Date Text
2007-04-15 09:04:46** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SUBMIT COMPLETED PLANS FOR COMMERCIAL OFFICE
 BUILDING APPLICATION. AT THIS TIME THERE ARE MANY ITEMS
 ON PLANS WHICH ARE UNDER RESIDENTIAL DESIGN.
  
 2) NOTE: PLEASE SUBMIT COMPLETE PLANS WHICH ARE CLEAR
 AND VISIBLE FOR ALL ELECTRICAL CIRCUITS, DESIGNATIONS
 ETC ON PLANS. PLEASE SEE FBC 106.1.3 WHICH REQUIRES
 PLANS TO BE A MINIMUM OF QUALITY.
 THERE ARE SEVERAL ITEMS, CIRCUITS ON PLANS WHICH ARE
 NOT CLEAR.
 PLEASE SEE THERE ARE SOME CIRCUITS WHICH ARE INDICATED
 WHICH ARE NOT ON PANEL SCHEDULE.
 PLEASE SEE 408.4 OF THE NEC, AND THE FOLLOWING TEXT
 BELOW WHICH IS TAKEN DIRECTLY FROM THE NEC.
 PLEASE KNOW THAT THE PLANS NEED TO LABEL AND PROVIDE
 ROOM AND AREA DESIGNATIONS ON PLANS AND CORRELATE WITH
 THE PANEL SCHEDULES SHOWING ALL ROOMS AND AREAS IN
 WHICH CIRCUITS FEED WILL BE REQUIRED FOR EACH PANEL.
 PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE
 CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SUBMIT PLANS DESIGNED FOR COMMERCIAL
 LOAD CALCULATIONS.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 215.5,
 230.42 ETC.
 PLEASE SEE THERE ARE CIRCUITS WHICH ARE OVER LOADED.
 PLEASE SEE NO LOADS ARE SHOWN FOR COMMERCIAL
 APPLICATION.
  
 4) NOTE: PLEASE SUBMIT PLANS WHICH ARE COMPLIANT WITH
 THE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. PLEASE
 SEE 13-413.1ABC.1, 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2.
 NO FIXTURE LEGEND WAS SUBMITTED, NO ENERGY
 CALCULATIONS, NO PERFORMANCE CALCULATIONS, ETC
 AS PLANS DO NOT INDICATED ANY ELECTRICAL FOR EXISTING
 STRUCTURE, SOME OTHER ITEMS FOR CODE COMPLIANCE WITH
 RESPECT TO CHAPTER 13 CAN NOT BE DETERMINED AT THIS
 TIME.
  
 5) NOTE: PLEASE SEE PLANS INDICATE THIS AS AN ADDITION
 TO AN EXISTING STRUCTURE, HOWEVER HOW IS THIS EXISTING
 BEING FED FROM THE NEW ELECTRICAL SERVICE AS SHOWN.
 PLANS DO NOT SHOW CIRCUITING , FEEDS, OR INDICATE ANY
 ELECTRICAL FOR REVIEW.
 NO REVIEW FOR THIS CAN BE DONE AT THIS TIME.
 PLEASE SEE NEC 2005.
 FBC 106.1.2, 106.3.5.1.2
 COMPLETE PLANS.
  
 6) NOTE: PLEASE SEE 422.13 FOR LOADS FOR WATER HEATER.
  
 7) NOTE: PLEASE SEE BATH ROOMS WHICH ONLY INDICATE TWO
 FANS, NO CONTROL FOR THESE FANS AND NO LIGHTING IN
 THESE TWO BATH ROOMS??
 PLEASE COMPLETE PLANS.
 FBC 106.3.5.1.2
 LS 101 7.8
  
 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT PER 110.9.
  
 9) NOTE: PLEASE SEE MISSING CWP AS PART OF THE GE
 SYSTEM PER 250.50
  
 10) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS.
  
 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR HWH.
 422.31
  
 12) NOTE: PLEASE SEE MISSING DISCONNECTS FOR AHU/ CU
 PER 440.11.
  
 13) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON
 TITLE BLOCK FOR THE ARCHITECT OF RECORD PER FAC
 61G1-16.004.
  
 14) NOTE: ** ARCHITECT OF RECORD NEEDS TO SEE FS
 481.221.
 ONE COPY OF PLANS IS BEING RETAINED.
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED TO
 SHOW CODE COMPLIANCE AND PLANS ARE NOT COMPLETE AT THIS
 TIME, THERE MAY BE NEW COMMENTS WHEN PLANS ARE
 RESUBMITTED DUE TO CHANGES AND INFORMATION BEING
 SUBMITTED FOR THE FIRST TIME FOR REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  