2007-04-15 09:04:46 | ** UNSAT ** |
| |
| ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO |
| CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE |
| CITY OF WEST PALM BEACH. |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLANS AT THIS TIME DO NOT INDICATE ANY CODES. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SUBMIT COMPLETED PLANS FOR COMMERCIAL OFFICE |
| BUILDING APPLICATION. AT THIS TIME THERE ARE MANY ITEMS |
| ON PLANS WHICH ARE UNDER RESIDENTIAL DESIGN. |
| |
| 2) NOTE: PLEASE SUBMIT COMPLETE PLANS WHICH ARE CLEAR |
| AND VISIBLE FOR ALL ELECTRICAL CIRCUITS, DESIGNATIONS |
| ETC ON PLANS. PLEASE SEE FBC 106.1.3 WHICH REQUIRES |
| PLANS TO BE A MINIMUM OF QUALITY. |
| THERE ARE SEVERAL ITEMS, CIRCUITS ON PLANS WHICH ARE |
| NOT CLEAR. |
| PLEASE SEE THERE ARE SOME CIRCUITS WHICH ARE INDICATED |
| WHICH ARE NOT ON PANEL SCHEDULE. |
| PLEASE SEE 408.4 OF THE NEC, AND THE FOLLOWING TEXT |
| BELOW WHICH IS TAKEN DIRECTLY FROM THE NEC. |
| PLEASE KNOW THAT THE PLANS NEED TO LABEL AND PROVIDE |
| ROOM AND AREA DESIGNATIONS ON PLANS AND CORRELATE WITH |
| THE PANEL SCHEDULES SHOWING ALL ROOMS AND AREAS IN |
| WHICH CIRCUITS FEED WILL BE REQUIRED FOR EACH PANEL. |
| PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE |
| CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| ACCEPTABLE. |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 3) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL |
| LOAD CALCULATIONS. |
| PLEASE SEE 220.12, 220.14, 220.42, 220.44, 215.5, |
| 230.42 ETC. |
| PLEASE SEE THERE ARE CIRCUITS WHICH ARE OVER LOADED. |
| PLEASE SEE NO LOADS ARE SHOWN FOR COMMERCIAL |
| APPLICATION. |
| |
| 4) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH |
| THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. PLEASE |
| SEE 13-413.1ABC.1, 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE 13-415.1.AB.1.1, 13-415.2. |
| NO FIXTURE LEGEND WAS SUBMITTED, NO ENERGY |
| CALCULATIONS, NO PERFORMANCE CALCULATIONS, ETC |
| AS PLANS DO NOT INDICATED ANY ELECTRICAL FOR EXISTING |
| STRUCTURE, SOME OTHER ITEMS FOR CODE COMPLIANCE WITH |
| RESPECT TO CHAPTER 13 CAN NOT BE DETERMINED AT THIS |
| TIME. |
| |
| 5) NOTE: PLEASE SEE PLANS INDICATE THIS AS AN ADDITION |
| TO AN EXISTING STRUCTURE, HOWEVER HOW IS THIS EXISTING |
| BEING FED FROM THE NEW ELECTRICAL SERVICE AS SHOWN. |
| PLANS DO NOT SHOW CIRCUITING , FEEDS, OR INDICATE ANY |
| ELECTRICAL FOR REVIEW. |
| NO REVIEW FOR THIS CAN BE DONE AT THIS TIME. |
| PLEASE SEE NEC 2005. |
| FBC 106.1.2, 106.3.5.1.2 |
| COMPLETE PLANS. |
| |
| 6) NOTE: PLEASE SEE 422.13 FOR LOADS FOR WATER HEATER. |
| |
| 7) NOTE: PLEASE SEE BATH ROOMS WHICH ONLY INDICATE TWO |
| FANS, NO CONTROL FOR THESE FANS AND NO LIGHTING IN |
| THESE TWO BATH ROOMS?? |
| PLEASE COMPLETE PLANS. |
| FBC 106.3.5.1.2 |
| LS 101 7.8 |
| |
| 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE |
| EQUIPMENT PER 110.9. |
| |
| 9) NOTE: PLEASE SEE MISSING CWP AS PART OF THE GE |
| SYSTEM PER 250.50 |
| |
| 10) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF |
| EMERGENCY AND EXIT LIGHTS. |
| |
| 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR HWH. |
| 422.31 |
| |
| 12) NOTE: PLEASE SEE MISSING DISCONNECTS FOR AHU/ CU |
| PER 440.11. |
| |
| 13) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON |
| TITLE BLOCK FOR THE ARCHITECT OF RECORD PER FAC |
| 61G1-16.004. |
| |
| 14) NOTE: ** ARCHITECT OF RECORD NEEDS TO SEE FS |
| 481.221. |
| ONE COPY OF PLANS IS BEING RETAINED. |
| |
| ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED TO |
| SHOW CODE COMPLIANCE AND PLANS ARE NOT COMPLETE AT THIS |
| TIME, THERE MAY BE NEW COMMENTS WHEN PLANS ARE |
| RESUBMITTED DUE TO CHANGES AND INFORMATION BEING |
| SUBMITTED FOR THE FIRST TIME FOR REVIEW. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |