Plan Review Notes
Plan Review Notes For Permit 07030437
Permit Number 07030437
Review Stop E
Sequence Number 3
Notes
Date Text
2007-07-02 13:08:24 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE RISER INDICATES A METER AND A PANEL, THE PLAN
 INDICATES A DISCONNECT AT THE METER AND THE PANEL
 INSIDE THE UNIT. PLEASE CORRELATE.
  
 2} CIRCUIT #27 MUST BE #12 WIRE ON A 20 AMP CIRCUIT TO
 COMPLY WITH 210.11(C)(1).
  
 3} INDICATE IF THE PROPOSED SERVICE IS OVERHEAD OR
 UNDERGROUND ON THE RISER. 215.5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718