Plan Review Notes For Permit 07030437 |
Permit Number |
07030437 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-07-02 13:08:24 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE RISER INDICATES A METER AND A PANEL, THE PLAN | | INDICATES A DISCONNECT AT THE METER AND THE PANEL | | INSIDE THE UNIT. PLEASE CORRELATE. | | | | 2} CIRCUIT #27 MUST BE #12 WIRE ON A 20 AMP CIRCUIT TO | | COMPLY WITH 210.11(C)(1). | | | | 3} INDICATE IF THE PROPOSED SERVICE IS OVERHEAD OR | | UNDERGROUND ON THE RISER. 215.5 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | | | | | | | |
|