Plan Review Notes
Plan Review Notes For Permit 07030449
Permit Number 07030449
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-26 10:41:54DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MORE INFORMATION IS REQUIRED. THE PERMIT
 APPLICATION STATES "MOVE AND CHANGE THE KITCHEN SINK.
 PLEASE INDICATE ON THE RESUBMITTAL WHERE THE PROPOSED
 LOCATION OF THEKITCHEN SINK IS.
 INDICATE ON A DRAWING THE EXISTING PLUMBING LAYOUT, AND
 ON A SEPERATE DRAWING PLEASE INDICATE THE NEW PROPOSED
 PLUMBING LAYOUT.
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE SUBMIT THE FOLLOWING
 INFORMATION REQUIRED IN COMMENT #2
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWOFAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 3. PERMIT APPLICATION STATES "REPLACE A WATER HEATER"
 . WHAT KIND OF A WATER HEATER IS BEING REPLACED, IS IT
 A GAS OR AN ELECTRIC WATER HEATER? PLEASE CLARIFY ON
 THE RESUBMITTAL.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  