Date |
Text |
2007-05-10 09:08:50 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 EXISTING BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ALL SHEETS. THE FIRM PHONE NUMBER IS REQUIRED IN THE |
| TITLE BLOCK OF EACH SHEET. FAC 61G1-19.004(1) & FS |
| 481.2055. |
| |
| 2. THE APPLICATION INDICATES THE REMODEL OF THE |
| EXISTING BAYS. PLEASE SUBMIT AN EXISTING FLOOR PLAN, |
| PRIOR TO REMODEL,FOR THE BAYS TO DETERMINE THE EXTENT |
| OF THE REMODEL.PLEASE INDICATE ONE OR A COMBINATION |
| OF LEVELS OF ALTERNATION OF THE EXISTING BAYS PER |
| SECTIONS 303, 304 OR 305 OF THE EXISTING BLDG CODE. |
| SECTION 301.5. |
| |
| 3. PLEASE INDICATE THE OCCUPANCY AND USE OF THE |
| EXISTING BAYS. SECTION 301.4. |
| |
| 4. SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY |
| ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| SUBSECTIONS. IN THE CALCULATIONS SHOW THE SQUARE |
| FOOTAGE OF THE ROOF, THE SQUARE FOOTAGE DRAINED BY EACH |
| DRAIN. SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| PARAPETS ALONG WITH THE ROOF AREA OF ANY ROOF THAT |
| DRAINS ONTO THE ROOF FROM ABOVE.--SHOW THE LOCATION |
| OF ALL ROOF DRAINS, PRIMARY & SECONDARY. SHOW ALL PIPE |
| SIZES FOR THE EXISTING ROOF DRAINS. IF SCUPPERS ARE |
| USED SHOW THE SIZE OF EACH SCUPPER, HEIGHT, WIDTH & |
| TOTAL SQUARE INCHES. INDICATE THE HEIGHT OFF THE ROOF |
| TO THE FLOW LINE AS REQUIRED IN SECTION 1503.4.2 IF |
| OVERFLOW SCUPPERS ARE USED. |
| |
| 5. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES |
| AND A SERVICE SINK IS REQUIRED IN SOME OCCUPANCIES. |
| WHEN THE OCCUPANCY OF THE EXISTING BAYS IS ESTABLISHED, |
| THE REQUIRED FIXTURES SHALL BE SHOWN WITH A NEW |
| SANITARY RISER DIAGRAM AND WATER RISER DIAGRAM |
| INDICATING ALL PIPE SIZES TRAPS, VENTS, VALVES ETC. FOR |
| THE NEW FIXTURES. TABLE 403.1 & SECTION 106.3.5.1.3. |
| |
| 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| WELL AS 11-4.11.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING. |
| |
| 7. SHT 3 THE NEW BLDG FLOOR PLAN. MENS AND WOMENS |
| TOILET ROOMS SHALL BE ACCESSIBLE. PLEASE SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16, |
| 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. SHOW THE W/C |
| 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE PER |
| FIG. 11-29. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| SPACE REQUIRED FOR ANY FIXTURE. SECTION 11-4.22.2(1). |
| |
| 8. SHT 3 THE BATHROOM SHALL BE ACCESSIBLE OR ADAPTABLE. |
| SHOW COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19, 11-4.21 |
| & 11-4.22 WITH ALL SUBSECTIONS IF BATHROOM WILL BE |
| ACCESSIBLE. SHOW COMPLIANCE WITH BACKING FOR FUTURE |
| GRAB BARS FOR THE SHOWER & W/C, A TURNING AREA PER |
| SECTION 11-4.2.3,SPACING FOR THE W/C BETWEEN THE |
| SHOWER AND THE LAV, 18" OFF ONE FIXTURE AND A MINIMUM |
| 15" OFF THE OTHER FIXTURE, FOR A MINIMUM 33" OPENING, |
| AND REQUIREMENTS FOR THE SHOWER PER 11-4.21 WITH |
| RESPECT TO THE SHOWER VALVE, SEAT, & CURB IF THE |
| BATHROOM WILL BE ADAPTABLE. SECTION 11-4.1.3(11). |
| |
| 9. SHT 3 THE BREAKROOM SINK SHALL BE ACCESSIBLE. SUBMIT |
| A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND |
| ALL SUBSECTIONS. A TRUNING AREA COMPLYING WITH SECTION |
| 11-4.2.3 IS REQUIRED IN THE BREAK ROOM. |
| |
| 10. SHT 4 THE PLUMBING RISER DIAGRAM DOES NOT REFLECT |
| THE FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS. THE |
| SHOWER IS MISSING, AND THE BREAK ROOM SINK SHALL |
| DISCHARGE DOWNSTREAM OF THE BATHROOM FIXTURES. SECTIONS |
| 106.1.1 AND 909.1.--PLEASE PROVIDE A PLAN VIEW OF |
| THE HORIZONTAL SANITARY PIPING AND SUBMIT A ISOMETRIC |
| RISER DIAGRAM TO REFLECT THE PIPING LAYOUT ON THE |
| HORIZONTAL PLAN VIEW. (SEE RED LINE EXAMPLES ON SHEETS |
| 3 & 4). |
| |
| 11. SUBMIT A WATER RISER DIAGRAM TO REFLECT THE FLOOR |
| PLAN. SHOW ALL PIPE SIZES, VALVES ETC. SECTION |
| 106.3.5.1.3(3)(10)(13). |
| |
| 12. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| TO THE BUILDING. INDICATE IF THERE IS AN EXISTING |
| BACKFLOW AND SHOW THE SIZE OF THE WATER SERVICE PIPE |
| PER TABLE 603.1. THIS CAN BE INDICATED ON THE WATER |
| RISER DIAGRAM. |
| |
| 13. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION |
| 607.3.2. PLEASE INDICATE METHOD. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |