIRE COMMAND CENTER.
  
 403.10.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 1.
 POWER AND LIGHTING FOR THE FIRE COMMAND CENTER REQUIRED
 BY SECTION 403.8 ;
 2.ELECTRICALLY POWERED FIRE PUMPS;
 3.VENTILATION AND AUTOMATIC FIRE DETECTION
 EQUIPMENT FOR SMOKEPROOF ENCLOSURES.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTION 3003 .
  
 403.11 EMERGENCY POWER SYSTEMS.
 AN EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED
 IN SECTION 403.11.1 .
  
 403.11.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
  
 1.EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION
 REQUIRED BY CHAPTER 10 ;
 2.ELEVATOR CAR LIGHTING;
 3.EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; 4.
 AUTOMATIC FIRE DETECTION SYSTEMS; AND
 5.FIRE ALARM SYSTEMS.
  
 403.12 STAIRWAY DOOR OPERATION.
 STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS
 SHALL BE PERMITTED TO BE LOCKED FROM
 STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED FROM THE
 STAIRWAY SIDE SHALL BE CAPABLE OF BEING UNLOCKED
 SIMULTANEOUSLY WITHOUT UNLATCHING UPON A SIGNAL FROM
 THE FIRE COMMAND CENTER.
  
 403.12.1 STAIRWAY COMMUNICATIONS SYSTEM.
 A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH REQUIRED STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 403.13 SMOKEPROOF EXIT ENCLOSURES.
 EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS
 909.20 AND 1019.1.8 .
  
 403.14 RESERVED.
  
 403.15 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 909.
  
 49)SHEET AC-01 THE VALET OFFICE INDICATES A THROUGH
 THE WALL A/C UNIT, IS THIS GOING TO DRAW FRESH AIR FROM
 THE ENCLOSED PARKING GARAGE?
  
 50)PROVIDE INFORMATION ON THE VENTILATION OF THE
 ENCLOSED PARKING GARAGE. 406.4.2 VENTILATION. A
 MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL
 .
  
  
 51)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 THIS REVIEW IS MAY HAVE ADDITIONAL COMMENTS AS A RESULT
 OF THE DESIGNERS ANSWERS TO THE PLAN REVIEW OR NEW
 INFORMATION BEING ADDED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 FLAGLER BEACH CLUB TOWER 1ST REVIEW.DOC
  
  