Plan Review Notes
Plan Review Notes For Permit 07030453
Permit Number 07030453
Review Stop P
Sequence Number 1
Notes
Date Text
2007-05-10 09:08:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE FIRM PHONE NUMBER IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. FAC 61G1-19.004(1) & FS
 481.2055.
  
 2. THE APPLICATION INDICATES THE REMODEL OF THE
 EXISTING BAYS. PLEASE SUBMIT AN EXISTING FLOOR PLAN,
 PRIOR TO REMODEL,FOR THE BAYS TO DETERMINE THE EXTENT
 OF THE REMODEL.PLEASE INDICATE ONE OR A COMBINATION
 OF LEVELS OF ALTERNATION OF THE EXISTING BAYS PER
 SECTIONS 303, 304 OR 305 OF THE EXISTING BLDG CODE.
 SECTION 301.5.
  
 3. PLEASE INDICATE THE OCCUPANCY AND USE OF THE
 EXISTING BAYS. SECTION 301.4.
  
 4. SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. IN THE CALCULATIONS SHOW THE SQUARE
 FOOTAGE OF THE ROOF, THE SQUARE FOOTAGE DRAINED BY EACH
 DRAIN. SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ALONG WITH THE ROOF AREA OF ANY ROOF THAT
 DRAINS ONTO THE ROOF FROM ABOVE.--SHOW THE LOCATION
 OF ALL ROOF DRAINS, PRIMARY & SECONDARY. SHOW ALL PIPE
 SIZES FOR THE EXISTING ROOF DRAINS. IF SCUPPERS ARE
 USED SHOW THE SIZE OF EACH SCUPPER, HEIGHT, WIDTH &
 TOTAL SQUARE INCHES. INDICATE THE HEIGHT OFF THE ROOF
 TO THE FLOW LINE AS REQUIRED IN SECTION 1503.4.2 IF
 OVERFLOW SCUPPERS ARE USED.
  
 5. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES
 AND A SERVICE SINK IS REQUIRED IN SOME OCCUPANCIES.
 WHEN THE OCCUPANCY OF THE EXISTING BAYS IS ESTABLISHED,
 THE REQUIRED FIXTURES SHALL BE SHOWN WITH A NEW
 SANITARY RISER DIAGRAM AND WATER RISER DIAGRAM
 INDICATING ALL PIPE SIZES TRAPS, VENTS, VALVES ETC. FOR
 THE NEW FIXTURES. TABLE 403.1 & SECTION 106.3.5.1.3.
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS 11-4.11.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 7. SHT 3 THE NEW BLDG FLOOR PLAN. MENS AND WOMENS
 TOILET ROOMS SHALL BE ACCESSIBLE. PLEASE SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. SHOW THE W/C
 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE PER
 FIG. 11-29. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE. SECTION 11-4.22.2(1).
  
 8. SHT 3 THE BATHROOM SHALL BE ACCESSIBLE OR ADAPTABLE.
 SHOW COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19, 11-4.21
 & 11-4.22 WITH ALL SUBSECTIONS IF BATHROOM WILL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH BACKING FOR FUTURE
 GRAB BARS FOR THE SHOWER & W/C, A TURNING AREA PER
 SECTION 11-4.2.3,SPACING FOR THE W/C BETWEEN THE
 SHOWER AND THE LAV, 18" OFF ONE FIXTURE AND A MINIMUM
 15" OFF THE OTHER FIXTURE, FOR A MINIMUM 33" OPENING,
 AND REQUIREMENTS FOR THE SHOWER PER 11-4.21 WITH
 RESPECT TO THE SHOWER VALVE, SEAT, & CURB IF THE
 BATHROOM WILL BE ADAPTABLE. SECTION 11-4.1.3(11).
  
 9. SHT 3 THE BREAKROOM SINK SHALL BE ACCESSIBLE. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. A TRUNING AREA COMPLYING WITH SECTION
 11-4.2.3 IS REQUIRED IN THE BREAK ROOM.
  
 10. SHT 4 THE PLUMBING RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS. THE
 SHOWER IS MISSING, AND THE BREAK ROOM SINK SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM FIXTURES. SECTIONS
 106.1.1 AND 909.1.--PLEASE PROVIDE A PLAN VIEW OF
 THE HORIZONTAL SANITARY PIPING AND SUBMIT A ISOMETRIC
 RISER DIAGRAM TO REFLECT THE PIPING LAYOUT ON THE
 HORIZONTAL PLAN VIEW. (SEE RED LINE EXAMPLES ON SHEETS
 3 & 4).
  
 11. SUBMIT A WATER RISER DIAGRAM TO REFLECT THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, VALVES ETC. SECTION
 106.3.5.1.3(3)(10)(13).
  
 12. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE BUILDING. INDICATE IF THERE IS AN EXISTING
 BACKFLOW AND SHOW THE SIZE OF THE WATER SERVICE PIPE
 PER TABLE 603.1. THIS CAN BE INDICATED ON THE WATER
 RISER DIAGRAM.
  
 13. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. PLEASE INDICATE METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved